4.5.3.2Output voltage 120Vac split-phase

1.The factory setting of the output tap (208Vac) has to be changed to 240Vac. Please refer to fig. 12 and 12a. Proceed as follows:

1.1Remove the yellow wire L from faston 67 (connect) and place this wire on faston 65 (park).

1.2Remove the brown wire F from faston 66 (park) and place this wire on faston 67 (connect).

Output tap factory setting: 208 Volt

Output tap changed to 240 Volt

(park)

(park)

(park)

(park)

(connect)

(connect)

Figure 12. LP 5/6/8/10-11U:

Output tap change

Figure 12a. LP 5/6/8/10-11U:

Rear view

2.Connect the load wires between the terminals 1 (L1) and 2 (N) (120V), and between the terminals 3 (N) and 4 (L2) (120V). Connect the ground wire to terminal 5. Ground connection is essential! Do not remove the link between terminals 2 and 3. See figure 13.

Figure 13. LP 5/6/8/10-11U:

120 Vac split-phase output connection

3.Return to either 4.5.1.1 step 5 or 4.5.1.2 step 5

LX: OPM_LPU_11U_5K0_10K_1US_V030

15

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Image 17
Contents Digital Energy LP 11U Page Digital Energy LP Series Important Safety Instructions Interfacing Features General Important Safety InstructionsInstallation Batteries StorageDescription WarrantyIntroduction Principles of Operation Functional ExplanationAutomatic Bypass Switch Package Contents InstallationTransport Unpacking LocationUPS model Tightening torque force Utility voltage UPS model 120V 208V 240VOutput voltage UPS model 120V 208V 240V LP 5/68/10-11U Standard installation procedure LP 5/6-11U Installation procedure 120V input Available input voltages hardware modifications Bypass tap factory setting 208 VoltInput voltage 208 or 240Vac Bypass tap changed to 240 VoltOutput voltage 208Vac Input voltage 120Vac optional, 5/6kVA onlyAvailable output voltages hardware modifications LP 5/6/8/10-11U Output tap change Output voltage 120Vac split-phaseOutput voltage 220/230/240Vac Output voltage 120Vac single phaseInput Voltage Setup ScreensInput Voltage Change to Output VoltageLP 5/6/8/10-11U Installation of battery pack Installation of parallel operating LP-U UPSs Autorestart OFF Press Enter Autorestart OFF Setting MismatchECO-mode MaintenanceNo-load shutdown Manual bypassDescription of Front and Rear Panel OperationRear panel Step-up transformer Rear panel of the step-up transformerSelftest Progress Start-upUse Battery 23CInput Line Autonomy Time Left Operating Time 0YEAR 29DAYSTemp TOO High On Line Alarm Press UPStatus and Alarm Menu Inverter OFF Battery Charger no Float Capacitor C1 Capacity LOWBattery Depleted Service Menu Service ScreensInput and Output not Synchronized Software Version R2.9 FAN Speed INV.DC +Tstamp Q4 Automatic Bypass EnabledOutput Frequency Language English Input Voltage Output VoltageFrequency Range 2% PLL Lock Speed Normal FAN CurveTest Screens Automatic Bypass Enabled Service Warning DisabledQuick Battery Test Start Calibrate BAT Test Activated Deep Battery TestProcedure Overload protection in bypass mode Other FeaturesShutdown Utility startECO Superior Battery ManagementAuto Restart OFF Press Enter Auto restartRS232 / contact interface Interfacing FeaturesEmergency shutdown Relay Card optional Snmp Interface optionalExtended Runtime Optional FeaturesPlug-in Cards RPA-Facility Redundant Parallel ArchitectureSeismic anchors PDM Power Distribution ModuleSafety MaintenanceRecycling the UPS at the end of service life Cooling fanSelftest Failure Q4 not OK TroubleshootingSelftest Failure Temp TOO High UPS Type 11U 10-11U SpecificationsAutomatic Bypass Switch Enclosure Center of Gravity Dimensions Conduit BoxLP 5/6/8/10-11U installation drawings LP 5/6/8/10-11U 208-240V input LP 5/6-11U 120V input