8.4 EMI

To protect the machines against electrical noise and to protect production of electrical noise you have to follow this rules:

Rule 1

All metallic parts must have a good and plane contact (no lacquer, aluminium oxide is an isolator). Use scratch washers.

Rule 2

Signal lines (Data- , communication- and control cable) has to separated to power cables. The minimum distance is 50 cm (20 cm inside a cabinet).

Rule 3

All signal lines should be lead in the machine or cabinet only on one side.

Rule 4

Unshielded cables must be twisted (both poles).

Rule 5

On all inductive components (relays, valves) must be directly connected a clamp circuit (diode, MOV).

Rule 6

All signal lines must be shielded. The shield must have a good earth connection on both sides. For the connection use metallic clamps. Don’t use a soldered wire for this connection.

In case of different earth potential on both cable sides install parallel a cable of at minimum 10 mm2.

Rule 7

The shield of analogue cable (Video etc) should be shielded only on one side. Normally there is no such cable with labelling machines.

Rule 8

Line filter has to be mounted directly on the cable entry.

Rule 9

Cables should not fly in the air. Lead all cables nearby metallic, grounded parts. Ground unused cables and wires in a cable at minimum on one side, better on both.

Rule 10

Cables should not be longer as necessary.

Release 4/06

Page 66

Connections and signals

Image 74
Contents Page Page ALS 330/430 Menu structure Errors and warnings ALS 330/430 Manufacturer Important NotesOverview CopyrightSafety General Safety NotesOperator’s duty of care Concrete security regulations and symbols used Security measures during maintenance and repairs Security measures during normal operationObserve environmental regulations Work on the electrical equipmentWork on pneumatic equipment Description MechanicsMachine layout Operator panel Operator panelPlug board Plug boardElectronics ALS 330/430 Prepare dispensing InstallationPreparing the machine Define label data Setting Lpit manually Manual adjustment of the Cont parameterCapacitive label sensor Capacitive sensorStop position Adjust dispense functionLabel guide Label position on the product Fixed dispensing speedAutomatic dispensing speed Apsf Product data bankSafety recommendation OperationInserting label material Left hand version Right hand versionRemoving label material Mounting a new label rollMounting a new label roll on ALS 330 Euro Mounting a new label roll on ALSAdjusting the pressure roller RewindPrinter adjustment Lead screw adjustmentAdjustment of the dispensing edge Adjust pressure roller Initializing new label materialDispenser Menu selection Function Display message Mains switchControl of dispense unit Missing label function and web breaksDisplay Menu function Function data value Display and data inputDispenser active on Label position POS Dispenser stopped OFFMaterial initialisation Init Dispense speed Velo Start delaySTADStop position Stod Product menu PD0n MaintenanceBlow on time Blow Release 4/06 Operation Page Standard menu Configuration menuMenu structure Extended standard menuApplicator ConfigurationStandard menu  Direct Extended menuDisplay Function Values Standard menuInitialisation Init Dispensing speed Velo Start delay StadLabelling time Blow Extended standard menu Display Function Data valueSensor status Sens Label pitch LpitLabel contrast Product length Prdl Label positionPOSSlew speed Slew Electronic gear ratio adjustment EgraEgra value check Stst Dwell time APT1Time constant compensation APT4 Restart delay APT3Blow on time APT2 Save parameter in data bank Save End of air stream signal AstpPrinter dwell time PDT Load data bank LoadProduct menu Page Calling the configuration menu Configuration menuPossible adjustments Possible testsHandling the menu Display Function of the parameter Possible data entryMenu functions Automatic product speed followerAPSF Type of applicator ApplAdditional functions in the standard menu Input and sensor check ICHOutput check OCH Parity bit Pari Adjustment resettingFACTInterface baud rate Baud Number of stop bits SbitDistance sensor to dispensing edge Dist Number of data bits DbitRecycle simulates max labels/min Recy Label counter LabcLeave Menu finishing Quit Data of the serial interface Dispenser connector Signal description Pol DSerial interface Direction Code Description 25 pol Pol SubExample Interface commandsCommand Description Range Ledg Message in display Connections and signals Output signalsSignals for direct dispense Applicator modesControl signals for the ASA applicator Timing ASA applicatorSignals for the EP applicator APT2Applicator connector Applicator connectorInput signals Connecting NPN left or PNP right inputsExample for connecting an NPN sensor Datalogic Product sensorOD Control sensor NPN connection of optional ODC sensor Apsf sensor Connection of a NPN type Apsf sensorControl signals Optional connector for process controInternal I/O connector EMI RuleElectronic diagrams Wiring diagram Layout dispenser electronic board Resolution ALS 330/430 Page STO! Power-fail message Errors and warningsDispenser error messages Message Meaning How to solveInto Dispenser warnings EepromALS 330/430 Description Details 330 430 Technical specificationTechnical Information Application specification APSF- Sensor Specification Optional functionPerformance charts ChartsPerformance chart Ramp Norm Deceleration Labels/min 900 25 mm 50 mm 75 mm 800 ALS 330/430 Page Adjustment Function Factory ApplicationFunction Factory PD01 PD02 PD03 PD04 Function PD05 PD06 PD07 PD08 PD09Index