Trane RT-PRC031-EN manual Performance Data-Return Fan

Page 66

Performance Data—Return Fan

Table 25 Return Fan Performance STANDARD CFM—Case A (36.5" Fan)

CFM

 

 

 

 

 

 

 

Negative Static Pressure

 

 

 

 

 

 

Std.

0.25

0.50

0.75

1.00

1.25

1.50

1.75

2.00

Air

RPM

BHP

 

RPM

BHP

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16000

614(i)

2.65

647

3.39

678

4.15

709

5.00

739

5.83

767

6.65

797

7.53

825

8.41

17000

648

3.07

680

3.87

 

 

 

739

5.53

767

6.44

795

7.31

822

8.19

849

9.11

 

710

4.66

18000

683

3.55

 

 

 

 

741

5.22

769

6.10

797

7.08

823

8.01

848

8.92

875

9.89

713

4.39

 

19000

 

 

 

746

4.96

773

5.84

799

6.74

826

7.72

851

8.74

876

9.73

900

10.69

717

4.07

 

20000

752

4.65

780

5.57

806

6.51

831

7.45

855

8.44

881

9.52

904

10.56

928

11.60

21000

787

5.29

813

6.25

839

7.23

863

8.21

886

9.21

910

10.33

934

11.45

956

12.53

22000

822

5.99

847

6.99

872

8.02

895

9.04

917

10.07

940

11.17

963

12.34

985

13.54

23000

858

6.75

881

7.80

905

8.87

928

9.93

949

11.00

971

12.11

992

13.31

1014

14.55

24000

893

7.57

915

8.66

938

9.78

960

10.89

981

12.00

1002

13.13

1022

14.33

1043

15.61

25000

928

8.46

950

9.59

972

10.75

994

11.92

1014

13.07

1034

14.24

1054

15.46

1074

16.76

26000

964

9.43

984

10.60

1006

11.79

1026

13.00

1046

14.21

1066

15.42

1085

16.65

1104

17.95

27000

999

10.46

1019

11.67

1039

12.91

1060

14.17

1079

15.43

1098

16.67

1116

17.93

1135

19.24

28000

1035

11.57

1054

12.82

1073

14.11

1093

15.41

1112

16.73

1131

18.01

1148

19.31

1166

20.64

29000

1070

12.76

1089

14.06

1108

15.39

1127

16.72

1145

18.09

1163

19.43

1181

20.76

1198

22.11

30000

1106

14.04

1124

15.38

1142

16.73

1160

18.12

1179

19.53

1196

20.93

1213

22.31

1230

23.72

31000

1142

15.40

1159

16.77

1176

18.17

1194

19.61

1212

21.05

1229

22.50

1246

23.93

1262

25.35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

Negative Static Pressure

 

 

 

 

 

 

Std.

2.25

2.50

 

 

 

 

 

 

 

 

 

 

 

 

 

Air

RPM

BHP

 

RPM

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16000

851

9.29

876

10.20

 

 

 

 

 

 

 

 

 

 

 

 

 

17000

875

10.04

900

11.00

 

 

 

 

 

 

 

 

 

 

 

 

 

18000

901

10.86

925

11.84

 

 

 

 

 

 

 

 

 

 

 

 

 

19000

925

11.70

949

12.72

 

 

 

 

 

 

 

 

 

 

 

 

 

20000

951

12.61

974

13.68

 

 

 

 

 

 

 

 

 

 

 

 

 

21000

978

13.61

1000

14.69

 

 

 

 

 

 

 

 

 

 

 

 

 

22000

1007

14.67

1027

15.78

 

 

 

 

 

 

 

 

 

 

 

 

 

23000

1035

15.76

1056

16.95

 

 

 

 

 

 

 

 

 

 

 

 

 

24000

1064

16.89

1084

18.16

 

 

 

 

 

 

 

 

 

 

 

 

 

25000

1093

18.07

1113

19.41

 

 

 

 

 

 

 

 

 

 

 

 

 

26000

1123

19.32

1142

20.72

 

 

 

 

 

 

 

 

 

 

 

 

 

27000

1153

20.60

1172

22.06

 

 

 

 

 

 

 

 

 

 

 

 

 

28000

1183

21.99

1202

23.49

 

 

 

 

 

 

 

 

 

 

 

 

 

29000

1215

23.49

1232

24.97

 

 

 

 

 

 

 

 

 

 

 

 

 

30000

1247

25.14

1263

26.58

 

 

 

 

 

 

 

 

 

 

 

 

 

31000

1278

26.81

1294

28.28

 

 

 

 

 

 

 

 

 

 

 

 

 

(i)Outlined area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.

66

RT-PRC031-EN

Image 66
Contents IntelliPak II Air Handlers Introduction Table of Contents Features and Benefits Standard FeaturesControls Cabinet Mechanical Features and Benefits Optional Features Installation and Service Features and Benefits Field Installed AccessoriesFeatures Summary ReliabilityFeatures and Benefits Application Flexibility Integrated Comfort with Trane Tracer LCISimplifying the Comfort System Features and Benefits InteroperabilityOptimum Building Comfort Control Statitrac Direct Space Building Pressurization Control StatitracSupply Fans with Inlet Guide Vanes Variable Frequency Drives VFDControls Variable Air Volume VAV Only Supply Air Temperature Controls Supply Air Pressure ControlControls Variable Air Volume VAV Only Supply Air Setpoint ResetHeating Zone Temperature Control Heating Controls Constant Volume CV OnlyOccupied Zone Temperature Control Gas Heating Two-StageCooling and Heating Controls Constant Volume CV Only Auto ChangeoverUnoccupied Zone Temperature Control Hot Water or Steam HeatingMorning Warm-up Options Controls VAV and CVSpace Pressure Control Statitrac Emergency OverrideControls VAV and CV Ventilation Override Module VOMHuman Interface Panel HI Generic Building Automation System Module Gbas 0-5 vdcHuman Interface Panel Main Menu Steam and Hot Water Coil Freeze Avoidance Generic Building Automation System Module Gbas 0-10 vdcChilled Water Coil Freeze Stat Night Setback SensorsTrane Tracer or BAS System Dry Bulb Temperature Control of EconomizerOccupied/Unoccupied input on the RTM Timed Override ActivationReturn Fan Control Humidification ControlLonTalk Building Automation System TwinningApplication Recommendations Applications ConsiderationsExhaust/Return Fan Options AdvantagesSupply and Return Airflow Configurations Applications ConsiderationsWith Bag Supply Airflow ConfigurationReturn Airflow Configuration CartridgeNatural Gas Heating Considerations Corrosive AtmospheresVentilation Override Sequences Acoustical ConsiderationsUnit Placement Clearance RequirementsDuct Design Protecting Hydronic Coils From FreezingExternal Piping Enclosure Selection Procedure Selection Procedure Unit Electrical Requirements Exhaust Fan Motor SizingReturn Fan Motor Sizing Altitude CorrectionsModel Number Description Digit 7 Chilled Water Coil FIN SeriesModel Number Description Digit 20 System Control SelectionDigit 38 Belt Guards Burglar BARS/MARINE Lights General Data All dimensions in inches General DataGeneral Data Inputs MBH Input MBH Range MBH Gas Heat Inputs/Input RangesEconomizer Outdoor Air Damper Leakage at rated airflowi Standard Damper Optional Low Leak DamperEnthalpy of Saturated Air Performance Adjustment FactorsWet Bulb Temperature Btu per Pound Gas Heating Capacity Altitude Correction FactorsPerformance Data-Chilled Water Coil Capacities Chilled Water Coil Capacities-2 Row 5WDB F WB F Performance Data-Chilled Water Coil Capacities Chilled Water Coil Capacities-4 Row WChilled Water Coil Capacities-6 Row WD Chilled Water Coil Capacities-8 Row WD Supply Fan Performance Standard CFM Casing a Total Static Pressure Std Air1644 Supply Fan w/o IGV Supply Fan Performance Standard CFM -Casing B 9311117 Supply Fan Performance Standard CFM-Casing B Supply Fan Performance Standard CFM Casing C 7491019 Total Static Pressure Std AirPerformance Data Supply Fan with Inlet Guide Vanes Performance Data Supply Fan with Inlet Guide Vanes Supply Fan Performance Standard CFM-Casing a Supply Fan Performance Standard CFM Casing B 1093 1600 RPM 1500 RPM 779 1021 1283 Performance Data-Exhaust Fan Negative Static Pressure Std AirPerformance Data-Exhaust Fan Static PresureInWC237i Wocfm Exhaust Fan Performance Standard CFM-Case C 32 Fan 4150 R P M Performance Data-Return Fan Return Fan Performance Standard CFM-Case a 36.5 FanPerformance Data-Return Fan Return Fan PerformanceReturn Fan Performance Standard CFM-Case B and Case C 40 Fan Return Fan Performance Natural Gas Heating Capacities1 Electric Heat Air Temperature RisePerformance Data-Heat Electric Heat kw RangesSteam Coil Heating Capacities Q/ITD Performance Data-HeatHot Water Coil Heating Capacities Q/ITD Properties of SteamChilled Water Coil Airside Pressure Drop in H20 Component Static Pressure Drops in. H2OHigh Low PD Cartridge Bag Filters Cartridge Filters Throw Temp Hi Temp Away Prefilter CasingFilters Prefilter Supply Air Fan Drive Selections Drive NoReturn Air Fan Drive Selections Horse Power HP Low Casing StdExhaust Air Fan Drive Selections 15 HP 20 HP 25 HP 30 HP 40 HP Drive NoSet 1. Cooling with Gas Heat Air Handling Units Electrical Service SizingElectrical Data Set 2. Cooling with Electric HeatElectrical Service Sizing Data-Motors Unit Voltage Electrical DataVoltage Utilization Range Nominal Tons Voltage 460 575 FLA Add 90-150Dimensional Data Unit Top/Front ViewDimensional Data Unit Dimensions In.-One-Piece UnitReturn Exhaust Unit Height Fan Casing Downflow/Horizontal Airflow Configuration Dimensions OpeningSupply Opening Blank Casing Gas Heat Section Electrical Entry Details Piping Chilled Water Piping Locations Minimum Required Clearance Ft Control Minimum Required ClearanceUnit Option Selection Door Swing Ft. Standard Exh BoxDimensions Blank Casing Section Blank Casing SectionCross Member Location Blank Casing Section Field Installed Sensors Variable Air Volume VAV Field Installed Sensors Constant Volume CV Field Installed Sensors VAV and CV Wireless Zone Sensor Wall or Duct Mount CO2 Zone Sensors Weights Approximate Operating Weights LbsComponent Weights Lbs Weights Roof Curb Weights Installed Shipping Casing Blank WeightSize Wt lbs Control Box Main 454 Convenience Outlet Options Options FiltersFresh Air System ControlAgency Approval Miscellaneous OptionsField Installed Accessories Electronic Zone SensorsRoof Curb Mechanical Specifications GeneralElectrical System External Piping Enclosure Mechanical Specifications Cooling System Chilled Water CoilWater Valve Air Handling SystemMechanical Specifications Filters No Relief Standard Mechanical SpecificationsExhaust Air Percent Modulating Exhaust Fan OptionMechanical Specifications Return Air Fresh AirHeating System CO2 Sensing Page RT-PRC031-EN