GE LP11U user manual ECO-mode, No-load shutdown, Manual bypass, Maintenance

Page 23

g

Digital EnergyLP Series

4.5.6.3 Notes concerning use / maintenance of a parallel system

ECO-mode:

If LP-U units operate in parallel, the ECO-mode feature is not available.

No-load shutdown:

If LP-U units operate in parallel, the no-load shutdown function is not available.

Manual bypass:

If you want to switch one of the UPSs to bypass operation using the manual bypass switch (switch is turned into position 2) then all UPSs in the parallel system have to be switched to bypass operation in order to prevent damage.

Maintenance:

To isolate a unit from the redundant system:

1.Switch off the UPS which has to be isolated,

2.Remove the installation fuse from the input of that UPS (F1-4 in figure 17),

3.Separate the output of the UPS from the output junction (S1-4 in figure 17).

To re-enter the unit into the system:

4.Reinstall the installation input fuse,

5.Connect the output of the UPS to the output junction,

6.Switch on the UPS.

LX: OPM_LPU_11U_5K0_10K_1US_V030

21

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Image 23
Contents Digital Energy LP 11U Page Digital Energy LP Series Important Safety Instructions Interfacing Features General Important Safety InstructionsInstallation Batteries StorageDescription WarrantyIntroduction Principles of Operation Functional ExplanationAutomatic Bypass Switch Location InstallationPackage Contents Transport UnpackingUPS model Tightening torque force Utility voltage UPS model 120V 208V 240VOutput voltage UPS model 120V 208V 240V LP 5/68/10-11U Standard installation procedure LP 5/6-11U Installation procedure 120V input Bypass tap changed to 240 Volt Bypass tap factory setting 208 VoltAvailable input voltages hardware modifications Input voltage 208 or 240VacOutput voltage 208Vac Input voltage 120Vac optional, 5/6kVA onlyAvailable output voltages hardware modifications LP 5/6/8/10-11U Output tap change Output voltage 120Vac split-phaseOutput voltage 220/230/240Vac Output voltage 120Vac single phaseOutput Voltage Setup ScreensInput Voltage Input Voltage Change to LP 5/6/8/10-11U Installation of battery pack Installation of parallel operating LP-U UPSs Autorestart OFF Press Enter Autorestart OFF Setting MismatchManual bypass MaintenanceECO-mode No-load shutdownDescription of Front and Rear Panel OperationRear panel Step-up transformer Rear panel of the step-up transformerSelftest Progress Start-upAutonomy Time Left Operating Time 0YEAR 29DAYS Battery 23CUse Input LineTemp TOO High On Line Alarm Press UPStatus and Alarm Menu Inverter OFF Battery Charger no Float Capacitor C1 Capacity LOWBattery Depleted Software Version R2.9 FAN Speed INV.DC + Service ScreensService Menu Input and Output not SynchronizedTstamp Q4 Automatic Bypass EnabledFAN Curve Language English Input Voltage Output VoltageOutput Frequency Frequency Range 2% PLL Lock Speed NormalTest Screens Automatic Bypass Enabled Service Warning DisabledQuick Battery Test Start Calibrate BAT Test Activated Deep Battery TestProcedure Utility start Other FeaturesOverload protection in bypass mode ShutdownAuto restart Superior Battery ManagementECO Auto Restart OFF Press EnterRelay Card optional Snmp Interface optional Interfacing FeaturesRS232 / contact interface Emergency shutdownRPA-Facility Redundant Parallel Architecture Optional FeaturesExtended Runtime Plug-in CardsSeismic anchors PDM Power Distribution ModuleCooling fan MaintenanceSafety Recycling the UPS at the end of service lifeSelftest Failure Q4 not OK TroubleshootingSelftest Failure Temp TOO High UPS Type 11U 10-11U SpecificationsAutomatic Bypass Switch Enclosure Center of Gravity Dimensions Conduit BoxLP 5/6/8/10-11U installation drawings LP 5/6/8/10-11U 208-240V input LP 5/6-11U 120V input