Trane RT-PRC031-EN manual Exhaust Fan Motor Sizing, Return Fan Motor Sizing, Altitude Corrections

Page 30

Selection Procedure

Exhaust Fan Motor Sizing

The exhaust/return fan is selected based on total return system negative static pressure and exhaust fan CFM. Return system negative static includes return duct static, and any other job site applicable static pressure drop.

Return duct static pressure = 0.30 inches.

Total return system negative static pressure = 0.30 inches.

Exhaust fan CFM = 36000 CFM

From Table 39, p. 77 the required BHP is 21.44 BHP at 400 RPM. Thus, the exhaust fan motor selected is 25 HP.

To select a drive, enter Table 37, p. 75 for a 25 HP motor and air handler "C". Drive selection number 4 - 400 RPM.

Return Fan Motor Sizing

The same static pressure and CFM considerations must be taken for return fan size, horsepower, and drive selection as are required for exhaust fan sizing. However, since the return fan runs continuously the sensible heat generated by the return fan motor must be included in the entering evaporator coil mixed air temperature equation.

In this selection, if the return motor BHP is equal to the exhaust motor BHP, 21.44 BHP = 58.1 MBH x 1000÷ (1.085 x 36000 Return CFM) = 1.5°F

an air density correction is needed to project accurate unit performance.

Figure 18, p. 37 shows the air density ratio at various temperatures and elevations.

The procedure to use when selecting a supply or exhaust/return fan at elevations and

temperatures other than standard is as follows:

1.First, determine the air density ratio using Figure 18, p. 37.

2.Divide the static pressure at the nonstandard condition by the air density ratio to obtain the corrected static pressure.

3.Use the actual CFM and the corrected static pressure to determine the fan RPM and BHP from the performance tables or curves.

4.The fan RPM is correct as selected.

5.BHP must be multiplied by the air density ratio to obtain the actual operating BHP.

In order to better illustrate this procedure, the following example is used:

Consider an air handler"C" that is to deliver 32000 actual CFM at 3-inches total static pressure (tsp), 55°F leaving air temperature, at an elevation of 5000 ft.

1.From Figure 18, p. 37, the air density ratio is 0.86.

2.Tsp = 3.0-inches / 0.86 = 3.49 inches tsp.

3.From fan performance Table 17, p. 48 air handler"C" (without inlet vanes) will deliver 32000 CFM at 3.49 inches TSP at 997 RPM and 30.27 BHP.

4.The RPM is correct as selected - 997 RPM.

5.BHP = 30.27 x 0.86 = 26.3 BHP actual.

Cooling coil MBH should be calculated at standard and then converted to actual using the correction factors in Table 6, p. 37, Table 7, p. 37, Table 8, p. 37. Apply these factors to the capacities selected at standard CFM so as to correct for the reduced mass flow rate across the condenser.

Heat selections other than gas heat will not be affected by altitude. Nominal gas capacity (output) should be multiplied by the factors given in Table 8, p. 37 before calculating the heating supply air temperature.

added to the return air temperature. Where altitudes are significantly above sea level, use Table 6, p. 37, Table 7, p. 37 and Table 8, p. 37 for applicable correction factors.

Unit Electrical Requirements

Selection procedures for electrical requirements for wire sizing amps, maximum fuse sizing, and dual element fuses are given in the electrical service section of this catalog.

Altitude Corrections

The air handler performance tables and curves of this catalog are based on standard air (.075 lbs/ft). If the airflow requirements are at other than standard conditions (sea level),

30

FAN MOTOR HEAT

 

300

 

 

 

 

 

 

 

 

 

 

 

250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Std Motor

 

 

 

 

 

 

MBH

200

 

 

Hi Efficiency Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat

150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Motor

100

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

0

10

20

30

40

50

60

70

80

90

100

Motor Brake Horse Power

PM1206

Figure 17. Fan Motor Heat

RT-PRC031-EN

Image 30
Contents IntelliPak II Air Handlers Introduction Table of Contents Features and Benefits Standard FeaturesControls Cabinet Mechanical Features and Benefits Optional Features Installation and Service Features and Benefits Field Installed AccessoriesFeatures Summary ReliabilityFeatures and Benefits Application Flexibility Integrated Comfort with Trane Tracer LCISimplifying the Comfort System Features and Benefits InteroperabilityOptimum Building Comfort Control Statitrac Direct Space Building Pressurization Control StatitracSupply Fans with Inlet Guide Vanes Variable Frequency Drives VFDControls Variable Air Volume VAV Only Supply Air Temperature Controls Supply Air Pressure ControlControls Variable Air Volume VAV Only Supply Air Setpoint ResetHeating Zone Temperature Control Heating Controls Constant Volume CV OnlyOccupied Zone Temperature Control Gas Heating Two-StageCooling and Heating Controls Constant Volume CV Only Auto ChangeoverUnoccupied Zone Temperature Control Hot Water or Steam HeatingMorning Warm-up Options Controls VAV and CVSpace Pressure Control Statitrac Emergency OverrideControls VAV and CV Ventilation Override Module VOMHuman Interface Panel HI Generic Building Automation System Module Gbas 0-5 vdcHuman Interface Panel Main Menu Steam and Hot Water Coil Freeze Avoidance Generic Building Automation System Module Gbas 0-10 vdcChilled Water Coil Freeze Stat Night Setback SensorsTrane Tracer or BAS System Dry Bulb Temperature Control of EconomizerOccupied/Unoccupied input on the RTM Timed Override ActivationReturn Fan Control Humidification ControlLonTalk Building Automation System TwinningApplication Recommendations Applications ConsiderationsExhaust/Return Fan Options AdvantagesSupply and Return Airflow Configurations Applications ConsiderationsWith Bag Supply Airflow ConfigurationReturn Airflow Configuration CartridgeNatural Gas Heating Considerations Corrosive AtmospheresVentilation Override Sequences Acoustical ConsiderationsUnit Placement Clearance RequirementsDuct Design Protecting Hydronic Coils From FreezingExternal Piping Enclosure Selection Procedure Selection Procedure Unit Electrical Requirements Exhaust Fan Motor SizingReturn Fan Motor Sizing Altitude CorrectionsModel Number Description Digit 7 Chilled Water Coil FIN SeriesModel Number Description Digit 20 System Control SelectionDigit 38 Belt Guards Burglar BARS/MARINE Lights General Data All dimensions in inches General DataGeneral Data Inputs MBH Input MBH Range MBH Gas Heat Inputs/Input RangesEconomizer Outdoor Air Damper Leakage at rated airflowi Standard Damper Optional Low Leak DamperEnthalpy of Saturated Air Performance Adjustment FactorsWet Bulb Temperature Btu per Pound Gas Heating Capacity Altitude Correction FactorsPerformance Data-Chilled Water Coil Capacities Chilled Water Coil Capacities-2 Row 5WDB F WB F Performance Data-Chilled Water Coil Capacities Chilled Water Coil Capacities-4 Row WChilled Water Coil Capacities-6 Row WD Chilled Water Coil Capacities-8 Row WD Supply Fan Performance Standard CFM Casing a Total Static Pressure Std Air1644 Supply Fan w/o IGV Supply Fan Performance Standard CFM -Casing B 9311117 Supply Fan Performance Standard CFM-Casing B Supply Fan Performance Standard CFM Casing C 7491019 Total Static Pressure Std AirPerformance Data Supply Fan with Inlet Guide Vanes Performance Data Supply Fan with Inlet Guide Vanes Supply Fan Performance Standard CFM-Casing a Supply Fan Performance Standard CFM Casing B 1093 1600 RPM 1500 RPM 779 1021 1283 Performance Data-Exhaust Fan Negative Static Pressure Std AirPerformance Data-Exhaust Fan Static PresureInWC237i Wocfm Exhaust Fan Performance Standard CFM-Case C 32 Fan 4150 R P M Performance Data-Return Fan Return Fan Performance Standard CFM-Case a 36.5 FanPerformance Data-Return Fan Return Fan PerformanceReturn Fan Performance Standard CFM-Case B and Case C 40 Fan Return Fan Performance Natural Gas Heating Capacities1 Electric Heat Air Temperature RisePerformance Data-Heat Electric Heat kw RangesSteam Coil Heating Capacities Q/ITD Performance Data-HeatHot Water Coil Heating Capacities Q/ITD Properties of SteamChilled Water Coil Airside Pressure Drop in H20 Component Static Pressure Drops in. H2OHigh Low PD Cartridge Bag Filters Cartridge Filters Throw Temp Hi Temp Away Prefilter CasingFilters Prefilter Supply Air Fan Drive Selections Drive NoReturn Air Fan Drive Selections Horse Power HP Low Casing StdExhaust Air Fan Drive Selections 15 HP 20 HP 25 HP 30 HP 40 HP Drive NoSet 1. Cooling with Gas Heat Air Handling Units Electrical Service SizingElectrical Data Set 2. Cooling with Electric HeatElectrical Service Sizing Data-Motors Unit Voltage Electrical DataVoltage Utilization Range Nominal Tons Voltage 460 575 FLA Add 90-150Dimensional Data Unit Top/Front ViewDimensional Data Unit Dimensions In.-One-Piece UnitReturn Exhaust Unit Height Fan Casing Downflow/Horizontal Airflow Configuration Dimensions OpeningSupply Opening Blank Casing Gas Heat Section Electrical Entry Details Piping Chilled Water Piping Locations Minimum Required Clearance Ft Control Minimum Required ClearanceUnit Option Selection Door Swing Ft. Standard Exh BoxDimensions Blank Casing Section Blank Casing SectionCross Member Location Blank Casing Section Field Installed Sensors Variable Air Volume VAV Field Installed Sensors Constant Volume CV Field Installed Sensors VAV and CV Wireless Zone Sensor Wall or Duct Mount CO2 Zone Sensors Weights Approximate Operating Weights LbsComponent Weights Lbs Weights Roof Curb Weights Installed Shipping Casing Blank WeightSize Wt lbs Control Box Main 454 Convenience Outlet Options Options FiltersFresh Air System ControlAgency Approval Miscellaneous OptionsField Installed Accessories Electronic Zone SensorsRoof Curb Mechanical Specifications GeneralElectrical System External Piping Enclosure Mechanical Specifications Cooling System Chilled Water CoilWater Valve Air Handling SystemMechanical Specifications Filters No Relief Standard Mechanical SpecificationsExhaust Air Percent Modulating Exhaust Fan OptionMechanical Specifications Return Air Fresh AirHeating System CO2 Sensing Page RT-PRC031-EN