Page 18

Specifications (continued)

Model: SU30K3/3

Input

Input Voltage

120/208V AC, 3ø, 4 Wire (plus ground), wye

Input Frequency

60 Hz ± 3 Hz

Voltage Correction Range

88-144/166-250V AC

Input Current (Per Phase, On-Line)

90A

Inrush Current

<300A

Power Factor (Full Load)

>0.95

Efficiency (Full Load/On-Line)

>89%

Circuit Breaker

200A (3p)

Input Bypass Circuit Breaker

200A (3p)

 

 

Output

 

VA

30000

Watts (Power Factor: 0.8)

24000

Waveform (On-Line)

Sinewave

Waveform (On-Battery)

Sinewave

Output Voltage (RMS)

120/208V AC, 3ø, 4 Wire (plus ground), wye

Output Frequency

60 Hz (± 0.1 Hz on battery)

Voltage Regulation

±2%

Max. Harmonic Distortion

 

(Non-Linear Full Load)

<5%

Overload Capabilities

<102% (continuous), 102%~125% (1 min.),

 

125%~150% (30 sec.), >150% (2 sec.)

Short Circuit Capability

>250A

Crest Factor

3:1

 

 

Battery

 

Battery Type

Sealed, Lead Acid, 240V DC, 9AH

Battery Pack Quantity

Three Packs (20 12V DC Batteries per pack)

Protection

Six UL-recognized 30A 600VDC rated

 

cartridge fuses (two per battery pack) and

 

fuse block (1 per battery pack)

Typical Backup Time (Half Load) 13 min. +

Typical Backup Time (Full Load) 5 min. +

Operation

On-Line Transfer Time

(Line to Battery, Battery to Line) 0 ms

Audible Noise (Full Load @ 1 meter) <65 dBA

Indicators

Includes an LCD Display and LEDs (AC Line In, Bypass Line In, AC to DC, DC to AC, AC Output, Battery Back-Up, Bypass).

Communications

Includes an RS-232 DB9 female connector, an AS-400 DB9 female connector, a dry contact DB9 female connector and an accessory slot.

Connections

Input Terminal Block

100A

Output Terminal Block

100A

 

 

Physical Specifications

 

Unit Dimensions (H x W x D)

35.3 x 19.3 x 36 in.

Unit Weight

662 lb.

Shipping Dimensions (H xW x D) 43 x 28 x 44.5 in.

Shipping Weight

750 lb.

Model: SU30K3/3XR5

Input

Input Voltage

120/208V AC, 3ø, 4 Wire (plus ground), wye

Input Frequency

60 Hz ± 3 Hz

Voltage Correction Range

88-144/166-250V AC

Input Current (Per Phase, On-Line)

90A

Inrush Current

<300A

Power Factor (Full Load)

>0.95

Efficiency (Full Load/On-Line)

>89%

Circuit Breaker

200A (3p)

Input Bypass Circuit Breaker

200A (3p)

 

 

Output

 

VA

30000

Watts (Power Factor: 0.8)

24000

Waveform (On-Line)

Sinewave

Waveform (On-Battery)

Sinewave

Output Voltage (RMS)

120/208V AC, 3ø, 4 Wire (plus ground), wye

Output Frequency

60 Hz (± 0.1 Hz on battery)

Voltage Regulation

±2%

Max. Harmonic Distortion

 

(Non-Linear Full Load)

<5%

Overload Capabilities

<102% (continuous), 102%~125% (1 min.),

 

125%~150% (30 sec.), >150% (2 sec.)

Short Circuit Capability

>250A

Crest Factor

3:1

 

 

Battery

 

Battery Type

Sealed, Lead Acid, 240V DC, 9AH

Battery Pack Quantity

Five Packs (20 12V DC Batteries per pack)

Protection

Ten UL-recognized 30A 600VDC rated

 

cartridge fuses (two per battery pack) and

 

fuse block (1 per battery pack)

Typical Backup Time (Half Load) 25 min. +

Typical Backup Time (Full Load) 11 min. +

Operation

On-Line Transfer Time

(Line to Battery, Battery to Line) 0 ms

Audible Noise (Full Load @ 1 meter) <65 dBA

Indicators

Includes an LCD Display and LEDs (AC Line In, Bypass Line In, AC to DC, DC to AC, AC Output, Battery Back-Up, Bypass).

Communications

Includes an RS-232 DB9 female connector, an AS-400 DB9 female connector, a dry contact DB9 female connector and an accessory slot.

Connections

Input Terminal Block

100A

Output Terminal Block

100A

 

 

Physical Specifications

 

Unit Dimensions (H x W x D)

48.5 x 19.3 x 36 in.

Unit Weight

935 lb.

Shipping Dimensions (H xW x D) 61.5 x 31 x 44.5 in.

Shipping Weight

1152 lb.

+ Backup times are expandable with additional Battery Packs, sold separately. The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.

Regulatory Compliance Identification Numbers

For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the marking name or model number of the product.

FCC Specifications for Models with FCC Approval:

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. The user must use shielded cables and connectors with this product. Any changes or modifications to this product not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.

18

Image 18
Contents Warranty RegistrationUPS Location Warnings Important Safety WarningsBattery Warnings UPS Connection WarningsFront Panel Control PanelBattery Access Panel cover removed Rear Panel Rear PanelUPS Input and Output Hardwire Connection InstallationMounting Bracket Installation UPS LocationOperation Normal Conditions Initial Battery ChargingSELF-TESTING Turning the UPS onOperation Special Conditions LCD Display Select ButtonOperation on BYPASS-VOLTAGE OUT of Range Switching UPS to Normal Mode Operation of Manual Bypass SwitchSwitching UPS to Bypass Mode Inverter on WarningsAS-400 Interface CommunicationsRS-232 Interface DRY Contact InterfaceBattery Packs are Heavy Remote Emergency Power OFF EPODo not Remove Battery Sleeve Check Battery Pack Voltage Before Completing InstallationInternal Battery Pack Wiring Diagram Adding or Replacing Internal Batteries Terminals Adding or Replacing Internal Batteries Phase UPS System Limited Warranty ServiceWarranty & Warranty Registration Warranty RegistrationSpecifications Model SU20K3/3Model SU20K3/3XR5 Model SU30K3/3 Model SU30K3/3XR5Manual del Propietario Advertencias para la conexión del UPS Advertencias de Seguridad ImportantesAdvertencias sobre la colocación y ubicación del UPS Advertencias Sobre la BateríaPanel Frontal Panel DE ControlPanel Frontal continuación Panel DE Acceso a LA Bateria Tapa RemovidaPanel Trasero Panel TraseroInstalacion DE LOS Soportes DE Montaje InstalaciónUbicación DEL UPS Conexion a TierraEncendiendo EL UPS Operación Condiciones NormalesCarga Inicial DE LA Bateria Apagando EL UPSBoton Select Seleccionar DE LA Pantalla LCD Operación Condiciones Normales continuaciónOperación Condiciones Especiales Operacion EN DERIVACION-VOLTAJE Fuera DE RangoOperación Condiciones Especiales continuación Interfaz AS-400 ComunicacionesInterfaz RS-232 Interfaz DEL Contacto SecoApagado DE Emergencia Remoto EPO Comunicaciones continuaciónAñadiendo o Remplazando las Baterías Internas ¡NO Remueva LA Cubierta Protectora DE LA BateriaDiagrama DEL Cableado DEL Modulo DE Baterias Internas Añadiendo o Remplazando las Baterías Internas continuaciónAñadiendo o Remplazando las Baterías Internas continuación Terminales ¡PELIGRO ¡OBSERVE LA Polaridad Correcta Servicio GarantíaGarantía Limitada del Sistema UPS Trifásico Especificaciones Modelo SU20K3/3Modelo SU20K3/3XR5 Especificaciones continuación Modelo SU30K3/3Modelo SU30K3/3XR5 Manuel du propriétaire Mises en garde relatives aux connexions de londuleur Importantes consignes de sécuritéMises en garde relatives à la localisation de londuleur Mises en garde relatives aux connexions de léquipementPanneau DE Commande Panneau avantPanneau avant suite Panneau Daccès AUX Batteries carter enlevéPanneau arrière Panneau ArrièreConnexion DE Mise À LA Terre IL Faut Installer Londuleur À Laide DE Brides DE FixationMises EN Garde Relatives À LA Localisation DE Londuleur Sélection DU CâblageInstallation suite Fonctionnement Conditions normalesBouton DE Sélection DE Lécran ACL Fonctionnement Conditions normales suiteFonctionnement Conditions spéciales Fonctionnement EN DÉRIVATION-TENSION Hors PlagMises EN Garde Inverseur EN Marche Commuter Londuleur EN Mode NormalFonctionnement Conditions spéciales suite Fonctionnement Pendant UN ArrêtInterface RS-232 Interface AS-400Interface Contact SEC Communications suite Ajout et remplacement des batteries internesArrêt Durgence Emergency Power OFF EPO À Distance NE PAS Retirer LA Gaine DE BatterieAjout et remplacement des batteries internes suite Schéma DU Câblage Interne DUN Bloc DE BatterieAjout et remplacement des batteries internes suite Bornes Ajout et remplacement des batteries internes suite Garantie Garantie limitée de londuleur triphaséObserver LA Bonne Polarité Spécifications Modèle SU20K3/3Modèle SU20K3/3XR5 Spécifications suite Modèle SU30K3/3 Modèle SU30K3/3XR5Th Street Chicago, IL 60609 USA 773