Installation
UPS LOCATION
Move your UPS over short distances using its wheels. NOTE: the wheels are not designed to provide
MOUNTING BRACKET INSTALLATION
DANGER!
RISK OF PRODUCT DAMAGE AND SERIOUS PERSONAL INJURY
The UPS System's wheels are not designed to provide
Using the included bolts, install one mounting bracket on each side of the UPS System as shown. If desired, install the bracket to the floor surface with
Front View |
GROUNDING CONNECTION
Using a
Rear View
UPS INPUT AND OUTPUT HARDWIRE CONNECTION
In addition to the instructions listed below, follow all warnings found in the Safety section prior to connection.
•Install with flex cable of sufficient length to move UPS clear of surrounding equipment for servicing (sides and rear).
•Use ferrule caps to cover termination cables connected to UPS to avoid frayed ends from shorting on terminal block.
•Neutral conductor must be same size as current conductors.
WIRING SELECTION
Choose appropriate cabling (rated
UPS System Model | Wiring Size |
20kVA | 6 AWG / 14 mm2 |
30kVA | 4 AWG / 22 mm2 |
Maximum Cable Length: 10 m (32.8 ft)