Performance Data — Supply Fan with Inlet Guide Vanes

Table 20 Supply Fan Performance STANDARD CFM — Casing C (36")

CFM

 

 

 

Total Static Pressure

Std.

8.25

8.50

Air

RPM

BHP

RPM

BHP

 

 

 

 

 

27000

1276

52.75

1294

54.50

28000

1279

54.48

1297

56.19

29000

1280

56.01

1299

57.96

30000

1283

57.73

1302

59.69

31000

1288

59.61

1304

61.36

32000

1295

61.65

1311

63.45

33000

1303

63.72

1318

65.44

34000

1315

66.15

1328

67.84

35000

1328

68.64

1341

70.37

36000

1341

71.22

 

 

Notes:

1.Supply fan performance table includes internal resistance of air handler. For total static pressure determination, system external static pressure must be added to appropriate component sp drops (chilled water coil, filters, optional economizer, optional heating system).

2.Maximum SP leaving the air handler is 5.5" H20 positive.

(i)Outlined area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.

36" Supply Fan Performance with IGV

12

11

10

9

8

M F C O W

% 0 1

1300 RPM

 

M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M

 

 

 

 

 

 

 

 

 

M

 

 

 

 

 

 

F

 

 

M

 

 

 

 

 

F

 

 

 

 

 

 

F

C

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

C

O

 

F

 

 

 

WO

 

 

 

 

 

 

 

 

 

O

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

W

W

 

W

 

 

%

 

 

 

 

 

 

 

 

 

 

 

%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

%

 

 

0

 

 

 

 

 

 

 

 

 

 

 

0

%

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

0

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

O

CF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

F

M

 

 

O

 

 

W

 

 

 

 

 

 

0%

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

Static Presure(InWC)

7

6

5

4

3

2

1

0

1200 RPM

1100 RPM

1000 RPM

900 RPM

800RPM

700 RPM

 

 

1

 

 

5

 

1

B

 

H

 

0

P

7

B

 

H

.

 

P

5

 

B

 

 

H

 

 

P

 

 

 

 

 

5

 

 

 

 

0

 

 

4

 

BHP

 

 

0

 

 

 

B

 

 

 

3

HP

 

 

 

0

 

 

 

25

B

 

 

 

HP

 

 

20

BH

 

 

 

P

 

 

B

 

 

 

H

 

 

 

 

P

 

 

 

 

7

 

5

 

B

 

H

6

P

0

 

B

 

H

 

P

 

 

M

F

C

 

O

 

W

 

%

 

0

 

8

 

 

 

FM

 

W

OC

%

 

 

 

90

 

 

0 5000

10000

15000

20000

25000

30000

35000

40000

45000

50000

55000

Volumetric Airflow Rate(CFM)

Figure 22. Supply Fan Performance STANDARD CFM —Casing C (36")

RT-PRC031-EN

59

Image 59
Contents IntelliPak II Air Handlers Introduction Table of Contents Controls Cabinet Mechanical Features and BenefitsStandard Features Features and Benefits Optional Features Reliability Features and Benefits Field Installed AccessoriesFeatures Summary Installation and ServiceSimplifying the Comfort System Features and Benefits Application FlexibilityIntegrated Comfort with Trane Tracer LCI Optimum Building Comfort Control Features and BenefitsInteroperability Statitrac Statitrac Direct Space Building Pressurization ControlVariable Frequency Drives VFD Supply Fans with Inlet Guide VanesSupply Air Temperature Controls Supply Air Pressure Control Controls Variable Air Volume VAV OnlyHeating Controls Variable Air Volume VAV OnlySupply Air Setpoint Reset Zone Temperature Control Gas Heating Two-Stage Controls Constant Volume CV OnlyOccupied Zone Temperature Control HeatingHot Water or Steam Heating Controls Constant Volume CV Only Auto ChangeoverUnoccupied Zone Temperature Control Cooling and HeatingEmergency Override Controls VAV and CVSpace Pressure Control Statitrac Morning Warm-up OptionsVentilation Override Module VOM Controls VAV and CVHuman Interface Panel Main Menu Human Interface Panel HIGeneric Building Automation System Module Gbas 0-5 vdc Night Setback Sensors Generic Building Automation System Module Gbas 0-10 vdcChilled Water Coil Freeze Stat Steam and Hot Water Coil Freeze AvoidanceTimed Override Activation Dry Bulb Temperature Control of EconomizerOccupied/Unoccupied input on the RTM Trane Tracer or BAS SystemTwinning Humidification ControlLonTalk Building Automation System Return Fan ControlAdvantages Applications ConsiderationsExhaust/Return Fan Options Application RecommendationsApplications Considerations Supply and Return Airflow ConfigurationsCartridge Supply Airflow ConfigurationReturn Airflow Configuration With BagAcoustical Considerations Corrosive AtmospheresVentilation Override Sequences Natural Gas Heating ConsiderationsClearance Requirements Unit PlacementExternal Piping Enclosure Duct DesignProtecting Hydronic Coils From Freezing Selection Procedure Selection Procedure Altitude Corrections Exhaust Fan Motor SizingReturn Fan Motor Sizing Unit Electrical RequirementsDigit 7 Chilled Water Coil FIN Series Model Number DescriptionDigit 20 System Control Selection Model Number DescriptionDigit 38 Belt Guards Burglar BARS/MARINE Lights General Data General Data All dimensions in inchesGeneral Data Standard Damper Optional Low Leak Damper Gas Heat Inputs/Input RangesEconomizer Outdoor Air Damper Leakage at rated airflowi Inputs MBH Input MBH Range MBHGas Heating Capacity Altitude Correction Factors Performance Adjustment FactorsWet Bulb Temperature Btu per Pound Enthalpy of Saturated AirDB F WB F Performance Data-Chilled Water Coil CapacitiesChilled Water Coil Capacities-2 Row 5W Chilled Water Coil Capacities-4 Row W Performance Data-Chilled Water Coil CapacitiesChilled Water Coil Capacities-6 Row WD Chilled Water Coil Capacities-8 Row WD Total Static Pressure Std Air Supply Fan Performance Standard CFM Casing a1644 Supply Fan w/o IGV 931 Supply Fan Performance Standard CFM -Casing B1117 Supply Fan Performance Standard CFM-Casing B 749 Supply Fan Performance Standard CFM Casing C1019 Std Air Total Static PressurePerformance Data Supply Fan with Inlet Guide Vanes Performance Data Supply Fan with Inlet Guide Vanes Supply Fan Performance Standard CFM-Casing a Supply Fan Performance Standard CFM Casing B 1093 1600 RPM 1500 RPM 779 1021 1283 Negative Static Pressure Std Air Performance Data-Exhaust FanStatic PresureInWC Performance Data-Exhaust Fan237i Wocfm 415 Exhaust Fan Performance Standard CFM-Case C 32 Fan0 R P M Return Fan Performance Standard CFM-Case a 36.5 Fan Performance Data-Return FanReturn Fan Performance Performance Data-Return FanReturn Fan Performance Standard CFM-Case B and Case C 40 Fan Return Fan Performance Electric Heat kw Ranges Electric Heat Air Temperature RisePerformance Data-Heat Natural Gas Heating Capacities1Properties of Steam Performance Data-HeatHot Water Coil Heating Capacities Q/ITD Steam Coil Heating Capacities Q/ITDComponent Static Pressure Drops in. H2O Chilled Water Coil Airside Pressure Drop in H20Filters Prefilter High Low PD Cartridge Bag FiltersCartridge Filters Throw Temp Hi Temp Away Prefilter Casing Drive No Supply Air Fan Drive Selections15 HP 20 HP 25 HP 30 HP 40 HP Drive No Horse Power HP Low Casing StdExhaust Air Fan Drive Selections Return Air Fan Drive SelectionsSet 2. Cooling with Electric Heat Electrical Service SizingElectrical Data Set 1. Cooling with Gas Heat Air Handling UnitsElectrical Service Sizing Data-Motors Nominal Tons Voltage 460 575 FLA Add 90-150 Electrical DataVoltage Utilization Range Unit VoltageUnit Top/Front View Dimensional DataReturn Exhaust Unit Height Fan Casing Dimensional DataUnit Dimensions In.-One-Piece Unit Supply Opening Blank Casing Gas Heat Section Downflow/Horizontal Airflow Configuration DimensionsOpening Electrical Entry Details Piping Chilled Water Piping Locations Exh Box Minimum Required ClearanceUnit Option Selection Door Swing Ft. Standard Minimum Required Clearance Ft ControlCross Member Location Blank Casing Section Dimensions Blank Casing SectionBlank Casing Section Field Installed Sensors Variable Air Volume VAV Field Installed Sensors Constant Volume CV Field Installed Sensors VAV and CV Wireless Zone Sensor Wall or Duct Mount CO2 Zone Sensors Component Weights Lbs WeightsApproximate Operating Weights Lbs Weights Size Wt lbs Control Box Main 454 Convenience Outlet Roof Curb WeightsInstalled Shipping Casing Blank Weight Options Filters OptionsSystem Control Fresh AirMiscellaneous Options Agency ApprovalElectronic Zone Sensors Field Installed AccessoriesRoof Curb Electrical System Mechanical SpecificationsGeneral Air Handling System Mechanical Specifications Cooling System Chilled Water CoilWater Valve External Piping EnclosureMechanical Specifications Filters Percent Modulating Exhaust Fan Option Mechanical SpecificationsExhaust Air No Relief StandardFresh Air Mechanical Specifications Return AirHeating System CO2 Sensing Page RT-PRC031-EN