(Center) and Stbd (Starboard). Select the tank you refilled and press MENU. The Fuel Quantity window will appear.
3.Use the UP and DOWN keys to input the amount of fuel you added to the tank and press MENU. You will be directed to the main display.
EP-15 Fluid Level Calibration
The default calibration for the
A
To execute 2-Point calibration:
1. Press MENU, select SYSTEM SETUP and press MENU.
2.Highlight B. DEVICES and press MENU, which will open the Bus Devices list.
3.Highlight the fluid level sensor you want to calibrate and press MENU, then select CAL (Calibrate) and press MENU. The Points menu will appear with three options: 2, 3 and 5.
4.Select 2 and press MENU. The Points menu will appear with two options: Empty Lev and Full Lev.
NOTE:
You DO NOT have to calibrate both points to complete the calibration and you can calibrate the points (Empty Level and Full Level) in any order you wish. Remember: Points that are not calibrated will not be as accurate as points that have been calibrated. For the greatest accuracy, we recommend both points be calibrated.
5.Make sure the tank is empty, then select EMPTY LEV from the Points menu and press MENU. The following message Tnk to Empty lev hit Menu. Press MENU and fill up the tank.
6.When the tank has been filled, follow steps