GE LP11U user manual Eco, Auto Restart OFF Press Enter, Auto restart, Superior Battery Management

Page 36

g

Digital EnergyLP Series

5.5.5ECO-mode

The UPS is equipped with the ‘ECO-mode’ feature. If the feature is enabled, the load is operated on utility through the electronic bypass switch. If the utility is interrupted or out of limits the load is automatically transferred to the inverter. Operating the load on utility improves the efficiency of the UPS with 5-8% and saves on energy costs. We advise not to use the ECO-mode in case of an unstable utility.

After enabling the ECO-mode (please refer to service screens 5.3.3) the standard menu changes to:

LP 5-11U

 

LOAD 37%

ECO

NOTE: If LP-U units operate in parallel, the ECO-mode feature is not available.

5.5.6Auto restart

If this feature is enabled and the unit has shut down (e.g. due to overload) the UPS will start up automatically when the normal situation is restored. The off-factory setting is: enabled.

If the auto restart feature is disabled the unit will not automatically restart when the normal situation is restored but the display will show:

AUTO RESTART OFF

PRESS ENTER

After ‘Enter’ the unit will restart. See also 5.3.3 ‘service screens’.

5.5.7Superior Battery Management

-Load dependent battery-end voltage: The allowable final battery voltage depends on the discharge

current: the higher the current, the lower the 'end-of-discharge' battery voltage. This gives maximum capacity without over discharging. Over discharging results in failure to recover normal capacity and in shortened battery life.

-Equalize mode: When switched on for the first time the UPS will start boost-charging the batteries for 15 hours in order to equalize all battery voltages.

-Boost mode: If after a discharge the battery voltage is lower than 240Vdc, the UPS will charge the batteries with a boost charge voltage of 285Vdc. This enables fast recharging of the batteries. The programmed battery charging mode will change from boost charge into float charge after boost charging twice.

-Temperature compensated battery charging: This feature reduces the battery charge voltage with increasing temperature (-18mV/°C or -32.4mV/°F per 12V battery). As a result poor charging of the batteries under low temperature conditions and overcharging of the batteries under high temperature conditions are prevented.

LX: OPM_LPU_11U_5K0_10K_1US_V030

34

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Image 36
Contents Digital Energy LP 11U Page Digital Energy LP Series Important Safety Instructions Interfacing Features Important Safety Instructions InstallationGeneral Storage BatteriesWarranty IntroductionDescription Functional Explanation Principles of OperationAutomatic Bypass Switch Installation Package ContentsTransport Unpacking LocationUtility voltage UPS model 120V 208V 240V Output voltage UPS model 120V 208V 240VUPS model Tightening torque force LP 5/68/10-11U Standard installation procedure LP 5/6-11U Installation procedure 120V input Bypass tap factory setting 208 Volt Available input voltages hardware modificationsInput voltage 208 or 240Vac Bypass tap changed to 240 VoltInput voltage 120Vac optional, 5/6kVA only Available output voltages hardware modificationsOutput voltage 208Vac Output voltage 120Vac split-phase LP 5/6/8/10-11U Output tap changeOutput voltage 120Vac single phase Output voltage 220/230/240VacSetup Screens Input VoltageInput Voltage Change to Output VoltageLP 5/6/8/10-11U Installation of battery pack Installation of parallel operating LP-U UPSs Autorestart OFF Setting Mismatch Autorestart OFF Press EnterMaintenance ECO-modeNo-load shutdown Manual bypassOperation Description of Front and Rear PanelRear panel of the step-up transformer Rear panel Step-up transformerStart-up Selftest ProgressBattery 23C UseInput Line Autonomy Time Left Operating Time 0YEAR 29DAYSOn Line Alarm Press UP Status and Alarm MenuTemp TOO High Battery Charger no Float Capacitor C1 Capacity LOW Battery DepletedInverter OFF Service Screens Service MenuInput and Output not Synchronized Software Version R2.9 FAN Speed INV.DC +Automatic Bypass Enabled Tstamp Q4Language English Input Voltage Output Voltage Output FrequencyFrequency Range 2% PLL Lock Speed Normal FAN Curve Automatic Bypass Enabled Service Warning Disabled Quick Battery Test Start Test Screens Deep Battery Test ProcedureCalibrate BAT Test Activated Other Features Overload protection in bypass modeShutdown Utility startSuperior Battery Management ECOAuto Restart OFF Press Enter Auto restartInterfacing Features RS232 / contact interfaceEmergency shutdown Relay Card optional Snmp Interface optionalOptional Features Extended RuntimePlug-in Cards RPA-Facility Redundant Parallel ArchitecturePDM Power Distribution Module Seismic anchorsMaintenance SafetyRecycling the UPS at the end of service life Cooling fanTroubleshooting Selftest Failure Temp TOO HighSelftest Failure Q4 not OK Specifications UPS Type 11U 10-11UAutomatic Bypass Switch Enclosure Dimensions Conduit Box Center of GravityLP 5/6/8/10-11U installation drawings LP 5/6/8/10-11U 208-240V input LP 5/6-11U 120V input