GE LP11U user manual Installation of parallel operating LP-U UPSs

Page 21

g

Digital EnergyLP Series

4.5.6 LP 11U series: 2 / 3 / 4 parallel operating units – additional info

The RPA option (Redundant Parallel Architecture) allows you to create a redundant UPS system in which 2, 3 or 4 LP-U units operate in parallel. The following should be considered when installing units in parallel.

This section gives aditional information on:

-installation (4.5.6.1)

-start-up (4.5.6.2)

-use / maintenance (4.5.6.3)

4.5.6.1Notes concerning installation of a parallel system

1.All inputs of the UPSs must be supplied from the same phase. This is to enable bypass operation of the parallel system. All inputs must be individually protected by fuses in the installation. The values of these fuses should correspond to the values mentioned in section 4.5 table 1.

2.All outputs must be connected together, supplying the load. It is advised to install switches (S 1-4, fig. 17) in the output wiring, in order to be able to isolate a unit from the remaining system for service and maintenance purposes. It is advised to make a Neutral-to-Ground bounding in the output junction.

3.The diameter of input and output cables must be according to the table in the installation drawings (see appendix). Cables with different diameters can cause tripping fuses in the UPS and/or the installation.

4.The length of all input cables from the input junction (Li, fig. 17) to the UPS inputs should be equal. The same applies to the cables from the outputs to the output junction (Lo, fig. 17). The minimum length of the input as well as the output cables is 3 meters / 10 feet.

1-PHASE 3-WIRE INPUT

INPUT JUNCTION

F1-4

DISTRIBUTION FUSE VALUES ACCORDING TO TABLE 1

BUS

TERMINATOR

IN

IN

 

IN

 

IN

LP-UPS

LP-UPS

 

LP-UPS

 

LP-UPS

 

 

 

 

 

 

 

RPA CARD

 

RPA CARD

 

RPA CARD

 

RPA CARD

OUT

OUT

 

OUT

 

OUT

S 1-4

SWITCH ALLOWS

ISOLATION OF A UNIT

FROM THE SYSTEM

 

 

OUTPUT JUNCTION

Li/Lo: LENGTH OF I/O WIRING

MAKE

YELLOW NETWORK

- EQUAL FOR EACH UPS

NEUTRAL-TO-GROUND

CABLES AS DELIVERED

- MINIMUM 3 METERS / 9.8 FEET

BOUNDING HERE

WITH THE UPS

 

 

TO LOAD

BUS

TERMINATOR

Figure 17. Installation of parallel operating LP-U UPSs

LX: OPM_LPU_11U_5K0_10K_1US_V030

19

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Image 21
Contents Digital Energy LP 11U Page Digital Energy LP Series Important Safety Instructions Interfacing Features Important Safety Instructions InstallationGeneral Batteries StorageWarranty IntroductionDescription Principles of Operation Functional ExplanationAutomatic Bypass Switch Package Contents InstallationTransport Unpacking LocationUtility voltage UPS model 120V 208V 240V Output voltage UPS model 120V 208V 240VUPS model Tightening torque force LP 5/68/10-11U Standard installation procedure LP 5/6-11U Installation procedure 120V input Available input voltages hardware modifications Bypass tap factory setting 208 VoltInput voltage 208 or 240Vac Bypass tap changed to 240 VoltInput voltage 120Vac optional, 5/6kVA only Available output voltages hardware modificationsOutput voltage 208Vac LP 5/6/8/10-11U Output tap change Output voltage 120Vac split-phaseOutput voltage 220/230/240Vac Output voltage 120Vac single phaseInput Voltage Setup ScreensInput Voltage Change to Output VoltageLP 5/6/8/10-11U Installation of battery pack Installation of parallel operating LP-U UPSs Autorestart OFF Press Enter Autorestart OFF Setting MismatchECO-mode MaintenanceNo-load shutdown Manual bypassDescription of Front and Rear Panel OperationRear panel Step-up transformer Rear panel of the step-up transformerSelftest Progress Start-upUse Battery 23CInput Line Autonomy Time Left Operating Time 0YEAR 29DAYSOn Line Alarm Press UP Status and Alarm MenuTemp TOO High Battery Charger no Float Capacitor C1 Capacity LOW Battery DepletedInverter OFF Service Menu Service ScreensInput and Output not Synchronized Software Version R2.9 FAN Speed INV.DC +Tstamp Q4 Automatic Bypass EnabledOutput Frequency Language English Input Voltage Output VoltageFrequency Range 2% PLL Lock Speed Normal FAN CurveAutomatic Bypass Enabled Service Warning Disabled Quick Battery Test StartTest Screens Deep Battery Test ProcedureCalibrate BAT Test Activated Overload protection in bypass mode Other FeaturesShutdown Utility startECO Superior Battery ManagementAuto Restart OFF Press Enter Auto restartRS232 / contact interface Interfacing FeaturesEmergency shutdown Relay Card optional Snmp Interface optionalExtended Runtime Optional FeaturesPlug-in Cards RPA-Facility Redundant Parallel ArchitectureSeismic anchors PDM Power Distribution ModuleSafety MaintenanceRecycling the UPS at the end of service life Cooling fanTroubleshooting Selftest Failure Temp TOO HighSelftest Failure Q4 not OK UPS Type 11U 10-11U SpecificationsAutomatic Bypass Switch Enclosure Center of Gravity Dimensions Conduit BoxLP 5/6/8/10-11U installation drawings LP 5/6/8/10-11U 208-240V input LP 5/6-11U 120V input