g
BATTERY CHARGER NO FLOAT
CAPACITOR C1
CAPACITY LOW
LOADnotPROTECTED
INVERTER OFF
LOADnotPROTECTED
BATTERY DEPLETED
LOADnotPROTECTED
BATTERY LOW
UPS SHUTDOWN LEFT 2 MINUTES
BYPASS ERROR
FUSE FAILURE
INPUT ERROR
FUSE FAILURE
INTERNAL BATTERY FUSE FAILURE
EXTERNAL BATTERY FUSE FAILURE
REPLACE BATTERY
INPUT out LIMITS
137V 60.0Hz
BYPASSoutLIMITS
197V 60.0Hz
Digital Energy™ LP Series
After 24 hours of charging time, the battery voltage did not reach the normal float voltage. This may be caused by faulty batteries, too many battery packs connected or a charger fault.
The main
Due to a failure the output converter's output is not available. As a result the load may have been transferred to bypass.
The remaining runtime is zero. As a result the load may have been transferred to bypass.
The remaining run time is less than the set time (standard 2 minutes). This text alternates with the following screen:
The output voltage can be lost after the indicated time due to discharged battery. Controlled shutdown of any computer equipment is absolutely necessary at this point. (Using the RS232 or SNMP communications interface, this procedure can be initiated automatically on unattended systems). If the UPS operates at 100% load, the shutdown procedure should be completed within 2 minutes after the 'battery low' alarm started. When the batteries are fully discharged, the UPS is no longer able to power the connected equipment.
The static bypass circuit breaker (rear panel, 9) is in 'off' (down position): no bypass voltage available. Utility voltage is available. If not manually operated, this may have been caused by an overload situation.
The utility circuit breaker (rear panel, 8) is in the 'off' (down position): no line voltage available, bypass voltage is available. If not manually operated, this may have been caused by an internal system failure.
The internal battery fuse is defective; this may have been caused by an internal system failure. This alarm also appears if no batteries are installed.
The
The batteries are (almost) chemically worn out. If the batteries are aged, they must be replaced as soon as possible to ensure full protection for your equipment (see section 8.3).
The utility voltage or utility frequency are outside UPS input tolerance (see chapter 10, specifications)
The utility voltage or utility frequency are outside bypass input tolerance but inside UPS (rectifier) input tolerance (see chapter 10, specifications). Bypass operation is inhibited: if for whatever reason the output converter is unable to deliver the required output, output power is lost.
LX: OPM_LPU_11U_5K0_10K_1US_V030 | 27 | GE DE LP 11U UPS: Installation / User Manual 3.0 (US) |