Trane RT-PRC031-EN manual Performance Data Supply Fan with Inlet Guide Vanes

Page 52

Performance Data — Supply Fan with Inlet Guide Vanes

Table 18 Supply Fan Performance STANDARD CFM — Casing A (25")

CFM

 

 

 

 

 

 

Total Static Pressure

 

 

 

 

 

 

 

Std.

6.25

6.50

6.75

7.00

7.25

7.50

7.75

8.00

Air

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16000

1657

24.15

1678

24.95

1697

25.68

1719

26.55

1739

27.34

1760

28.16

1780

28.98

1803

29.88

17000

1694

26.21

1715

27.05

1736

27.92

1755

28.73

1775

29.56

1795

30.43

1815

31.32

1833

32.11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18000

1734

28.48

1754

29.36

1773

30.16

1794

31.12

1813

31.98

1833

32.88

1853

33.82

1870

34.66

19000

1776

30.93

1794

31.76

1814

32.74

1833

33.62

1852

34.53

1871

35.48

1889

36.38

1908

37.32

20000

1820

33.62

1838

34.50

1856

35.41

1874

36.35

1892

37.26

1910

38.18

1929

39.21

1946

40.12

21000

1869

36.64

1885

37.52

1902

38.42

1919

39.35

1937

40.31

1954

41.30

1971

42.24

1988

43.21

22000

1918

39.84

1934

40.78

1951

41.75

1967

42.67

1983

43.61

1999

44.58

 

 

 

 

23000

1968

43.32

1984

44.25

1999

45.20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

Total Static Pressure

 

 

 

 

 

 

 

Std.

8.25

8.50

8.75

9.00

 

 

 

 

 

 

 

 

Air

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16000

1827

30.81

1849

31.71

1872

32.64

1895

33.60

 

 

 

 

 

 

 

 

17000

1853

33.00

1873

33.91

1892

34.76

1914

35.77

 

 

 

 

 

 

 

 

18000

1888

35.53

1906

36.42

1925

37.33

1944

38.28

 

 

 

 

 

 

 

 

19000

1927

38.29

1945

39.22

1962

40.11

1981

41.10

 

 

 

 

 

 

 

 

20000

1964

41.06

1983

42.11

1999

43.02

 

 

 

 

 

 

 

 

 

 

21000

2005

44.20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

1.Supply fan performance table includes internal resistance of air handler. For total static pressure determination, system external static pressure must be added to appropriate component sp drops (chilled water coil, filters, optional economizer, optional heating system).

2.Maximum SP leaving the air handler is 5.5" H20 positive.

(i)Outlined area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.

(ii)Outlined area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.

52

RT-PRC031-EN

Image 52
Contents IntelliPak II Air Handlers Introduction Table of Contents Standard Features Features and BenefitsControls Cabinet Mechanical Features and Benefits Optional Features Features and Benefits Field Installed Accessories Features SummaryInstallation and Service ReliabilityIntegrated Comfort with Trane Tracer LCI Features and Benefits Application FlexibilitySimplifying the Comfort System Interoperability Features and BenefitsOptimum Building Comfort Control Statitrac Direct Space Building Pressurization Control StatitracSupply Fans with Inlet Guide Vanes Variable Frequency Drives VFDControls Variable Air Volume VAV Only Supply Air Temperature Controls Supply Air Pressure ControlSupply Air Setpoint Reset Controls Variable Air Volume VAV OnlyHeating Zone Temperature Control Controls Constant Volume CV Only Occupied Zone Temperature ControlHeating Gas Heating Two-StageControls Constant Volume CV Only Auto Changeover Unoccupied Zone Temperature ControlCooling and Heating Hot Water or Steam HeatingControls VAV and CV Space Pressure Control StatitracMorning Warm-up Options Emergency OverrideControls VAV and CV Ventilation Override Module VOMGeneric Building Automation System Module Gbas 0-5 vdc Human Interface Panel HIHuman Interface Panel Main Menu Generic Building Automation System Module Gbas 0-10 vdc Chilled Water Coil Freeze StatSteam and Hot Water Coil Freeze Avoidance Night Setback SensorsDry Bulb Temperature Control of Economizer Occupied/Unoccupied input on the RTMTrane Tracer or BAS System Timed Override ActivationHumidification Control LonTalk Building Automation SystemReturn Fan Control TwinningApplications Considerations Exhaust/Return Fan OptionsApplication Recommendations AdvantagesSupply and Return Airflow Configurations Applications ConsiderationsSupply Airflow Configuration Return Airflow ConfigurationWith Bag CartridgeCorrosive Atmospheres Ventilation Override SequencesNatural Gas Heating Considerations Acoustical ConsiderationsUnit Placement Clearance RequirementsProtecting Hydronic Coils From Freezing Duct DesignExternal Piping Enclosure Selection Procedure Selection Procedure Exhaust Fan Motor Sizing Return Fan Motor SizingUnit Electrical Requirements Altitude CorrectionsModel Number Description Digit 7 Chilled Water Coil FIN SeriesModel Number Description Digit 20 System Control SelectionDigit 38 Belt Guards Burglar BARS/MARINE Lights General Data All dimensions in inches General DataGeneral Data Gas Heat Inputs/Input Ranges Economizer Outdoor Air Damper Leakage at rated airflowiInputs MBH Input MBH Range MBH Standard Damper Optional Low Leak DamperPerformance Adjustment Factors Wet Bulb Temperature Btu per PoundEnthalpy of Saturated Air Gas Heating Capacity Altitude Correction FactorsChilled Water Coil Capacities-2 Row 5W Performance Data-Chilled Water Coil CapacitiesDB F WB F Performance Data-Chilled Water Coil Capacities Chilled Water Coil Capacities-4 Row WChilled Water Coil Capacities-6 Row WD Chilled Water Coil Capacities-8 Row WD Supply Fan Performance Standard CFM Casing a Total Static Pressure Std Air1644 Supply Fan w/o IGV Supply Fan Performance Standard CFM -Casing B 9311117 Supply Fan Performance Standard CFM-Casing B Supply Fan Performance Standard CFM Casing C 7491019 Total Static Pressure Std AirPerformance Data Supply Fan with Inlet Guide Vanes Performance Data Supply Fan with Inlet Guide Vanes Supply Fan Performance Standard CFM-Casing a Supply Fan Performance Standard CFM Casing B 1093 1600 RPM 1500 RPM 779 1021 1283 Performance Data-Exhaust Fan Negative Static Pressure Std AirPerformance Data-Exhaust Fan Static PresureInWC237i Wocfm Exhaust Fan Performance Standard CFM-Case C 32 Fan 4150 R P M Performance Data-Return Fan Return Fan Performance Standard CFM-Case a 36.5 FanPerformance Data-Return Fan Return Fan PerformanceReturn Fan Performance Standard CFM-Case B and Case C 40 Fan Return Fan Performance Electric Heat Air Temperature Rise Performance Data-HeatNatural Gas Heating Capacities1 Electric Heat kw RangesPerformance Data-Heat Hot Water Coil Heating Capacities Q/ITDSteam Coil Heating Capacities Q/ITD Properties of SteamChilled Water Coil Airside Pressure Drop in H20 Component Static Pressure Drops in. H2OCartridge Filters Throw Temp Hi Temp Away Prefilter Casing High Low PD Cartridge Bag FiltersFilters Prefilter Supply Air Fan Drive Selections Drive NoHorse Power HP Low Casing Std Exhaust Air Fan Drive SelectionsReturn Air Fan Drive Selections 15 HP 20 HP 25 HP 30 HP 40 HP Drive NoElectrical Service Sizing Electrical DataSet 1. Cooling with Gas Heat Air Handling Units Set 2. Cooling with Electric HeatElectrical Service Sizing Data-Motors Electrical Data Voltage Utilization RangeUnit Voltage Nominal Tons Voltage 460 575 FLA Add 90-150Dimensional Data Unit Top/Front ViewUnit Dimensions In.-One-Piece Unit Dimensional DataReturn Exhaust Unit Height Fan Casing Opening Downflow/Horizontal Airflow Configuration DimensionsSupply Opening Blank Casing Gas Heat Section Electrical Entry Details Piping Chilled Water Piping Locations Minimum Required Clearance Unit Option Selection Door Swing Ft. StandardMinimum Required Clearance Ft Control Exh BoxBlank Casing Section Dimensions Blank Casing SectionCross Member Location Blank Casing Section Field Installed Sensors Variable Air Volume VAV Field Installed Sensors Constant Volume CV Field Installed Sensors VAV and CV Wireless Zone Sensor Wall or Duct Mount CO2 Zone Sensors Approximate Operating Weights Lbs WeightsComponent Weights Lbs Weights Installed Shipping Casing Blank Weight Roof Curb WeightsSize Wt lbs Control Box Main 454 Convenience Outlet Options Options FiltersFresh Air System ControlAgency Approval Miscellaneous OptionsField Installed Accessories Electronic Zone SensorsRoof Curb General Mechanical SpecificationsElectrical System Mechanical Specifications Cooling System Chilled Water Coil Water ValveExternal Piping Enclosure Air Handling SystemMechanical Specifications Filters Mechanical Specifications Exhaust AirNo Relief Standard Percent Modulating Exhaust Fan OptionMechanical Specifications Return Air Fresh AirHeating System CO2 Sensing Page RT-PRC031-EN