g
Digital Energy™ LP Series
10 - Specifications
UPS Type |
| : |
|
|
| |||
Output power (kVA/kW) |
| : | 5/4 |
| 6/4.8 | 8/6.4 | 10/8 | |
AC input voltage |
| : 120/208/240 Vac (120V only with | ||||||
Input frequency |
| : | 60/50 Hz |
|
|
| ||
AC output voltage |
| : | 120/208/220/230/240V |
|
| |||
Output frequency |
| : 60 or 50 Hz, std. 60 Hz; selectable on front | ||||||
System efficiency (full load) |
| : | 87% |
|
|
|
| |
Line input breaker |
| : | 32A |
| 32A | 50A | 63A | |
Bypass input breaker |
| : | 32A |
| 32A | 50A | 63A | |
Battery safety fuse (F4A) |
| : | 30A |
| 30A | 30A | 30A | |
Battery safety fuse (F4B) |
| : | 30A (spare) | 30A (spare) | 30A | 30A | ||
Internal safety fuse (F5A) |
| : | - |
| - | 30A | 30A | |
Internal safety fuse (F5B) |
| : | 30A |
| 30A | 30A | 30A | |
Input/output connectors |
| : terminals at rear of unit |
|
| ||||
INPUT |
|
|
|
|
|
|
|
|
AC input voltage range |
|
|
|
|
|
|
| |
at 100% load |
| : | 162 - 285 V |
|
|
| ||
at | 50% load |
| : | 146 - 285 V |
|
|
| |
at | 20% load |
| : | 133 - 285 V |
|
|
| |
AC input voltage range (120V, |
|
|
|
|
|
| ||
at 100% load |
| : | 81 - 141 V |
|
|
| ||
at | 50% load |
| : | 72 - 141 V |
|
|
| |
at | 20% load |
| : | 66 - 141 V |
|
|
| |
Input frequency range |
| : |
|
|
| |||
Input current wave form |
| : | sinusoidal |
|
|
| ||
Input power factor |
| : | ≥ 0.99 |
|
|
|
| |
Max. input current at 100% load | 120V | : | 43.3A |
| 50.8A | n.a. | n.a. | |
|
| 208V | : | 25.0A |
| 30.0A | 40.5 | 50.3 |
|
| 240V | : | 21.4A |
| 25.1 | 34.8 | 42.0 |
Inrush current |
| : | none |
|
|
|
| |
Rectified DC voltage out |
| : | 380 V |
|
|
|
| |
BATTERY CHARGER |
|
|
|
|
|
|
| |
Characteristic |
| : | current | charging until boost/float voltage, then | ||||
|
|
|
| constant voltage charging and boost charge mode for fast recharging of | ||||
|
|
|
| batteries |
|
|
| |
DC input voltage range |
| : |
|
|
| |||
DC output voltage at 20 °C |
| : | float: 273 V | boost: 295 V |
|
| ||
Output current limit (Adc) |
| : | 2.0 |
| 2.0 | 3.0 | 3.0 | |
OUTPUT CONVERTER |
|
|
|
|
|
|
| |
Output power at pf. = 0.8, VA* |
| : | 5000 |
| 6000 | 8000 | 10000 | |
Semiconductor |
| : | IGBT |
|
|
|
| |
AC output voltage |
| : 120/208/240V ± 1% static resistive load | ||||||
|
|
|
| 120/208/240V ± 2% measured crest load 2.5:1 | ||||
|
|
|
| 120/208/240V ± 2% dynamic mean deviation over one half cycle for 100% of | ||||
|
|
|
| rated load applied or removed |
| |||
Typical overload |
| : | 110% ≥ | 20 minutes |
|
| ||
(temp. dependent) |
|
| 130% ≥ | 3.5 minutes |
|
| ||
|
|
|
| 150% ≥ | 2 minutes |
|
| |
Output frequency |
| : 60 or 50 Hz selectable, ± 0.1%, unless synchronized with the utility | ||||||
Freq. tracking range |
| : ± 2/4/6% of nominal, user selectable |
| |||||
Output wave form |
| : | sine wave |
|
|
| ||
Max. phase difference |
| : | max 7° |
|
|
|
| |
Harmonic distortion |
| : 2% max. with linear load |
|
| ||||
Power factor range |
| : | Any lagging or leading power factor permitted within the specified rating to | |||||
|
|
|
| pf. 0.5 |
|
|
|
|
Output derating altitude |
| : Till 1000m no derating |
|
| ||||
|
|
|
| Above 1000m 12.5% per 1000m, max. 4000m | ||||
Protection |
| : Automatic shut down (or transfer to bypass, if bypass is available) in case of |
-low/high DC voltage
-overtemperature
-overload / short circuit
The output is protected against connection to the utility supply * according to EN
LX: OPM_LPU_11U_5K0_10K_1US_V030 | 40 | GE DE LP 11U UPS: Installation / User Manual 3.0 (US) |