GE LP11U user manual Input and Output not Synchronized, Service Screens, Service Menu

Page 30

g

INPUT AND OUTPUT NOT SYNCHRONIZED

Digital EnergyLP Series

The output converter frequency is not synchronized to the utility (input) frequency. In this situation the automatic bypass switch is not able to transfer the load from output converter to bypass and reverse: automatic bypass operation is inhibited: if for whatever reason the output converter is unable to deliver the required output, output power is lost. (see section 3.5).

Synchronization is only possible if the utility frequency remains within certain limits (see chapter 10).

BATTERY RUNTIME LEFT 0:09:41

OUTPUT OFF

NO INPUT POWER

PROG. SHUTDOWN WITHIN 0:09:17

PROG. SHUTDOWN LEFT 0:14:03

SHUTDOWN ALARM PRESS UP

IMMEDIATE

SHUTDOWN

5.3.3 Service Menu

The remaining runtime. This figure is counted down during battery operation until either the utility returns or the batteries are depleted.

The output is switched off due to a faulty situation, indicated by the second line.

The output will be switched off by a remote command (RS232/SNMP). The second line indicates the time until shutdown.

The output is switched off by a remote command (RS232/SNMP). The second line indicates the time until wake-up.

The output is switched off by the 'no-load shutdown' feature: no input voltage and load <2%. If the input voltage is restored, the output will be available again. See also section 5.5.1

The wire on connector J3 pin 3-4 (rear panel, plug-in card 12) is interrupted. The output is no longer available. To restart the unit, restore the connection and turn the on/off switch (rear panel, 7) off and on again.

When the default screen is displayed you can enter the first service screen by depressing the keys 'down' (2) and 'Enter/Reset' (3) simultaneously for approx. 1 second. Using the 'up' (4) and 'down' (2) keys you can scroll through several service screens.

SERVICE SCREENS

ENTER exit

SERIAL NUMBER l051U01/0020A030

SOFTWARE VERSION R2.9; 640777

FAN SPEED

10

INV.DC: +

375

 

 

HEATSI.TEMP: 0

TRANSF.TEMP: 310

FLOAT CHARGE: 1

OUTPUT FAST : 0

The intro service screen. 'Enter/Reset' returns to the default screen.

The serial number of the UPS.

Release number of the installed software and production code of the UPS.

Service information about fan speed (min. 10, max. 30) and internal DC voltage.

Service information on internal temperature levels, values in mV over the temperature sensors.

First line: service information on charger. ‘1’ = batteries have reached float voltage.

Second line: service information on output converter.

LX: OPM_LPU_11U_5K0_10K_1US_V030

28

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Image 30
Contents Digital Energy LP 11U Page Digital Energy LP Series Important Safety Instructions Interfacing Features Important Safety Instructions InstallationGeneral Storage BatteriesWarranty IntroductionDescription Functional Explanation Principles of OperationAutomatic Bypass Switch Transport Unpacking InstallationPackage Contents LocationUtility voltage UPS model 120V 208V 240V Output voltage UPS model 120V 208V 240VUPS model Tightening torque force LP 5/68/10-11U Standard installation procedure LP 5/6-11U Installation procedure 120V input Input voltage 208 or 240Vac Bypass tap factory setting 208 VoltAvailable input voltages hardware modifications Bypass tap changed to 240 VoltInput voltage 120Vac optional, 5/6kVA only Available output voltages hardware modificationsOutput voltage 208Vac Output voltage 120Vac split-phase LP 5/6/8/10-11U Output tap changeOutput voltage 120Vac single phase Output voltage 220/230/240VacInput Voltage Change to Setup ScreensInput Voltage Output VoltageLP 5/6/8/10-11U Installation of battery pack Installation of parallel operating LP-U UPSs Autorestart OFF Setting Mismatch Autorestart OFF Press EnterNo-load shutdown MaintenanceECO-mode Manual bypassOperation Description of Front and Rear PanelRear panel of the step-up transformer Rear panel Step-up transformerStart-up Selftest Progress Input Line Battery 23C Use Autonomy Time Left Operating Time 0YEAR 29DAYSOn Line Alarm Press UP Status and Alarm MenuTemp TOO High Battery Charger no Float Capacitor C1 Capacity LOW Battery DepletedInverter OFF Input and Output not Synchronized Service ScreensService Menu Software Version R2.9 FAN Speed INV.DC +Automatic Bypass Enabled Tstamp Q4Frequency Range 2% PLL Lock Speed Normal Language English Input Voltage Output VoltageOutput Frequency FAN CurveAutomatic Bypass Enabled Service Warning Disabled Quick Battery Test StartTest Screens Deep Battery Test ProcedureCalibrate BAT Test Activated Shutdown Other FeaturesOverload protection in bypass mode Utility startAuto Restart OFF Press Enter Superior Battery ManagementECO Auto restartEmergency shutdown Interfacing FeaturesRS232 / contact interface Relay Card optional Snmp Interface optionalPlug-in Cards Optional FeaturesExtended Runtime RPA-Facility Redundant Parallel ArchitecturePDM Power Distribution Module Seismic anchorsRecycling the UPS at the end of service life MaintenanceSafety Cooling fanTroubleshooting Selftest Failure Temp TOO HighSelftest Failure Q4 not OK Specifications UPS Type 11U 10-11UAutomatic Bypass Switch Enclosure Dimensions Conduit Box Center of GravityLP 5/6/8/10-11U installation drawings LP 5/6/8/10-11U 208-240V input LP 5/6-11U 120V input