Trane RT-PRC031-EN manual Chilled Water Coil Capacities-6 Row WD

Page 40

Performance Data—Chilled Water Coil Capacities

Table 11 Chilled Water Coil Capacities—6 Row WD

 

 

 

 

 

 

 

Entering Dry Bulb/Wet Bulb 80/67 F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entering Water 45 F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water Temperature Rise F 10 F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Without Turbulators

 

 

 

 

 

With Turbulators

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air

 

Total

Sensible

 

 

 

Water

Water

Total

 

Sensible

 

 

Water

Water

Flow

 

capacity

capacity

Leaving

Leaving

 

Flow

PD

Capacity

 

Capacity

Leaving

Leaving

Flow

PD

CFM

FPF

(MBH)

(MBH)

DB (F)

WB (F)

 

GPM

(ft H2O)

(MBH)

 

(MBH)

DB (F)

WB (F)

GPM

(ft H2O)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16000

80

561

413

56.6

55.8

 

111.9

1.1

635

 

443

54.9

54.1

126.6

2.3

 

108

676

470

53.4

53.2

 

134.7

1.6

739

 

497

51.8

51.7

147.3

2.9

 

144

777

515

50.8

50.7

 

154.9

2.1

832

 

539

49.5

49.4

165.8

3.5

 

168

809

528

50.0

49.9

 

161.2

2.2

860

 

552

48.7

48.6

171.5

3.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20000

80

692

510

56.9

56.0

 

137.8

1.6

762

 

538

55.6

54.7

151.8

3.0

 

108

826

578

53.8

53.5

 

164.6

2.3

890

 

605

52.6

52.3

177.3

3.9

 

144

950

634

51.2

51.1

 

189.4

3.0

1008

 

659

50.1

50.0

200.9

4.9

 

168

993

652

50.4

50.3

 

197.8

3.3

1048

 

677

49.3

49.2

208.9

5.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

23000

80

780

577

57.2

56.2

 

155.4

2.1

849

 

605

56.1

55.1

169.2

3.6

 

108

929

655

54.2

53.9

 

185.2

2.9

995

 

682

53.1

52.8

198.2

4.8

 

144

1070

719

51.6

51.5

 

213.3

3.8

1131

 

746

50.6

50.5

225.5

6.0

 

168

1121

742

50.8

50.7

 

223.5

4.1

1181

 

768

49.7

49.6

235.3

6.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28000

80

913

684

57.8

56.7

 

181.9

2.8

983

 

712

56.9

55.8

195.9

4.7

 

108

1086

776

54.9

54.4

 

216.5

3.9

1156

 

805

53.9

53.5

230.4

6.2

 

144

1255

856

52.3

52.2

 

250.1

5.1

1323

 

885

51.3

51.2

263.7

7.9

 

168

1321

883

51.4

51.3

 

263.2

5.6

1388

 

913

50.4

50.3

276.7

8.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33000

80

1032

784

58.5

57.1

 

205.7

3.5

1105

 

813

57.7

56.4

220.2

5.7

 

108

1229

891

55.5

55.0

 

244.9

4.9

1304

 

921

54.7

54.2

259.8

7.7

 

144

1423

985

52.9

52.8

 

283.7

6.5

1499

 

1017

52.1

52.0

298.8

9.9

 

168

1504

1019

52.0

51.9

 

299.7

7.2

1581

 

1052

51.1

51.0

315.0

10.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38000

80

1141

879

59.0

57.6

 

227.5

4.3

1217

 

908

58.3

56.9

242.5

6.8

 

108

1359

1000

56.1

55.5

 

270.9

5.9

1439

 

1032

55.4

54.8

286.9

9.2

 

144

1578

1108

53.6

53.4

 

314.6

7.9

1663

 

1143

52.7

52.6

331.5

12.0

 

168

-

-

-

-

 

-

-

-

 

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

43000

80

1242

969

59.6

58.0

 

247.4

5.0

1320

 

1000

58.9

57.3

263.1

7.9

 

108

1479

1104

56.7

56.0

 

294.8

7.0

1566

 

1138

56.0

55.3

312.0

10.7

 

144

-

-

-

-

 

-

-

-

 

-

-

-

-

-

 

168

-

-

-

-

 

-

-

-

 

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45000

80

1279

1004

59.8

58.1

 

255.0

5.3

1359

 

1035

59.1

57.5

270.9

8.3

 

108

1525

1144

56.9

56.2

 

303.9

7.4

1614

 

1180

56.2

55.5

321.7

11.3

 

144

-

-

-

-

 

-

-

-

 

-

-

-

-

-

 

168

-

-

-

-

 

-

-

-

 

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

RT-PRC031-EN

Image 40
Contents IntelliPak II Air Handlers Introduction Table of Contents Standard Features Features and BenefitsControls Cabinet Mechanical Features and Benefits Optional Features Features and Benefits Field Installed Accessories Features SummaryInstallation and Service ReliabilityIntegrated Comfort with Trane Tracer LCI Features and Benefits Application FlexibilitySimplifying the Comfort System Interoperability Features and BenefitsOptimum Building Comfort Control Statitrac Direct Space Building Pressurization Control StatitracSupply Fans with Inlet Guide Vanes Variable Frequency Drives VFDControls Variable Air Volume VAV Only Supply Air Temperature Controls Supply Air Pressure ControlSupply Air Setpoint Reset Controls Variable Air Volume VAV OnlyHeating Zone Temperature Control Controls Constant Volume CV Only Occupied Zone Temperature ControlHeating Gas Heating Two-StageControls Constant Volume CV Only Auto Changeover Unoccupied Zone Temperature ControlCooling and Heating Hot Water or Steam HeatingControls VAV and CV Space Pressure Control StatitracMorning Warm-up Options Emergency OverrideControls VAV and CV Ventilation Override Module VOMGeneric Building Automation System Module Gbas 0-5 vdc Human Interface Panel HIHuman Interface Panel Main Menu Generic Building Automation System Module Gbas 0-10 vdc Chilled Water Coil Freeze StatSteam and Hot Water Coil Freeze Avoidance Night Setback SensorsDry Bulb Temperature Control of Economizer Occupied/Unoccupied input on the RTMTrane Tracer or BAS System Timed Override ActivationHumidification Control LonTalk Building Automation SystemReturn Fan Control TwinningApplications Considerations Exhaust/Return Fan OptionsApplication Recommendations AdvantagesSupply and Return Airflow Configurations Applications ConsiderationsSupply Airflow Configuration Return Airflow ConfigurationWith Bag CartridgeCorrosive Atmospheres Ventilation Override SequencesNatural Gas Heating Considerations Acoustical ConsiderationsUnit Placement Clearance RequirementsProtecting Hydronic Coils From Freezing Duct DesignExternal Piping Enclosure Selection Procedure Selection Procedure Exhaust Fan Motor Sizing Return Fan Motor SizingUnit Electrical Requirements Altitude CorrectionsModel Number Description Digit 7 Chilled Water Coil FIN SeriesModel Number Description Digit 20 System Control SelectionDigit 38 Belt Guards Burglar BARS/MARINE Lights General Data All dimensions in inches General DataGeneral Data Gas Heat Inputs/Input Ranges Economizer Outdoor Air Damper Leakage at rated airflowiInputs MBH Input MBH Range MBH Standard Damper Optional Low Leak DamperPerformance Adjustment Factors Wet Bulb Temperature Btu per PoundEnthalpy of Saturated Air Gas Heating Capacity Altitude Correction FactorsChilled Water Coil Capacities-2 Row 5W Performance Data-Chilled Water Coil CapacitiesDB F WB F Performance Data-Chilled Water Coil Capacities Chilled Water Coil Capacities-4 Row WChilled Water Coil Capacities-6 Row WD Chilled Water Coil Capacities-8 Row WD Supply Fan Performance Standard CFM Casing a Total Static Pressure Std Air1644 Supply Fan w/o IGV Supply Fan Performance Standard CFM -Casing B 9311117 Supply Fan Performance Standard CFM-Casing B Supply Fan Performance Standard CFM Casing C 7491019 Total Static Pressure Std AirPerformance Data Supply Fan with Inlet Guide Vanes Performance Data Supply Fan with Inlet Guide Vanes Supply Fan Performance Standard CFM-Casing a Supply Fan Performance Standard CFM Casing B 1093 1600 RPM 1500 RPM 779 1021 1283 Performance Data-Exhaust Fan Negative Static Pressure Std AirPerformance Data-Exhaust Fan Static PresureInWC237i Wocfm Exhaust Fan Performance Standard CFM-Case C 32 Fan 4150 R P M Performance Data-Return Fan Return Fan Performance Standard CFM-Case a 36.5 FanPerformance Data-Return Fan Return Fan PerformanceReturn Fan Performance Standard CFM-Case B and Case C 40 Fan Return Fan Performance Electric Heat Air Temperature Rise Performance Data-HeatNatural Gas Heating Capacities1 Electric Heat kw RangesPerformance Data-Heat Hot Water Coil Heating Capacities Q/ITDSteam Coil Heating Capacities Q/ITD Properties of SteamChilled Water Coil Airside Pressure Drop in H20 Component Static Pressure Drops in. H2OCartridge Filters Throw Temp Hi Temp Away Prefilter Casing High Low PD Cartridge Bag FiltersFilters Prefilter Supply Air Fan Drive Selections Drive NoHorse Power HP Low Casing Std Exhaust Air Fan Drive SelectionsReturn Air Fan Drive Selections 15 HP 20 HP 25 HP 30 HP 40 HP Drive NoElectrical Service Sizing Electrical DataSet 1. Cooling with Gas Heat Air Handling Units Set 2. Cooling with Electric HeatElectrical Service Sizing Data-Motors Electrical Data Voltage Utilization RangeUnit Voltage Nominal Tons Voltage 460 575 FLA Add 90-150Dimensional Data Unit Top/Front ViewUnit Dimensions In.-One-Piece Unit Dimensional DataReturn Exhaust Unit Height Fan Casing Opening Downflow/Horizontal Airflow Configuration DimensionsSupply Opening Blank Casing Gas Heat Section Electrical Entry Details Piping Chilled Water Piping Locations Minimum Required Clearance Unit Option Selection Door Swing Ft. StandardMinimum Required Clearance Ft Control Exh BoxBlank Casing Section Dimensions Blank Casing SectionCross Member Location Blank Casing Section Field Installed Sensors Variable Air Volume VAV Field Installed Sensors Constant Volume CV Field Installed Sensors VAV and CV Wireless Zone Sensor Wall or Duct Mount CO2 Zone Sensors Approximate Operating Weights Lbs WeightsComponent Weights Lbs Weights Installed Shipping Casing Blank Weight Roof Curb WeightsSize Wt lbs Control Box Main 454 Convenience Outlet Options Options FiltersFresh Air System ControlAgency Approval Miscellaneous OptionsField Installed Accessories Electronic Zone SensorsRoof Curb General Mechanical SpecificationsElectrical System Mechanical Specifications Cooling System Chilled Water Coil Water ValveExternal Piping Enclosure Air Handling SystemMechanical Specifications Filters Mechanical Specifications Exhaust AirNo Relief Standard Percent Modulating Exhaust Fan OptionMechanical Specifications Return Air Fresh AirHeating System CO2 Sensing Page RT-PRC031-EN