Trane RT-PRC031-EN manual Applications Considerations, Supply and Return Airflow Configurations

Page 23

Applications Considerations

The Trane 100 percent modulating exhaust system with Statitrac provides efficient control of building pressure in most applications simply because 100 percent modulating exhaust discharge dampers (or VFD) are controlled directly from building pressure, rather than from an indirect indicator of building pressure, such as outdoor air damper position.

100 Percent Modulating Exhaust System without Statitrac, Constant Volume Units Only

This fan system has performance capabilities equal to the supply fan. The FC exhaust fans are started by the economizer's outdoor air damper position and the exhaust dampers track the economizer outdoor air damper position. The amount of air exhausted by this fan is controlled by modulating discharge dampers at the fan outlet. The discharge damper position is controlled by a signal that varies with the position of the economizer dampers. When the exhaust fans start, the modulating discharge dampers are fully closed, and exhaust airflow is 15 to 20 percent of total exhaust capabilities.

Advantages:

The exhaust fan runs only when the economizer reaches the desired exhaust enable point.

Exhaust dampers are modulated based on the economizer position.

The exhaust fan discharges in a single direction resulting in more efficient fan operation compared to return fan systems.

When discharge dampers are utilized to modulate the exhaust airflow, the exhaust fan may be running unloaded whenever the economizer dampers are less than 100 percent open.

The Trane 100 percent modulating exhaust system provides excellent linear control of building exhaust in most applications where maintaining building pressure is not important.

100 Percent Modulating Return Fan Systems with Statitrac™ Control, Constant Volume and VAV units

For both CV and VAV applications, the IntelliPak II air handler offers 100 percent modulating return fan systems. A differential pressure control system, Statitrac, uses a differential pressure transducer to compare indoor building pressure to atmospheric pressure. The return fan exhaust dampers are modulated, based on space pressure, to control the building pressure to within the adjustable, specified deadband that is set at the Human Interface Panel. A VFD modulates the return fan speed based on return duct static pressure. Economizer and return air dampers are modulated independent of the exhaust dampers based on ventilation control and economizer cooling requests.

Advantages:

The return fan operates independently of the supply fan to provide proper balance throughout the airflow envelope.

Statitrac compensates for pressure variations within the building from remote exhaust fans and makeup air units.

The return fan acts as both exhaust and return fan based on operation requirements.

The Trane 100 percent modulating return system with Statitrac provides efficient control of building pressure in applications with higher return duct static pressure and applications requiring duct returns.

Exhaust discharge dampers are controlled directly from building pressure, return fan VFD is controlled from return static pressure, and return/economizer dampers are controlled based on ventilation control and economizer cooling requests. 100 Percent Modulating Return Fan without Statitrac™ Control, Constant Volume Units Only

The exhaust discharge dampers are modulated in response to building pressure. The return fan runs continuously while the supply fan is energized.

Economizer and return air dampers are modulated independent of the exhaust dampers based on ventilation control, and economizer cooling requests.

Advantages:

The exhaust dampers are modulated as needed through a space pressure sensor input to maintain building pressure.

The return fan discharges in two directions, thereby balancing exhaust and unit return air volumes.

Supply and Return Airflow Configurations

The typical air handler installation has both the supply and return air paths routed through the roof curb and building roof. However, many air handler installations require horizontal supply and/or return from the air handler because of a building's unique design or for acoustic considerations.

With IntelliPak II, there are several ways to accomplish horizontal supply, see Table 1, p. 24 and/or return, see Table 2, p. 24.

RT-PRC031-EN

23

Image 23
Contents IntelliPak II Air Handlers Introduction Table of Contents Controls Cabinet Mechanical Features and BenefitsStandard Features Features and Benefits Optional Features Reliability Features and Benefits Field Installed AccessoriesFeatures Summary Installation and ServiceSimplifying the Comfort System Features and Benefits Application FlexibilityIntegrated Comfort with Trane Tracer LCI Optimum Building Comfort Control Features and BenefitsInteroperability Statitrac Statitrac Direct Space Building Pressurization ControlVariable Frequency Drives VFD Supply Fans with Inlet Guide VanesSupply Air Temperature Controls Supply Air Pressure Control Controls Variable Air Volume VAV OnlyHeating Controls Variable Air Volume VAV OnlySupply Air Setpoint Reset Zone Temperature Control Gas Heating Two-Stage Controls Constant Volume CV OnlyOccupied Zone Temperature Control HeatingHot Water or Steam Heating Controls Constant Volume CV Only Auto ChangeoverUnoccupied Zone Temperature Control Cooling and HeatingEmergency Override Controls VAV and CVSpace Pressure Control Statitrac Morning Warm-up OptionsVentilation Override Module VOM Controls VAV and CVHuman Interface Panel Main Menu Human Interface Panel HIGeneric Building Automation System Module Gbas 0-5 vdc Night Setback Sensors Generic Building Automation System Module Gbas 0-10 vdcChilled Water Coil Freeze Stat Steam and Hot Water Coil Freeze AvoidanceTimed Override Activation Dry Bulb Temperature Control of EconomizerOccupied/Unoccupied input on the RTM Trane Tracer or BAS SystemTwinning Humidification ControlLonTalk Building Automation System Return Fan ControlAdvantages Applications ConsiderationsExhaust/Return Fan Options Application RecommendationsApplications Considerations Supply and Return Airflow ConfigurationsCartridge Supply Airflow ConfigurationReturn Airflow Configuration With BagAcoustical Considerations Corrosive AtmospheresVentilation Override Sequences Natural Gas Heating ConsiderationsClearance Requirements Unit PlacementExternal Piping Enclosure Duct DesignProtecting Hydronic Coils From Freezing Selection Procedure Selection Procedure Altitude Corrections Exhaust Fan Motor SizingReturn Fan Motor Sizing Unit Electrical RequirementsDigit 7 Chilled Water Coil FIN Series Model Number DescriptionDigit 20 System Control Selection Model Number DescriptionDigit 38 Belt Guards Burglar BARS/MARINE Lights General Data General Data All dimensions in inchesGeneral Data Standard Damper Optional Low Leak Damper Gas Heat Inputs/Input RangesEconomizer Outdoor Air Damper Leakage at rated airflowi Inputs MBH Input MBH Range MBHGas Heating Capacity Altitude Correction Factors Performance Adjustment FactorsWet Bulb Temperature Btu per Pound Enthalpy of Saturated AirDB F WB F Performance Data-Chilled Water Coil CapacitiesChilled Water Coil Capacities-2 Row 5W Chilled Water Coil Capacities-4 Row W Performance Data-Chilled Water Coil CapacitiesChilled Water Coil Capacities-6 Row WD Chilled Water Coil Capacities-8 Row WD Total Static Pressure Std Air Supply Fan Performance Standard CFM Casing a1644 Supply Fan w/o IGV 931 Supply Fan Performance Standard CFM -Casing B1117 Supply Fan Performance Standard CFM-Casing B 749 Supply Fan Performance Standard CFM Casing C1019 Std Air Total Static PressurePerformance Data Supply Fan with Inlet Guide Vanes Performance Data Supply Fan with Inlet Guide Vanes Supply Fan Performance Standard CFM-Casing a Supply Fan Performance Standard CFM Casing B 1093 1600 RPM 1500 RPM 779 1021 1283 Negative Static Pressure Std Air Performance Data-Exhaust FanStatic PresureInWC Performance Data-Exhaust Fan237i Wocfm 415 Exhaust Fan Performance Standard CFM-Case C 32 Fan0 R P M Return Fan Performance Standard CFM-Case a 36.5 Fan Performance Data-Return FanReturn Fan Performance Performance Data-Return FanReturn Fan Performance Standard CFM-Case B and Case C 40 Fan Return Fan Performance Electric Heat kw Ranges Electric Heat Air Temperature RisePerformance Data-Heat Natural Gas Heating Capacities1Properties of Steam Performance Data-HeatHot Water Coil Heating Capacities Q/ITD Steam Coil Heating Capacities Q/ITDComponent Static Pressure Drops in. H2O Chilled Water Coil Airside Pressure Drop in H20Filters Prefilter High Low PD Cartridge Bag FiltersCartridge Filters Throw Temp Hi Temp Away Prefilter Casing Drive No Supply Air Fan Drive Selections15 HP 20 HP 25 HP 30 HP 40 HP Drive No Horse Power HP Low Casing StdExhaust Air Fan Drive Selections Return Air Fan Drive SelectionsSet 2. Cooling with Electric Heat Electrical Service SizingElectrical Data Set 1. Cooling with Gas Heat Air Handling UnitsElectrical Service Sizing Data-Motors Nominal Tons Voltage 460 575 FLA Add 90-150 Electrical DataVoltage Utilization Range Unit VoltageUnit Top/Front View Dimensional DataReturn Exhaust Unit Height Fan Casing Dimensional DataUnit Dimensions In.-One-Piece Unit Supply Opening Blank Casing Gas Heat Section Downflow/Horizontal Airflow Configuration DimensionsOpening Electrical Entry Details Piping Chilled Water Piping Locations Exh Box Minimum Required ClearanceUnit Option Selection Door Swing Ft. Standard Minimum Required Clearance Ft ControlCross Member Location Blank Casing Section Dimensions Blank Casing SectionBlank Casing Section Field Installed Sensors Variable Air Volume VAV Field Installed Sensors Constant Volume CV Field Installed Sensors VAV and CV Wireless Zone Sensor Wall or Duct Mount CO2 Zone Sensors Component Weights Lbs WeightsApproximate Operating Weights Lbs Weights Size Wt lbs Control Box Main 454 Convenience Outlet Roof Curb WeightsInstalled Shipping Casing Blank Weight Options Filters OptionsSystem Control Fresh AirMiscellaneous Options Agency ApprovalElectronic Zone Sensors Field Installed AccessoriesRoof Curb Electrical System Mechanical SpecificationsGeneral Air Handling System Mechanical Specifications Cooling System Chilled Water CoilWater Valve External Piping EnclosureMechanical Specifications Filters Percent Modulating Exhaust Fan Option Mechanical SpecificationsExhaust Air No Relief StandardFresh Air Mechanical Specifications Return AirHeating System CO2 Sensing Page RT-PRC031-EN