Digital EnergyLP Series

5.3Use

Once the unit is in operation, there is no need to switch the unit on/off during use.

If the manual bypass switch (rear panel, 10) is in position '1', switching off by the on/off switch (rear panel, 7) results in a total absence of the output voltage (also the bypass voltage) of at least 5 secs.

If an emergency shutdown switch has been installed (see 4.5.1.1-2, step 6) the UPS will stop immediately when the switch is opened. Restart is only possible after closing the switch and turning the UPS off and on again with the UPS on/off switch (rear panel, 7).

The UPS is operated via the push-buttons (front panel, 2-3-4) and the LCD display (front panel, 1). Furthermore the UPS can be controlled via the RS232/contact interface port (rear panel, 12a). For more information see 6.1.

The menus on the display can be divided into 5 groups:

1standard screen

2information menu (5.3.1)

3status- and alarm menu (5.3.2)

4 service menu (5.3.3)

5 set-up menu (5.3.4)

The standard menu shows UPS model and actual load.

LP 5-11U

LOAD 37%

5.3.1 Information Menu

When the default screen is displayed the first information screen can be entered by depressing the 'up' key (front panel, 4). Using the 'up' and 'down' keys (front panel, 4 and 2) you can scroll through several information screens. After the last information screen the default screen will appear.

The screens display the following information:

INPUT LINE 208V

2.45kW 60Hz

OUTPUT 208V LOAD 50% 60.0Hz

BATTERY 23°C

271V 1.9A

AUTONOMY TIME LEFT 5:27:00

OPERATING TIME 0YEAR 29DAYS

Utility voltage and utility frequency, and the power delivered by the utility.

Output voltages and output frequency, and the power delivered by the UPS (as % of the nominal UPS rating).

The temperature near the batteries, the battery voltage and the battery current (charging: + value, discharging: - value).

The remaining battery runtime (or autonomy) during a utility failure.

The total operating time of the UPS.

LX: OPM_LPU_11U_5K0_10K_1US_V030

25

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Image 27
Contents Digital Energy LP 11U Page Digital Energy LP Series Important Safety Instructions Interfacing Features Important Safety Instructions InstallationGeneral Batteries StorageWarranty IntroductionDescription Principles of Operation Functional ExplanationAutomatic Bypass Switch Location InstallationPackage Contents Transport UnpackingUtility voltage UPS model 120V 208V 240V Output voltage UPS model 120V 208V 240VUPS model Tightening torque force LP 5/68/10-11U Standard installation procedure LP 5/6-11U Installation procedure 120V input Bypass tap changed to 240 Volt Bypass tap factory setting 208 VoltAvailable input voltages hardware modifications Input voltage 208 or 240VacInput voltage 120Vac optional, 5/6kVA only Available output voltages hardware modificationsOutput voltage 208Vac LP 5/6/8/10-11U Output tap change Output voltage 120Vac split-phaseOutput voltage 220/230/240Vac Output voltage 120Vac single phaseOutput Voltage Setup ScreensInput Voltage Input Voltage Change toLP 5/6/8/10-11U Installation of battery pack Installation of parallel operating LP-U UPSs Autorestart OFF Press Enter Autorestart OFF Setting MismatchManual bypass MaintenanceECO-mode No-load shutdownDescription of Front and Rear Panel OperationRear panel Step-up transformer Rear panel of the step-up transformerSelftest Progress Start-upAutonomy Time Left Operating Time 0YEAR 29DAYS Battery 23CUse Input LineOn Line Alarm Press UP Status and Alarm MenuTemp TOO High Battery Charger no Float Capacitor C1 Capacity LOW Battery DepletedInverter OFF Software Version R2.9 FAN Speed INV.DC + Service ScreensService Menu Input and Output not SynchronizedTstamp Q4 Automatic Bypass EnabledFAN Curve Language English Input Voltage Output VoltageOutput Frequency Frequency Range 2% PLL Lock Speed NormalAutomatic Bypass Enabled Service Warning Disabled Quick Battery Test StartTest Screens Deep Battery Test ProcedureCalibrate BAT Test Activated Utility start Other FeaturesOverload protection in bypass mode ShutdownAuto restart Superior Battery ManagementECO Auto Restart OFF Press EnterRelay Card optional Snmp Interface optional Interfacing FeaturesRS232 / contact interface Emergency shutdownRPA-Facility Redundant Parallel Architecture Optional FeaturesExtended Runtime Plug-in CardsSeismic anchors PDM Power Distribution ModuleCooling fan MaintenanceSafety Recycling the UPS at the end of service lifeTroubleshooting Selftest Failure Temp TOO HighSelftest Failure Q4 not OK UPS Type 11U 10-11U SpecificationsAutomatic Bypass Switch Enclosure Center of Gravity Dimensions Conduit BoxLP 5/6/8/10-11U installation drawings LP 5/6/8/10-11U 208-240V input LP 5/6-11U 120V input