American Power Conversion 400kW1MW Specifications, Rack/battery options, Weights and dimensions

Page 9

Specifications

Rack/battery options

The racks are deployed in multiples of two, with each rack housing one battery string. A maximum of eight racks (battery strings) can be used to support a single Symmetra MW UPS. The total number of strings deployed depends on the customer’s requirements for run-time. The racks can accommodate either Power or Fiamm battery types.

Refer to “APC Warranty on Batteries” on page 57.

Note

The following product SKUs reflect the currently available rack/battery options.

Rack SKU

Battery Type (Model)

Assembly

Qty

Wiring Style Cable Size (ref)*

 

 

 

 

 

 

SYR400k1000HxR-2CP

Power (TC-12150)

16 rails

2

E

120 mm2 (#4/0)

SYR400k1000HxR-2CF

Fiamm (12SLB130)

16 rails

2

E

120 mm2 (#4/0)

*Cobra cable rated for 150°C

Weights and dimensions

Each assembled rack measures 1778mm (H) x 1047mm (W) x 797mm (D) [70” x 41.2” x 31.4”]. For each two-rack combination, the width doubles to 2094mm [82.4”]. The weight of individual racks, battery types, and a fully loaded TWO-rack system is presented below.

Rack SKU

Weight Per Rack

Battery Type

Weight Per Batt

Total Wgt

 

 

 

 

 

SYR400k1000HxR-2CP

156 kg

Power (TC-12150)

45 kg

3192 kg

 

 

 

 

 

SYR400k1000HxR-2CF

156 kg

Fiamm (12SLB130)

42 kg

3000 kg

 

 

 

 

 

Battery Rack Assembly and Installation Manual

3

Image 9
Contents Assembly and Installation Manual Battery Racks for 400kW-1MW UPS SystemsBattery Rack Assembly and Installation Manual Contents Rack Assembly Appendix C Employing Sidecars Battery Rack Assembly and Installation Manual Safety Safety warningsSafety precautions Additional considerations Specifications Rack/battery optionsWeights and dimensions Shipping and Receiving ShippingReceiving Placement PositioningHandling Installation considerations Installation SiteInstallation equipment Torque specificationsAPC P/N Parts ListBattery Cabling Assembling the bottom section Rack AssemblyRefer to graphic in below Assembling the top section Top Side Subassembly #2 870-1657A Bottom Side Subassembly #2 Top Side Subassembly #1 Cross Bar #6 Top Side Subassembly #2 Connection Stabilizing the rack Accessing your wiring diagrams Anchoring the rack optionalNumbering the batteries Addressing the bottom shelf Positioning rails on shelvesWiring the batteries Rack Assembly Stud Terminal Addressing the second shelf Addressing the third shelfAddressing the top shelf Shelf-to-shelf wiring Assembling the second rack Employing sidecars to support separated racks Labelling the terminal blocksConnecting terminal blocks to battery breakers To Battery Breaker #1 BAT 1- terminal Connecting terminal blocks to batteries Rack #1, Top Shelf Terminal Block #1 Shelf-to-shelf From Battery #24 Rack #2, Top Shelf Terminal Block #2 Shelf-to-shelf From Battery #56 Reattaching terminal block covers Applying warning labelsGrounding the racks APC GlossaryStyle E, rack #1, shelf #1 top Appendix a Battery Wiring Style EStyle E, rack #1, shelf #2 Style E, rack #1, shelf #3 Style E, rack #1, shelf #4 bottom Style E, rack #2, shelf #1 top Style E, rack #2, shelf #2 Style E, rack #2, shelf #3 Style E, rack #2, shelf #4 bottom Appendix B Battery Cabling Kits References for Power battery cablesReferences for Fiamm battery cables Sidecar overview Appendix C Employing SidecarsPositioning and accessing the sidecar Connecting terminal blocks to sidecars To BAT To BAT 2+ Appendix C Employing Sidecars At the Sidecar Connecting sidecars to battery breakersBAT 2+ Top BAT BAT 1+ Top Battery Rack Assembly and Installation Manual Battery Rack Assembly and Installation Manual Battery Rack Assembly and Installation Manual APC Warranty on Batteries APC Worldwide Customer Support 990-4194A03/2004