Tripp Lite 30kVA Operation Normal Conditions, Initial Battery Charging, Turning the UPS on

Page 7

Installation (continued)

WIRING CONNECTION

Connect your wiring to the input and output terminal blocks located on the rear panel of your UPS (see figure below).

CAUTION!

Qualified personnel should follow all procedures prescribed by N.E.C. and other local codes for hardwiring devices to a utility source.

Ensure that cables are fitted with cable sleeves and are secured by connector clamps. Tighten connections with a torque of not less than 35 inch-pounds. Observe the appropriate cable connection regulations [e.g. National Electrical Code (NEC) in the U.S.] at all times. Using cables of improper size may damage your equipment and cause fire hazards.

G N1 R1 S1 T1

N2 T2 S2 R2 G

NOTE: when shipped from the factory, bypass input and main input wires are connected.

INITIAL BATTERY CHARGING

Although the internal batteries are charged prior to shipping, allow the internal batteries to charge uninterrupted for 24 hours after initial installation.

Operation (Normal Conditions)

TURNING THE UPS ON

Make sure the UPS is properly installed (see Installation section) and the Manual Bypass Switch is set to NORMAL.

Turn the AC Main Input Switch and Bypass Input Switch Circuit Breakers ON.

If your AC input is providing power normally within your selected range, your connected load will energize in Bypass. However, the UPS's inverter is not yet on. Press the front “ON” button to begin inverter operation.

If your AC input is not providing power normally, you have the option of starting from battery. (Your battery must be at least partially charged for this operation to succeed.) Press and hold both the "Battery Start" switch and the “ON” button for three seconds to start your UPS in “ON BATTERY” mode. Note that some electronic equipment may draw more amps during startup; when starting from battery, consider reducing the initial load on the UPS.

The UPS will perform a brief self-test and show the results on the LCD Display. (See Self-Testing section, for display sequence.) After a successful self-test, the UPS will provide AC power from the inverter to your load.

TURNING THE UPS OFF

Press the front “OFF” button. Your load will still be energized. The inverter is now off, but your UPS is not fully deactivated. The LCD Display will show “ON BYPASS.”

Turn the Main Input Switch and Bypass Input Switch Circuit Breakers OFF. Your load will no longer be energized, and the LCD display will be dark.

NOTE: If the UPS System remains off for an extended period of time, it should be turned back on periodically to allow the internal batteries to recharge. The UPS System should be turned on and the internal batteries should be recharged at least one uninterrupted 24-hour period every 3 months. Failure to provide periodic recharge time may cause irreversible battery damage.

SELF-TESTING

When you turn the UPS ON, it will perform a brief self-test. See charts below for display sequences.

Display sequence when AC input power is present:

SELF TESTING...

RECTIFIER OK

CHARGER OK

BATTERY OK

DC TO DC OK

INVERTER TEST

Display sequence when AC input power is absent: (possible only with the "Battery Start" Switch)

SELF TESTING...

BATTERY OK

DC TO DC OK

INVERTER TEST

7

Image 7
Contents Registration WarrantyUPS Connection Warnings Important Safety WarningsBattery Warnings UPS Location WarningsControl Panel Front PanelBattery Access Panel cover removed Rear Panel Rear PanelUPS Location InstallationMounting Bracket Installation UPS Input and Output Hardwire ConnectionTurning the UPS on Initial Battery ChargingSELF-TESTING Operation Normal ConditionsLCD Display Select Button Operation Special ConditionsOperation on BYPASS-VOLTAGE OUT of Range Inverter on Warnings Operation of Manual Bypass SwitchSwitching UPS to Bypass Mode Switching UPS to Normal ModeDRY Contact Interface CommunicationsRS-232 Interface AS-400 InterfaceCheck Battery Pack Voltage Before Completing Installation Remote Emergency Power OFF EPODo not Remove Battery Sleeve Battery Packs are HeavyInternal Battery Pack Wiring Diagram Adding or Replacing Internal Batteries Terminals Adding or Replacing Internal Batteries Warranty Registration ServiceWarranty & Warranty Registration Phase UPS System Limited WarrantyModel SU20K3/3 SpecificationsModel SU20K3/3XR5 Model SU30K3/3XR5 Model SU30K3/3Manual del Propietario Advertencias Sobre la Batería Advertencias de Seguridad ImportantesAdvertencias sobre la colocación y ubicación del UPS Advertencias para la conexión del UPSPanel DE Control Panel FrontalPanel DE Acceso a LA Bateria Tapa Removida Panel Frontal continuaciónPanel Trasero Panel TraseroConexion a Tierra InstalaciónUbicación DEL UPS Instalacion DE LOS Soportes DE MontajeApagando EL UPS Operación Condiciones NormalesCarga Inicial DE LA Bateria Encendiendo EL UPSOperacion EN DERIVACION-VOLTAJE Fuera DE Rango Operación Condiciones Normales continuaciónOperación Condiciones Especiales Boton Select Seleccionar DE LA Pantalla LCDOperación Condiciones Especiales continuación Interfaz DEL Contacto Seco ComunicacionesInterfaz RS-232 Interfaz AS-400¡NO Remueva LA Cubierta Protectora DE LA Bateria Comunicaciones continuaciónAñadiendo o Remplazando las Baterías Internas Apagado DE Emergencia Remoto EPOAñadiendo o Remplazando las Baterías Internas continuación Diagrama DEL Cableado DEL Modulo DE Baterias InternasAñadiendo o Remplazando las Baterías Internas continuación Terminales ¡PELIGRO ¡OBSERVE LA Polaridad Correcta Garantía ServicioGarantía Limitada del Sistema UPS Trifásico Modelo SU20K3/3 EspecificacionesModelo SU20K3/3XR5 Modelo SU30K3/3 Especificaciones continuaciónModelo SU30K3/3XR5 Manuel du propriétaire Mises en garde relatives aux connexions de léquipement Importantes consignes de sécuritéMises en garde relatives à la localisation de londuleur Mises en garde relatives aux connexions de londuleurPanneau avant Panneau DE CommandePanneau Daccès AUX Batteries carter enlevé Panneau avant suitePanneau Arrière Panneau arrièreSélection DU Câblage IL Faut Installer Londuleur À Laide DE Brides DE FixationMises EN Garde Relatives À LA Localisation DE Londuleur Connexion DE Mise À LA TerreFonctionnement Conditions normales Installation suiteFonctionnement EN DÉRIVATION-TENSION Hors Plag Fonctionnement Conditions normales suiteFonctionnement Conditions spéciales Bouton DE Sélection DE Lécran ACLFonctionnement Pendant UN Arrêt Commuter Londuleur EN Mode NormalFonctionnement Conditions spéciales suite Mises EN Garde Inverseur EN MarcheInterface AS-400 Interface RS-232Interface Contact SEC NE PAS Retirer LA Gaine DE Batterie Ajout et remplacement des batteries internesArrêt Durgence Emergency Power OFF EPO À Distance Communications suiteSchéma DU Câblage Interne DUN Bloc DE Batterie Ajout et remplacement des batteries internes suiteAjout et remplacement des batteries internes suite Bornes Ajout et remplacement des batteries internes suite Garantie limitée de londuleur triphasé GarantieObserver LA Bonne Polarité Modèle SU20K3/3 SpécificationsModèle SU20K3/3XR5 Modèle SU30K3/3 Modèle SU30K3/3XR5 Spécifications suiteTh Street Chicago, IL 60609 USA 773