Trane RT-PRC031-EN manual Mechanical Specifications, Exhaust Air, No Relief Standard

Page 103

Mechanical Specifications

MERV 14, 90-95 Percent, Low

Pressure Drop, Totally

Incinerable, Cartridge, Final Filter

Option

Note: Available on cooling only units with four or eight-foot blank section, as well as steam and hot water units with eight-foot blank section, unit casing only.

Twelve-inch deep cartridge filter shall be U.L. Class 2 and mounted with a rigid 7/8” nominal thickness header frame. These cartridge filters shall have an efficiency rating of MERV 14 per ASHRAE 52.2. To ensure maximum cartridge final filter life four-inch prefilters shall be included with these cartridge filters. Filters shall be mounted in a galvanized steel filter frame bank.

MERV 14, 90-95 Percent, High

Temperature Rated, Cartridge,

Final Filter Option

Note: Available on gas and electric heat units with eight-foot blank section casing only.

Twelve-inch deep cartridge filters shall be U.L. Class 1 and be mounted in a galvanized steel casing with a 7/8” nominal thickness header frame. These cartridge filters shall have an efficiency rating of MERV 14 per ASHRAE 52.2. To ensure maximum cartridge final filter life high temperature rated two-inch prefilters shall be included with the cartridge filters. Filters shall be mounted in a galvanized steel filter frame bank.

MERV 17, 99.97 Percent, Standard

Temperature Rated, HEPA, Final

Filter Option

Note: Available on cooling only units with four or eight-foot blank section, as well as steam and hot water units with eight-foot blank section, unit casing only.

Twelve-inch deep HEPA filters shall be U.L. Class 1 and be mounted in a galvanized steel casing. These filters have an efficiency rating of MERV 17 per ASHRAE 52.2 and an efficiency of 99.97% on a 0.3 micron DOP particle size. To ensure maximum HEPA final filter life two-inch prefilters shall be included with the HEPA final filters.

Filters shall be mounted in a galvanized steel filter frame bank.

MERV 17, 99.97 Percent, High

Temperature Rated, HEPA, Final

Filter Option

Note: Available on gas and electric heat units with eight-foot blank section casing only.

Twelve-inch deep HEPA filters shall be U.L. Class 1 and be mounted in a galvanized steel casing. These filters have an efficiency rating of MERV 17 per ASHRAE 52.2 and an efficiency of 99.97% on a 0.3 micron DOP particle size. To ensure maximum HEPA final filter life high temperature rated two- inch prefilters shall be included with the HEPA final filters. Filters shall be mounted in a galvanized steel filter frame bank.

Exhaust Air

General

Exhaust air options shall include no relief, 100 percent modulating exhaust fan and 100 percent modulating exhaust fan with direct space building pressurization control.

Exhaust fans shall be either standard or low airflow

No Relief (Standard)

Relief air opening shall be sealed with panel and made watertight.

100 Percent Modulating Exhaust Fan Option

Fan design shall be double width, double inlet forward-curved type. Fan shall be mounted on a shaft with fixed sheave drive. All fans shall be dynamically balanced and tested in factory before being installed in unit. It shall be test run in unit as part of unit test. Fan operating envelop rpm shall be below first critical speed. Fan shaft shall be mounted on two grease lubricated ball or roller bearings as applicable designed for 200000-hour average life. Extended grease lines shall be provided to allow greasing of bearings from section base rail.

Fan motor and assembly shall be mounted on common base to allow consistent belt tension with no relative motion between fan and motor shafts. The entire assembly

shall be completely isolated from unit with 2-inch spring isolation. Discharge dampers at unit outlet shall modulate exhaust airflow in response to OA damper position.

100 Percent Modulating Exhaust Fan with Statitrac™ Control Option

Fan design shall be double width, double inlet forward-curved type. Fan shall be mounted on a shaft with fixed sheave drive. All fans shall be dynamically balanced and tested in factory before being installed in unit. Exhaust fan shall be test run as part of unit final run test. Fan operating envelop rpm shall be below first critical speed. Fan shaft shall be mounted on two grease lubricated ball or roller bearings designed for 200000-hour average life. Extended grease lines shall be provided to allow greasing of bearings from section base rail.

Fan motor and assembly shall be mounted on common base to allow consistent belt tension with no relative motion between fan and motor shafts. The entire assembly shall be completely isolated from unit with 2-inch spring isolators. For both CV and VAV air handlers, the 100 percent modulating exhaust discharge damper (or VFD) shall be modulated in response to building pressure.

A differential pressure control system, (Statitrac), shall use a differential pressure transducer to compare indoor building pressure to outdoor ambient atmospheric pressure. The FC exhaust fan shall be turned on when required to lower building static pressure setpoint. The (Statitrac) control system shall then modulate the discharge dampers (or VFD) to control the building pressure to within the adjustable, specified deadband that shall be adjustable at the Human Interface Panel.

RT-PRC031-EN

103

Image 103
Contents IntelliPak II Air Handlers Introduction Table of Contents Standard Features Features and BenefitsControls Cabinet Mechanical Features and Benefits Optional Features Reliability Features and Benefits Field Installed AccessoriesFeatures Summary Installation and ServiceIntegrated Comfort with Trane Tracer LCI Features and Benefits Application FlexibilitySimplifying the Comfort System Interoperability Features and BenefitsOptimum Building Comfort Control Statitrac Statitrac Direct Space Building Pressurization ControlVariable Frequency Drives VFD Supply Fans with Inlet Guide VanesSupply Air Temperature Controls Supply Air Pressure Control Controls Variable Air Volume VAV OnlySupply Air Setpoint Reset Controls Variable Air Volume VAV OnlyHeating Zone Temperature Control Gas Heating Two-Stage Controls Constant Volume CV OnlyOccupied Zone Temperature Control HeatingHot Water or Steam Heating Controls Constant Volume CV Only Auto ChangeoverUnoccupied Zone Temperature Control Cooling and HeatingEmergency Override Controls VAV and CVSpace Pressure Control Statitrac Morning Warm-up OptionsVentilation Override Module VOM Controls VAV and CVGeneric Building Automation System Module Gbas 0-5 vdc Human Interface Panel HIHuman Interface Panel Main Menu Night Setback Sensors Generic Building Automation System Module Gbas 0-10 vdcChilled Water Coil Freeze Stat Steam and Hot Water Coil Freeze AvoidanceTimed Override Activation Dry Bulb Temperature Control of EconomizerOccupied/Unoccupied input on the RTM Trane Tracer or BAS SystemTwinning Humidification ControlLonTalk Building Automation System Return Fan ControlAdvantages Applications ConsiderationsExhaust/Return Fan Options Application RecommendationsApplications Considerations Supply and Return Airflow ConfigurationsCartridge Supply Airflow ConfigurationReturn Airflow Configuration With BagAcoustical Considerations Corrosive AtmospheresVentilation Override Sequences Natural Gas Heating ConsiderationsClearance Requirements Unit PlacementProtecting Hydronic Coils From Freezing Duct DesignExternal Piping Enclosure Selection Procedure Selection Procedure Altitude Corrections Exhaust Fan Motor SizingReturn Fan Motor Sizing Unit Electrical RequirementsDigit 7 Chilled Water Coil FIN Series Model Number DescriptionDigit 20 System Control Selection Model Number DescriptionDigit 38 Belt Guards Burglar BARS/MARINE Lights General Data General Data All dimensions in inchesGeneral Data Standard Damper Optional Low Leak Damper Gas Heat Inputs/Input RangesEconomizer Outdoor Air Damper Leakage at rated airflowi Inputs MBH Input MBH Range MBHGas Heating Capacity Altitude Correction Factors Performance Adjustment FactorsWet Bulb Temperature Btu per Pound Enthalpy of Saturated AirChilled Water Coil Capacities-2 Row 5W Performance Data-Chilled Water Coil CapacitiesDB F WB F Chilled Water Coil Capacities-4 Row W Performance Data-Chilled Water Coil CapacitiesChilled Water Coil Capacities-6 Row WD Chilled Water Coil Capacities-8 Row WD Total Static Pressure Std Air Supply Fan Performance Standard CFM Casing a1644 Supply Fan w/o IGV 931 Supply Fan Performance Standard CFM -Casing B1117 Supply Fan Performance Standard CFM-Casing B 749 Supply Fan Performance Standard CFM Casing C1019 Std Air Total Static PressurePerformance Data Supply Fan with Inlet Guide Vanes Performance Data Supply Fan with Inlet Guide Vanes Supply Fan Performance Standard CFM-Casing a Supply Fan Performance Standard CFM Casing B 1093 1600 RPM 1500 RPM 779 1021 1283 Negative Static Pressure Std Air Performance Data-Exhaust FanStatic PresureInWC Performance Data-Exhaust Fan237i Wocfm 415 Exhaust Fan Performance Standard CFM-Case C 32 Fan0 R P M Return Fan Performance Standard CFM-Case a 36.5 Fan Performance Data-Return FanReturn Fan Performance Performance Data-Return FanReturn Fan Performance Standard CFM-Case B and Case C 40 Fan Return Fan Performance Electric Heat kw Ranges Electric Heat Air Temperature RisePerformance Data-Heat Natural Gas Heating Capacities1Properties of Steam Performance Data-HeatHot Water Coil Heating Capacities Q/ITD Steam Coil Heating Capacities Q/ITDComponent Static Pressure Drops in. H2O Chilled Water Coil Airside Pressure Drop in H20Cartridge Filters Throw Temp Hi Temp Away Prefilter Casing High Low PD Cartridge Bag FiltersFilters Prefilter Drive No Supply Air Fan Drive Selections15 HP 20 HP 25 HP 30 HP 40 HP Drive No Horse Power HP Low Casing StdExhaust Air Fan Drive Selections Return Air Fan Drive SelectionsSet 2. Cooling with Electric Heat Electrical Service SizingElectrical Data Set 1. Cooling with Gas Heat Air Handling UnitsElectrical Service Sizing Data-Motors Nominal Tons Voltage 460 575 FLA Add 90-150 Electrical DataVoltage Utilization Range Unit VoltageUnit Top/Front View Dimensional DataUnit Dimensions In.-One-Piece Unit Dimensional DataReturn Exhaust Unit Height Fan Casing Opening Downflow/Horizontal Airflow Configuration DimensionsSupply Opening Blank Casing Gas Heat Section Electrical Entry Details Piping Chilled Water Piping Locations Exh Box Minimum Required ClearanceUnit Option Selection Door Swing Ft. Standard Minimum Required Clearance Ft ControlBlank Casing Section Dimensions Blank Casing SectionCross Member Location Blank Casing Section Field Installed Sensors Variable Air Volume VAV Field Installed Sensors Constant Volume CV Field Installed Sensors VAV and CV Wireless Zone Sensor Wall or Duct Mount CO2 Zone Sensors Approximate Operating Weights Lbs WeightsComponent Weights Lbs Weights Installed Shipping Casing Blank Weight Roof Curb WeightsSize Wt lbs Control Box Main 454 Convenience Outlet Options Filters OptionsSystem Control Fresh AirMiscellaneous Options Agency ApprovalElectronic Zone Sensors Field Installed AccessoriesRoof Curb General Mechanical SpecificationsElectrical System Air Handling System Mechanical Specifications Cooling System Chilled Water CoilWater Valve External Piping EnclosureMechanical Specifications Filters Percent Modulating Exhaust Fan Option Mechanical SpecificationsExhaust Air No Relief StandardFresh Air Mechanical Specifications Return AirHeating System CO2 Sensing Page RT-PRC031-EN