Tripp Lite 30kVA Inverter on Warnings, Operation Under Shutdown, Switching UPS to Bypass Mode

Page 9

Operation (Special Conditions) (continued)

INVERTER ON WARNINGS

When the inverter is ON, the LCD Display may show any one of the following warnings:

Condition

LCD Display Message

 

 

UPS Output Overload

OVERLOAD 110%

 

 

UPS Charger Failure

CHARGER FAILURE

 

 

Abnormal Input Frequency

FREQUENCY ERROR

 

 

Abnormal Input Phase

PHASE ABNORMAL!

 

 

Battery is Depleting*

ON BATTERY

 

 

Battery Charge is Nearly Depleted*

BATTERY LOW

 

 

* During a prolonged blackout, users should save files and shut down connected equipment.

The “BATTERY LOW” message indicates the UPS's batteries are nearly out of power and UPS shut down is imminent.

OPERATION UNDER SHUTDOWN

Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: For all conditions, the “Input,” “Output” and “Bypass” LEDs will be illuminated.

Condition

LCD Display Message

 

 

Overload Shutdown

ON BYPASS

 

OVERLOAD 150%

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

UPS Output Short Circuit

ON BYPASS

 

SHORT CIRCUIT!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

Overtemperature

ON BYPASS

 

HIGH TEMP!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

DC BUS Overvoltage

ON BYPASS

 

DC BUS O.V.P.!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

DC BUS Failure

ON BYPASS

 

DC BUS FAIL!

 

SHUTDOWN...

 

VERSION: XXXXXXX

Condition

LCD Display Message

 

 

R/S/T Inverter Output Failure

ON BYPASS

 

R OUTPUT FAIL!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

Low Battery

BYPS OFF NO O/P

 

LOW BATTERY!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

Remote Shutdown

BYPS OFF NO O/P

 

REMOTE SHUTDOWN

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

Emergency Stop

BYPS OFF NO O/P

 

EMERGENCY STOP!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

OPERATION OF MANUAL BYPASS SWITCH

Turn this switch to “BYPASS” before performing any maintenance on the UPS with the connected load supported. Connected equipment will receive filtered AC mains power, but will not receive battery power in the event of a blackout.

SWITCHING UPS TO “BYPASS” MODE

Press the “OFF” button.

Turn the “Manual Bypass” Switch clockwise from NORMAL to BYPASS.

Turn the Main Input Switch Circuit Breaker OFF.

SWITCHING UPS TO “NORMAL” MODE

Turn the Main Input Switch Circuit Breaker ON.

Turn the “Manual Bypass” Switch counterclockwise from BYPASS back to NORMAL.

Press the “ON” button.

9

Image 9
Contents Registration WarrantyBattery Warnings Important Safety WarningsUPS Location Warnings UPS Connection WarningsControl Panel Front PanelBattery Access Panel cover removed Rear Panel Rear PanelMounting Bracket Installation InstallationUPS Input and Output Hardwire Connection UPS LocationSELF-TESTING Initial Battery ChargingOperation Normal Conditions Turning the UPS onOperation Special Conditions LCD Display Select ButtonOperation on BYPASS-VOLTAGE OUT of Range Switching UPS to Bypass Mode Operation of Manual Bypass SwitchSwitching UPS to Normal Mode Inverter on WarningsRS-232 Interface CommunicationsAS-400 Interface DRY Contact InterfaceDo not Remove Battery Sleeve Remote Emergency Power OFF EPOBattery Packs are Heavy Check Battery Pack Voltage Before Completing InstallationInternal Battery Pack Wiring Diagram Adding or Replacing Internal Batteries Terminals Adding or Replacing Internal Batteries Warranty & Warranty Registration ServicePhase UPS System Limited Warranty Warranty RegistrationSpecifications Model SU20K3/3Model SU20K3/3XR5 Model SU30K3/3XR5 Model SU30K3/3Manual del Propietario Advertencias sobre la colocación y ubicación del UPS Advertencias de Seguridad ImportantesAdvertencias para la conexión del UPS Advertencias Sobre la BateríaPanel DE Control Panel FrontalPanel DE Acceso a LA Bateria Tapa Removida Panel Frontal continuaciónPanel Trasero Panel TraseroUbicación DEL UPS InstalaciónInstalacion DE LOS Soportes DE Montaje Conexion a TierraCarga Inicial DE LA Bateria Operación Condiciones NormalesEncendiendo EL UPS Apagando EL UPSOperación Condiciones Especiales Operación Condiciones Normales continuaciónBoton Select Seleccionar DE LA Pantalla LCD Operacion EN DERIVACION-VOLTAJE Fuera DE RangoOperación Condiciones Especiales continuación Interfaz RS-232 ComunicacionesInterfaz AS-400 Interfaz DEL Contacto SecoAñadiendo o Remplazando las Baterías Internas Comunicaciones continuaciónApagado DE Emergencia Remoto EPO ¡NO Remueva LA Cubierta Protectora DE LA BateriaAñadiendo o Remplazando las Baterías Internas continuación Diagrama DEL Cableado DEL Modulo DE Baterias InternasAñadiendo o Remplazando las Baterías Internas continuación Terminales ¡PELIGRO ¡OBSERVE LA Polaridad Correcta Servicio GarantíaGarantía Limitada del Sistema UPS Trifásico Especificaciones Modelo SU20K3/3Modelo SU20K3/3XR5 Especificaciones continuación Modelo SU30K3/3Modelo SU30K3/3XR5 Manuel du propriétaire Mises en garde relatives à la localisation de londuleur Importantes consignes de sécuritéMises en garde relatives aux connexions de londuleur Mises en garde relatives aux connexions de léquipementPanneau avant Panneau DE CommandePanneau Daccès AUX Batteries carter enlevé Panneau avant suitePanneau Arrière Panneau arrièreMises EN Garde Relatives À LA Localisation DE Londuleur IL Faut Installer Londuleur À Laide DE Brides DE FixationConnexion DE Mise À LA Terre Sélection DU CâblageFonctionnement Conditions normales Installation suiteFonctionnement Conditions spéciales Fonctionnement Conditions normales suiteBouton DE Sélection DE Lécran ACL Fonctionnement EN DÉRIVATION-TENSION Hors PlagFonctionnement Conditions spéciales suite Commuter Londuleur EN Mode NormalMises EN Garde Inverseur EN Marche Fonctionnement Pendant UN ArrêtInterface RS-232 Interface AS-400Interface Contact SEC Arrêt Durgence Emergency Power OFF EPO À Distance Ajout et remplacement des batteries internesCommunications suite NE PAS Retirer LA Gaine DE BatterieSchéma DU Câblage Interne DUN Bloc DE Batterie Ajout et remplacement des batteries internes suiteAjout et remplacement des batteries internes suite Bornes Ajout et remplacement des batteries internes suite Garantie Garantie limitée de londuleur triphaséObserver LA Bonne Polarité Spécifications Modèle SU20K3/3Modèle SU20K3/3XR5 Modèle SU30K3/3 Modèle SU30K3/3XR5 Spécifications suiteTh Street Chicago, IL 60609 USA 773