GE LP11U Utility voltage UPS model 120V 208V 240V, Output voltage UPS model 120V 208V 240V

Page 12

g

Digital EnergyLP Series

Ensure that the total power requirement of the equipment to be protected does not exceed the rated

 

output power of the UPS. (output power for your unit is indicated on the rating label on the rear panel).

When using the 120V split phase outputs make sure that the load per 120V output does not exceed half

 

the rating.

 

 

 

 

 

 

 

The UPS may only be installed by trained personnel. The UPS must be grounded when in use: Connect

 

the UPS to a single phase, three wire AC source equipped with an earth connection.

Use insulated copper input and output wiring, rated 90°C derated to 40°C, wire size based on the

 

ampacities given in Tables 310-16 of the National Electrical code, ANSI/NFPA 70-1993.

 

This wiring shall have the following minimum sizes:

 

INPUT WIRING:

 

 

 

 

 

 

 

 

 

 

 

 

Utility voltage

 

 

 

UPS model

 

120V

 

208V

 

240V

 

 

LP 5-11U

 

6 AWG

 

10 AWG

 

10 AWG

 

 

LP 6-11U

 

4 AWG

 

8 AWG

 

10 AWG

 

 

LP 8-11U

 

N/A

 

6 AWG

 

8 AWG

 

 

LP 10-11U

 

N/A

 

4 AWG

 

6 AWG

 

 

Table 2. Input wiring

 

 

 

 

 

 

OUTPUT WIRING:

 

 

 

 

 

 

 

 

 

 

 

 

Output voltage

 

 

UPS model

 

120V

 

208V

 

240V

 

 

LP 5-11U

 

8 AWG

 

10 AWG

 

10 AWG

 

 

LP 6-11U

 

8 AWG

 

10 AWG

 

10 AWG

 

 

LP 8-11U

 

6 AWG

 

8 AWG

 

8 AWG

 

 

LP 10-11U

 

4 AWG

 

8 AWG

 

8 AWG

 

 

Table 3. Output wiring

 

 

 

 

 

 

TIGHTENING TORQUE FORCE:

 

 

 

UPS model

 

Tightening torque force

 

 

LP 5/6-11U/120V

 

22

Lbs/inch

 

 

 

All other models

 

18-20 Lbs/inch

 

 

Table 4. Tightening torque force

LX: OPM_LPU_11U_5K0_10K_1US_V030

10

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Image 12
Contents Digital Energy LP 11U Page Digital Energy LP Series Important Safety Instructions Interfacing Features Important Safety Instructions InstallationGeneral Storage BatteriesWarranty IntroductionDescription Functional Explanation Principles of OperationAutomatic Bypass Switch Installation Package ContentsTransport Unpacking LocationUtility voltage UPS model 120V 208V 240V Output voltage UPS model 120V 208V 240VUPS model Tightening torque force LP 5/68/10-11U Standard installation procedure LP 5/6-11U Installation procedure 120V input Bypass tap factory setting 208 Volt Available input voltages hardware modificationsInput voltage 208 or 240Vac Bypass tap changed to 240 VoltInput voltage 120Vac optional, 5/6kVA only Available output voltages hardware modificationsOutput voltage 208Vac Output voltage 120Vac split-phase LP 5/6/8/10-11U Output tap changeOutput voltage 120Vac single phase Output voltage 220/230/240VacSetup Screens Input VoltageInput Voltage Change to Output VoltageLP 5/6/8/10-11U Installation of battery pack Installation of parallel operating LP-U UPSs Autorestart OFF Setting Mismatch Autorestart OFF Press EnterMaintenance ECO-modeNo-load shutdown Manual bypassOperation Description of Front and Rear PanelRear panel of the step-up transformer Rear panel Step-up transformerStart-up Selftest ProgressBattery 23C UseInput Line Autonomy Time Left Operating Time 0YEAR 29DAYSOn Line Alarm Press UP Status and Alarm MenuTemp TOO High Battery Charger no Float Capacitor C1 Capacity LOW Battery DepletedInverter OFF Service Screens Service MenuInput and Output not Synchronized Software Version R2.9 FAN Speed INV.DC +Automatic Bypass Enabled Tstamp Q4Language English Input Voltage Output Voltage Output FrequencyFrequency Range 2% PLL Lock Speed Normal FAN CurveAutomatic Bypass Enabled Service Warning Disabled Quick Battery Test StartTest Screens Deep Battery Test ProcedureCalibrate BAT Test Activated Other Features Overload protection in bypass modeShutdown Utility startSuperior Battery Management ECOAuto Restart OFF Press Enter Auto restartInterfacing Features RS232 / contact interfaceEmergency shutdown Relay Card optional Snmp Interface optionalOptional Features Extended RuntimePlug-in Cards RPA-Facility Redundant Parallel ArchitecturePDM Power Distribution Module Seismic anchorsMaintenance SafetyRecycling the UPS at the end of service life Cooling fanTroubleshooting Selftest Failure Temp TOO HighSelftest Failure Q4 not OK Specifications UPS Type 11U 10-11UAutomatic Bypass Switch Enclosure Dimensions Conduit Box Center of GravityLP 5/6/8/10-11U installation drawings LP 5/6/8/10-11U 208-240V input LP 5/6-11U 120V input