g
Digital Energy™ LP Series
5.3Use
Once the unit is in operation, there is no need to switch the unit on/off during use.
If the manual bypass switch (rear panel, 10) is in position '1', switching off by the on/off switch (rear panel, 7) results in a total absence of the output voltage (also the bypass voltage) of at least 5 secs.
If an emergency shutdown switch has been installed (see
The UPS is operated via the
The menus on the display can be divided into 5 groups:
1standard screen
2information menu (5.3.1)
3status- and alarm menu (5.3.2)
4 service menu (5.3.3)
5
The standard menu shows UPS model and actual load.
LP 5-11U
LOAD 37%
5.3.1 Information Menu
When the default screen is displayed the first information screen can be entered by depressing the 'up' key (front panel, 4). Using the 'up' and 'down' keys (front panel, 4 and 2) you can scroll through several information screens. After the last information screen the default screen will appear.
The screens display the following information:
INPUT LINE 208V
2.45kW 60Hz
OUTPUT 208V LOAD 50% 60.0Hz
BATTERY 23°C
271V 1.9A
AUTONOMY TIME LEFT 5:27:00
OPERATING TIME 0YEAR 29DAYS
Utility voltage and utility frequency, and the power delivered by the utility.
Output voltages and output frequency, and the power delivered by the UPS (as % of the nominal UPS rating).
The temperature near the batteries, the battery voltage and the battery current (charging: + value, discharging: - value).
The remaining battery runtime (or autonomy) during a utility failure.
The total operating time of the UPS.
LX: OPM_LPU_11U_5K0_10K_1US_V030 | 25 | GE DE LP 11U UPS: Installation / User Manual 3.0 (US) |