Accessing Charger Information
◆Press ON/STANDBY on the optional remote display to initialize another cycle.
If AC power is connected, the XC Series will turn on, check which battery banks are present and healthy, and begin charging.
While the XC Series is off, and a fault is present, the remote display will turn itself on approximately once per minute to show the fault and then turn itself off.
Using A Generator As Source Power
The XC Series can be run from a regular power source or from an alternate power source such as a generator. Refer to Appendix A, “Specifications” for AC input draw to determine the size of generator you need. Many generators provide output voltage that is modified sine wave or modified square wave (MSW) rather than the true sine wave (TSW) that your utility provides.
The XC Series may be used with MSW generators but the lifetime may be reduced somewhat depending on the severity of any peak voltage overshoots, and the severity of waveshape risetimes.