Trane RT-PRC031-EN manual Agency Approval, Miscellaneous Options

Page 97

Options

with VAV air handlers to control duct static pressure. Option includes vanes and static pressure controls. Airfoil supply fans with inlet vanes are an efficient way to mechanically modulate airflow.

VAV Supply Air Temperature Control with Variable Frequency Drives w/o Bypass—Provided with all necessary controls to operate a VAV air handler from the discharge air temperature, including discharge air microprocessor controller and discharge air sensor. The microprocessor controller coordinates the economizer control and the stages of cooling with discharge air temperature reset capabilities. Includes factory installed and tested variable frequency drives (VFD) to provide supply fan motor speed modulation. VFD receives 0-10 vdc from the unit microprocessor based upon supply static pressure and causes the drive to accelerate or decelerate as required to maintain the supply static pressure setpoint.

VAV Supply Air Temperature Control with Variable Frequency Drives and Bypass—Bypass control provides full nominal airflow in the event of drive failure.

Agency Approval

Air Handlers can be provided with UL/CSA approval.

Miscellaneous Options

Marine Lights (Customer Powered)—A 120V master light switch is factory installed in the main unit control box for lighting control. The master switch is wired into an isolated terminal block with access for customer provided service. Marine light fixtures are supplied with 150W incandescent bulbs. Marine light fixtures are placed in the Supply Section (2), Fresh Air Section (1), Return Section (1), and Extended Casing Section (1) for units without Heat.

Non-Fused Disconnect Switch with External Handle—External

RT-PRC031-EN

handle enables the operator to disconnect unit power with the control box door closed for safety.

Unit Interrupt Rating—Using a non-fused circuit breaker for disconnect switch purposes a 65000 Amp rating is optionally available on 460/3/60 powered units and a 25000 Amp rating is available on 575/3/60 units. Fan motors and electric heat (if applicable) circuits are also equipped with series rated circuit breakers.

GFI Convenience Outlet (Factory Powered)—A 15A, 115V Ground Fault Interrupter convenience outlet is factory installed. It is wired and powered from a factory mounted transformer. Unit mounted non-fused disconnect with external handle is furnished with factory powered outlet.

Economizer Control with Comparative Enthalpy—used with the fresh air economizer, two enthalpy sensors are provided to compare total heat content of the indoor air and outdoor air to determine the most efficient air source when economizing.

Economizer Control with Reference Enthalpy—used with the fresh air economizer, an outdoor enthalpy sensor is provided to compare the total heat content of outdoor air to a locally adjustable setpoint. The setpoint is programmed at the human interface, or remote human interface, to determine if the outdoor enthalpy condition is suitable for economizer operation.

Economizer Control with Dry Bulb—used with the fresh air economizer, an outdoor temperature sensor is included for comparing the outdoor dry bulb temperature to a locally adjustable temperature setpoint. The setpoint is programmed either at the human interface, or remote human interface, to determine if outdoor air temperature is suitable for economizer operation.

Low Leak Dampers—Return air, fresh air and relief air dampers have chlorinated polyvinyl chloride gasketing to seal to a leakage rate of 10 cfm/ft^2 (AMCA Class 2) at 1.0 in w.g. pressure difference.

Ultra Low Leak Fresh Air Dampers—Dampers have chlorinated polyvinyl chloride gasketing to seal to a leakage rate of 4 cfm/ft^2 (AMCA Class 1) at 1.0 in w.g. pressure difference.

High Duct Temperature Thermostats—Two manual reset thermostats are provided with one located in the discharge section of the unit set at 240°F and the other in the return section set at 135°F. The air handler will shut down if the thermostats are tripped.

High Efficiency Motors—Supply and exhaust/return fans are provided with high efficiency motors.

High Efficiency TEFC Motors— Supply and exhaust/return fans are provided with high efficiency Totally Enclosed Fan Cooled motors.

Belt Guards—Supply and exhaust fans can be optionally equipped with a universal size belt guard to accommodate any applicable drive configuration. The guard totally encloses the drive system and is provided with a two-piece removable front panel for servicing. Return fan guards are also available with individually sized belt guard with a single-piece removable panel for servicing.

Airflow Paths—In addition to the traditional downflow supply and upflow return, horizontal supply and return is available. End return is also available on select units. For additional details on airflow configuration, see Table 1, p. 24 Table 2, p. 24

Burglar Bars—A grate system is available for the supply and return air duct connection areas on non-horizontal airflow path units to minimize unwanted intrusion into duct systems.

Generic Building Automation System (GBAS 0-5vdc) Module—

97

Image 97
Contents IntelliPak II Air Handlers Introduction Table of Contents Standard Features Features and BenefitsControls Cabinet Mechanical Features and Benefits Optional Features Features Summary Features and Benefits Field Installed AccessoriesInstallation and Service ReliabilityIntegrated Comfort with Trane Tracer LCI Features and Benefits Application FlexibilitySimplifying the Comfort System Interoperability Features and BenefitsOptimum Building Comfort Control Statitrac Statitrac Direct Space Building Pressurization ControlVariable Frequency Drives VFD Supply Fans with Inlet Guide VanesSupply Air Temperature Controls Supply Air Pressure Control Controls Variable Air Volume VAV OnlySupply Air Setpoint Reset Controls Variable Air Volume VAV OnlyHeating Zone Temperature Control Occupied Zone Temperature Control Controls Constant Volume CV OnlyHeating Gas Heating Two-StageUnoccupied Zone Temperature Control Controls Constant Volume CV Only Auto ChangeoverCooling and Heating Hot Water or Steam HeatingSpace Pressure Control Statitrac Controls VAV and CVMorning Warm-up Options Emergency OverrideVentilation Override Module VOM Controls VAV and CVGeneric Building Automation System Module Gbas 0-5 vdc Human Interface Panel HIHuman Interface Panel Main Menu Chilled Water Coil Freeze Stat Generic Building Automation System Module Gbas 0-10 vdcSteam and Hot Water Coil Freeze Avoidance Night Setback SensorsOccupied/Unoccupied input on the RTM Dry Bulb Temperature Control of EconomizerTrane Tracer or BAS System Timed Override ActivationLonTalk Building Automation System Humidification ControlReturn Fan Control TwinningExhaust/Return Fan Options Applications ConsiderationsApplication Recommendations AdvantagesApplications Considerations Supply and Return Airflow ConfigurationsReturn Airflow Configuration Supply Airflow ConfigurationWith Bag CartridgeVentilation Override Sequences Corrosive AtmospheresNatural Gas Heating Considerations Acoustical ConsiderationsClearance Requirements Unit PlacementProtecting Hydronic Coils From Freezing Duct DesignExternal Piping Enclosure Selection Procedure Selection Procedure Return Fan Motor Sizing Exhaust Fan Motor SizingUnit Electrical Requirements Altitude CorrectionsDigit 7 Chilled Water Coil FIN Series Model Number DescriptionDigit 20 System Control Selection Model Number DescriptionDigit 38 Belt Guards Burglar BARS/MARINE Lights General Data General Data All dimensions in inchesGeneral Data Economizer Outdoor Air Damper Leakage at rated airflowi Gas Heat Inputs/Input RangesInputs MBH Input MBH Range MBH Standard Damper Optional Low Leak DamperWet Bulb Temperature Btu per Pound Performance Adjustment FactorsEnthalpy of Saturated Air Gas Heating Capacity Altitude Correction FactorsChilled Water Coil Capacities-2 Row 5W Performance Data-Chilled Water Coil CapacitiesDB F WB F Chilled Water Coil Capacities-4 Row W Performance Data-Chilled Water Coil CapacitiesChilled Water Coil Capacities-6 Row WD Chilled Water Coil Capacities-8 Row WD Total Static Pressure Std Air Supply Fan Performance Standard CFM Casing a1644 Supply Fan w/o IGV 931 Supply Fan Performance Standard CFM -Casing B1117 Supply Fan Performance Standard CFM-Casing B 749 Supply Fan Performance Standard CFM Casing C1019 Std Air Total Static PressurePerformance Data Supply Fan with Inlet Guide Vanes Performance Data Supply Fan with Inlet Guide Vanes Supply Fan Performance Standard CFM-Casing a Supply Fan Performance Standard CFM Casing B 1093 1600 RPM 1500 RPM 779 1021 1283 Negative Static Pressure Std Air Performance Data-Exhaust FanStatic PresureInWC Performance Data-Exhaust Fan237i Wocfm 415 Exhaust Fan Performance Standard CFM-Case C 32 Fan0 R P M Return Fan Performance Standard CFM-Case a 36.5 Fan Performance Data-Return FanReturn Fan Performance Performance Data-Return FanReturn Fan Performance Standard CFM-Case B and Case C 40 Fan Return Fan Performance Performance Data-Heat Electric Heat Air Temperature RiseNatural Gas Heating Capacities1 Electric Heat kw RangesHot Water Coil Heating Capacities Q/ITD Performance Data-HeatSteam Coil Heating Capacities Q/ITD Properties of SteamComponent Static Pressure Drops in. H2O Chilled Water Coil Airside Pressure Drop in H20Cartridge Filters Throw Temp Hi Temp Away Prefilter Casing High Low PD Cartridge Bag FiltersFilters Prefilter Drive No Supply Air Fan Drive SelectionsExhaust Air Fan Drive Selections Horse Power HP Low Casing StdReturn Air Fan Drive Selections 15 HP 20 HP 25 HP 30 HP 40 HP Drive NoElectrical Data Electrical Service SizingSet 1. Cooling with Gas Heat Air Handling Units Set 2. Cooling with Electric HeatElectrical Service Sizing Data-Motors Voltage Utilization Range Electrical DataUnit Voltage Nominal Tons Voltage 460 575 FLA Add 90-150Unit Top/Front View Dimensional DataUnit Dimensions In.-One-Piece Unit Dimensional DataReturn Exhaust Unit Height Fan Casing Opening Downflow/Horizontal Airflow Configuration DimensionsSupply Opening Blank Casing Gas Heat Section Electrical Entry Details Piping Chilled Water Piping Locations Unit Option Selection Door Swing Ft. Standard Minimum Required ClearanceMinimum Required Clearance Ft Control Exh BoxBlank Casing Section Dimensions Blank Casing SectionCross Member Location Blank Casing Section Field Installed Sensors Variable Air Volume VAV Field Installed Sensors Constant Volume CV Field Installed Sensors VAV and CV Wireless Zone Sensor Wall or Duct Mount CO2 Zone Sensors Approximate Operating Weights Lbs WeightsComponent Weights Lbs Weights Installed Shipping Casing Blank Weight Roof Curb WeightsSize Wt lbs Control Box Main 454 Convenience Outlet Options Filters OptionsSystem Control Fresh AirMiscellaneous Options Agency ApprovalElectronic Zone Sensors Field Installed AccessoriesRoof Curb General Mechanical SpecificationsElectrical System Water Valve Mechanical Specifications Cooling System Chilled Water CoilExternal Piping Enclosure Air Handling SystemMechanical Specifications Filters Exhaust Air Mechanical SpecificationsNo Relief Standard Percent Modulating Exhaust Fan OptionFresh Air Mechanical Specifications Return AirHeating System CO2 Sensing Page RT-PRC031-EN