Trane RT-PRC031-EN manual Fresh Air, System Control

Page 96

Options

MERV 14, 90-95 percent, high temperature rated, cartridge, final filter option—Available on gas and electric heat units with eight foot blank section unit casing option only.

Twelve-inch deep cartridge filters are U.L. Class 1 and are mounted in a galvanized steel casing with a 7/8” nominal thickness header frame. These cartridge filters have an efficiency rating of MERV 14 per ASHRAE 52.2. To ensure maximum cartridge final filter life, high temperature rated two-inch prefilters are included with the cartridge filters. Filters are mounted in a galvanized steel filter frame bank.

MERV 17, 99.97 percent, standard temperature rated, HEPA, final filter option—Available on cooling only units with four or eight-foot blank section, as well as steam and hot water units with eight-foot blank section, unit casing only.

Twelve-inch deep HEPA filters are U.L. Class 1 and are mounted in a galvanized steel casing. These filters have an efficiency rating of MERV 17 per ASHRAE

52.2and an efficiency of 99.97% on a 0.3 micron DOP particle size. To ensure maximum HEPA final filter life, two-inch prefilters are included with the HEPA final filters. Filters are mounted in a galvanized steel filter frame bank.

MERV 17, 99.97 percent, high temperature rated, HEPA, final filter option—Available on gas and electric heat units with eight foot blank section unit casing option only.

Twelve-inch deep HEPA filters are U.L. Class 1 and are mounted in a galvanized steel casing. These filters have an efficiency rating of MERV 17 per ASHRAE

52.2and an efficiency of 99.97% on a 0.3 micron DOP particle size. To ensure maximum HEPA final filter life, high temperature rated two-inch prefilters are included with the HEPA final filters. Filters are mounted in a galvanized steel filter frame bank.

96

Fresh Air

0 to 25 percent Motorized Outside Air Damper—includes only an outside air opening with moisture eliminator and motorized position damper for drawing up to 25 percent outside air. The damper position can be set at the unit mounted Human Interface panel.

Economizer—Includes the primary temperature controls necessary to automatically use outdoor air for free cooling. Option includes modulating return and outside air dampers, high ambient temperature lockout, minimum position control and spring return motor.

Standard outside air dampers are provided with a leakage rate of 20 cfm/ft^2 at 1.0 in w.g. pressure difference. Optional Low leakage dampers are available with a leakage rate of 10 cfm/ft^2 (AMCA Class 2) at 1.0 inch w.g. pressure difference, as well as Ultra Low leakage dampers with a leakage rate of 4 cfm/ft^2 (AMCA Class 1) at 1.0 inch w.g. pressure difference.

The 0 to 100% fresh air economizer has three optional economizer controls available: comparative enthalpy, reference enthalpy, or dry bulb control.

Fresh Air Measurement—The Trane Traq™ airflow-monitoring solution allows direct measurement and control of fresh air. The Traq damper assembly consists of butterfly- type dampers. The bellmouth inlet of each damper guides air uniformly through a flow- sensing ring that accurately measures total and static pressure from 15 to 100 percent of nominal airflow. The damper assembly ventilation control module (VCM) produces a vdc signal that is proportional to airflow, re-calibrates itself once every 60 seconds, and automatically adjusts for temperature variations. When applied as part of an Integrated Comfort™ system (ICS) with the Tracer Summit™ building automation system, ventilation

airflow can be controlled dynamically and documented to verify compliance with ASHRAE Standard 62.1.

Demand Control Ventilation— When equipped with a CO2 sensor and the (VCM) module, the IntelliPak II controller modulates the fresh air damper position in order to minimize the unit energy consumption yet simultaneously meet the ventilation requirements of ASHRAE Std 62.1. The Traq airflow monitoring solution augments the system, allowing for measurement and control of fresh air airflow.

System Control

Constant Volume (CV)—Provided with all the necessary controls to operate the air handler from a zone sensor, including CV microprocessor unit control module and a unit mounted Human Interface Panel.

Variable Air Volume (VAV) Supply Air Temperature control without inlet guide vanes— Provided with all the necessary controls to operate a VAV air handler from the discharge air temperature, including discharge air microprocessor controller and discharge air sensor. The microprocessor controller coordinates the economizer control and the stages of cooling with zone or outdoor air reset capabilities and an adjustable control band to fine-tune the control to specific applications.

VAV Supply Air Temperature control with inlet guide vanes— Provided with all the necessary controls to control/operate a VAV air handler from the discharge air temperature, including a discharge air microprocessor controller, a discharge air sensor, pressure sensor and inlet guide vanes on the supply fan. The microprocessor controller coordinates the economizer control and the stages of cooling with zone or outdoor air reset capabilities and an adjustable control band to fine-tune the control to specific applications. The inlet guide vanes are used

RT-PRC031-EN

Image 96
Contents IntelliPak II Air Handlers Introduction Table of Contents Features and Benefits Standard FeaturesControls Cabinet Mechanical Features and Benefits Optional Features Features and Benefits Field Installed Accessories Features SummaryInstallation and Service ReliabilityFeatures and Benefits Application Flexibility Integrated Comfort with Trane Tracer LCISimplifying the Comfort System Features and Benefits InteroperabilityOptimum Building Comfort Control Statitrac Direct Space Building Pressurization Control StatitracSupply Fans with Inlet Guide Vanes Variable Frequency Drives VFDControls Variable Air Volume VAV Only Supply Air Temperature Controls Supply Air Pressure ControlControls Variable Air Volume VAV Only Supply Air Setpoint ResetHeating Zone Temperature Control Controls Constant Volume CV Only Occupied Zone Temperature ControlHeating Gas Heating Two-StageControls Constant Volume CV Only Auto Changeover Unoccupied Zone Temperature ControlCooling and Heating Hot Water or Steam HeatingControls VAV and CV Space Pressure Control StatitracMorning Warm-up Options Emergency OverrideControls VAV and CV Ventilation Override Module VOMHuman Interface Panel HI Generic Building Automation System Module Gbas 0-5 vdcHuman Interface Panel Main Menu Generic Building Automation System Module Gbas 0-10 vdc Chilled Water Coil Freeze StatSteam and Hot Water Coil Freeze Avoidance Night Setback SensorsDry Bulb Temperature Control of Economizer Occupied/Unoccupied input on the RTMTrane Tracer or BAS System Timed Override ActivationHumidification Control LonTalk Building Automation SystemReturn Fan Control TwinningApplications Considerations Exhaust/Return Fan OptionsApplication Recommendations AdvantagesSupply and Return Airflow Configurations Applications ConsiderationsSupply Airflow Configuration Return Airflow ConfigurationWith Bag CartridgeCorrosive Atmospheres Ventilation Override SequencesNatural Gas Heating Considerations Acoustical ConsiderationsUnit Placement Clearance RequirementsDuct Design Protecting Hydronic Coils From FreezingExternal Piping Enclosure Selection Procedure Selection Procedure Exhaust Fan Motor Sizing Return Fan Motor SizingUnit Electrical Requirements Altitude CorrectionsModel Number Description Digit 7 Chilled Water Coil FIN SeriesModel Number Description Digit 20 System Control SelectionDigit 38 Belt Guards Burglar BARS/MARINE Lights General Data All dimensions in inches General DataGeneral Data Gas Heat Inputs/Input Ranges Economizer Outdoor Air Damper Leakage at rated airflowiInputs MBH Input MBH Range MBH Standard Damper Optional Low Leak DamperPerformance Adjustment Factors Wet Bulb Temperature Btu per PoundEnthalpy of Saturated Air Gas Heating Capacity Altitude Correction FactorsPerformance Data-Chilled Water Coil Capacities Chilled Water Coil Capacities-2 Row 5WDB F WB F Performance Data-Chilled Water Coil Capacities Chilled Water Coil Capacities-4 Row WChilled Water Coil Capacities-6 Row WD Chilled Water Coil Capacities-8 Row WD Supply Fan Performance Standard CFM Casing a Total Static Pressure Std Air1644 Supply Fan w/o IGV Supply Fan Performance Standard CFM -Casing B 9311117 Supply Fan Performance Standard CFM-Casing B Supply Fan Performance Standard CFM Casing C 7491019 Total Static Pressure Std AirPerformance Data Supply Fan with Inlet Guide Vanes Performance Data Supply Fan with Inlet Guide Vanes Supply Fan Performance Standard CFM-Casing a Supply Fan Performance Standard CFM Casing B 1093 1600 RPM 1500 RPM 779 1021 1283 Performance Data-Exhaust Fan Negative Static Pressure Std AirPerformance Data-Exhaust Fan Static PresureInWC237i Wocfm Exhaust Fan Performance Standard CFM-Case C 32 Fan 4150 R P M Performance Data-Return Fan Return Fan Performance Standard CFM-Case a 36.5 FanPerformance Data-Return Fan Return Fan PerformanceReturn Fan Performance Standard CFM-Case B and Case C 40 Fan Return Fan Performance Electric Heat Air Temperature Rise Performance Data-HeatNatural Gas Heating Capacities1 Electric Heat kw RangesPerformance Data-Heat Hot Water Coil Heating Capacities Q/ITDSteam Coil Heating Capacities Q/ITD Properties of SteamChilled Water Coil Airside Pressure Drop in H20 Component Static Pressure Drops in. H2OHigh Low PD Cartridge Bag Filters Cartridge Filters Throw Temp Hi Temp Away Prefilter CasingFilters Prefilter Supply Air Fan Drive Selections Drive NoHorse Power HP Low Casing Std Exhaust Air Fan Drive SelectionsReturn Air Fan Drive Selections 15 HP 20 HP 25 HP 30 HP 40 HP Drive NoElectrical Service Sizing Electrical DataSet 1. Cooling with Gas Heat Air Handling Units Set 2. Cooling with Electric HeatElectrical Service Sizing Data-Motors Electrical Data Voltage Utilization RangeUnit Voltage Nominal Tons Voltage 460 575 FLA Add 90-150Dimensional Data Unit Top/Front ViewDimensional Data Unit Dimensions In.-One-Piece UnitReturn Exhaust Unit Height Fan Casing Downflow/Horizontal Airflow Configuration Dimensions OpeningSupply Opening Blank Casing Gas Heat Section Electrical Entry Details Piping Chilled Water Piping Locations Minimum Required Clearance Unit Option Selection Door Swing Ft. StandardMinimum Required Clearance Ft Control Exh BoxDimensions Blank Casing Section Blank Casing SectionCross Member Location Blank Casing Section Field Installed Sensors Variable Air Volume VAV Field Installed Sensors Constant Volume CV Field Installed Sensors VAV and CV Wireless Zone Sensor Wall or Duct Mount CO2 Zone Sensors Weights Approximate Operating Weights LbsComponent Weights Lbs Weights Roof Curb Weights Installed Shipping Casing Blank WeightSize Wt lbs Control Box Main 454 Convenience Outlet Options Options FiltersFresh Air System ControlAgency Approval Miscellaneous OptionsField Installed Accessories Electronic Zone SensorsRoof Curb Mechanical Specifications GeneralElectrical System Mechanical Specifications Cooling System Chilled Water Coil Water ValveExternal Piping Enclosure Air Handling SystemMechanical Specifications Filters Mechanical Specifications Exhaust AirNo Relief Standard Percent Modulating Exhaust Fan OptionMechanical Specifications Return Air Fresh AirHeating System CO2 Sensing Page RT-PRC031-EN