Trane RT-PRC031-EN manual Clearance Requirements, Unit Placement

Page 26

Applications Considerations

will help reduce sound transmission. The ASHRAE publication "A Practical Guide to Noise and Vibration Control for HVAC Systems" also provides valuable information.

There are several other sources of unit sound, i.e., supply fan, exhaust/ return fans, and aerodynamic noise generated at the duct fittings. Refer to the ASHRAE Applications Handbook, Chapter 47, 2003 edition for guidelines for minimizing the generation of aerodynamic noise associated with duct fittings. A good source of information on general acoustical considerations for air handlers is the 2000 ASHRAE Journal article titled, "Controlling Noise from Large Rooftop Units".

The Trane Acoustic Program (TAP) allows complete modeling of air handler acoustical installation parameters. The software models airborne sound from supply and return ducts, as well as duct breakout and roof transmission sound, so that the designer can identify potential sound problems and make design alterations before equipment installation. Output of the program shows the resulting NC (or RC) level for any point in the occupied space. TAP is also capable of modeling the effect of outdoor sound on the surrounding area. This program is available from Trane's Customer Direct Service NetworkTM (C.D.S.), ask your local Trane representative for additional information on this program.

Clearance Requirements

The recommended clearances identified in Figure 31, p. 85 should be maintained to assure adequate service capability, maximum capacity and peak operating efficiency. If the clearances shown are not possible on a particular job, consider the following:

Do the clearances available allow for major service work such as changing coils?

Do the clearances available allow for proper outside air intake and exhaust air removal?

If screening around the unit is being used, is there a possibility of air recirculation from the exhaust to the outside air intake?

26

Figure 15. Unit Placement

Air Intake

Outdoor

Exhaust

Air

Outdoor Air Intake

Outdoor Air Intake

Exhaust

Air

Actual clearances which appear inadequate should be reviewed with a local Trane sales engineer.

When two or more units are to be placed side by side, the distance between the units should be increased to 150 percent of the recommended single unit clearance. The units should also be staggered, see Figure 15, p. 26, for two reasons:

1

To reduce span deflection if more than one unit is placed on a single span. Reducing deflection discourages sound transmission.

2

To assure proper diffusion of exhaust air before contact with the outside air intake of adjacent unit.

Outdoor Air Intake

RT-PRC031-EN

Image 26
Contents IntelliPak II Air Handlers Introduction Table of Contents Controls Cabinet Mechanical Features and BenefitsStandard Features Features and Benefits Optional Features Installation and Service Features and Benefits Field Installed AccessoriesFeatures Summary ReliabilitySimplifying the Comfort System Features and Benefits Application FlexibilityIntegrated Comfort with Trane Tracer LCI Optimum Building Comfort Control Features and BenefitsInteroperability Statitrac Direct Space Building Pressurization Control StatitracSupply Fans with Inlet Guide Vanes Variable Frequency Drives VFDControls Variable Air Volume VAV Only Supply Air Temperature Controls Supply Air Pressure ControlHeating Controls Variable Air Volume VAV OnlySupply Air Setpoint Reset Zone Temperature Control Heating Controls Constant Volume CV OnlyOccupied Zone Temperature Control Gas Heating Two-StageCooling and Heating Controls Constant Volume CV Only Auto ChangeoverUnoccupied Zone Temperature Control Hot Water or Steam HeatingMorning Warm-up Options Controls VAV and CVSpace Pressure Control Statitrac Emergency OverrideControls VAV and CV Ventilation Override Module VOMHuman Interface Panel Main Menu Human Interface Panel HIGeneric Building Automation System Module Gbas 0-5 vdc Steam and Hot Water Coil Freeze Avoidance Generic Building Automation System Module Gbas 0-10 vdcChilled Water Coil Freeze Stat Night Setback SensorsTrane Tracer or BAS System Dry Bulb Temperature Control of EconomizerOccupied/Unoccupied input on the RTM Timed Override ActivationReturn Fan Control Humidification ControlLonTalk Building Automation System TwinningApplication Recommendations Applications ConsiderationsExhaust/Return Fan Options AdvantagesSupply and Return Airflow Configurations Applications ConsiderationsWith Bag Supply Airflow ConfigurationReturn Airflow Configuration CartridgeNatural Gas Heating Considerations Corrosive AtmospheresVentilation Override Sequences Acoustical ConsiderationsUnit Placement Clearance RequirementsExternal Piping Enclosure Duct DesignProtecting Hydronic Coils From Freezing Selection Procedure Selection Procedure Unit Electrical Requirements Exhaust Fan Motor SizingReturn Fan Motor Sizing Altitude CorrectionsModel Number Description Digit 7 Chilled Water Coil FIN SeriesModel Number Description Digit 20 System Control SelectionDigit 38 Belt Guards Burglar BARS/MARINE Lights General Data All dimensions in inches General DataGeneral Data Inputs MBH Input MBH Range MBH Gas Heat Inputs/Input RangesEconomizer Outdoor Air Damper Leakage at rated airflowi Standard Damper Optional Low Leak DamperEnthalpy of Saturated Air Performance Adjustment FactorsWet Bulb Temperature Btu per Pound Gas Heating Capacity Altitude Correction FactorsDB F WB F Performance Data-Chilled Water Coil CapacitiesChilled Water Coil Capacities-2 Row 5W Performance Data-Chilled Water Coil Capacities Chilled Water Coil Capacities-4 Row WChilled Water Coil Capacities-6 Row WD Chilled Water Coil Capacities-8 Row WD Supply Fan Performance Standard CFM Casing a Total Static Pressure Std Air1644 Supply Fan w/o IGV Supply Fan Performance Standard CFM -Casing B 9311117 Supply Fan Performance Standard CFM-Casing B Supply Fan Performance Standard CFM Casing C 7491019 Total Static Pressure Std AirPerformance Data Supply Fan with Inlet Guide Vanes Performance Data Supply Fan with Inlet Guide Vanes Supply Fan Performance Standard CFM-Casing a Supply Fan Performance Standard CFM Casing B 1093 1600 RPM 1500 RPM 779 1021 1283 Performance Data-Exhaust Fan Negative Static Pressure Std AirPerformance Data-Exhaust Fan Static PresureInWC237i Wocfm Exhaust Fan Performance Standard CFM-Case C 32 Fan 4150 R P M Performance Data-Return Fan Return Fan Performance Standard CFM-Case a 36.5 FanPerformance Data-Return Fan Return Fan PerformanceReturn Fan Performance Standard CFM-Case B and Case C 40 Fan Return Fan Performance Natural Gas Heating Capacities1 Electric Heat Air Temperature RisePerformance Data-Heat Electric Heat kw RangesSteam Coil Heating Capacities Q/ITD Performance Data-HeatHot Water Coil Heating Capacities Q/ITD Properties of SteamChilled Water Coil Airside Pressure Drop in H20 Component Static Pressure Drops in. H2OFilters Prefilter High Low PD Cartridge Bag FiltersCartridge Filters Throw Temp Hi Temp Away Prefilter Casing Supply Air Fan Drive Selections Drive NoReturn Air Fan Drive Selections Horse Power HP Low Casing StdExhaust Air Fan Drive Selections 15 HP 20 HP 25 HP 30 HP 40 HP Drive NoSet 1. Cooling with Gas Heat Air Handling Units Electrical Service SizingElectrical Data Set 2. Cooling with Electric HeatElectrical Service Sizing Data-Motors Unit Voltage Electrical DataVoltage Utilization Range Nominal Tons Voltage 460 575 FLA Add 90-150Dimensional Data Unit Top/Front ViewReturn Exhaust Unit Height Fan Casing Dimensional DataUnit Dimensions In.-One-Piece Unit Supply Opening Blank Casing Gas Heat Section Downflow/Horizontal Airflow Configuration DimensionsOpening Electrical Entry Details Piping Chilled Water Piping Locations Minimum Required Clearance Ft Control Minimum Required ClearanceUnit Option Selection Door Swing Ft. Standard Exh BoxCross Member Location Blank Casing Section Dimensions Blank Casing SectionBlank Casing Section Field Installed Sensors Variable Air Volume VAV Field Installed Sensors Constant Volume CV Field Installed Sensors VAV and CV Wireless Zone Sensor Wall or Duct Mount CO2 Zone Sensors Component Weights Lbs WeightsApproximate Operating Weights Lbs Weights Size Wt lbs Control Box Main 454 Convenience Outlet Roof Curb WeightsInstalled Shipping Casing Blank Weight Options Options FiltersFresh Air System ControlAgency Approval Miscellaneous OptionsField Installed Accessories Electronic Zone SensorsRoof Curb Electrical System Mechanical SpecificationsGeneral External Piping Enclosure Mechanical Specifications Cooling System Chilled Water CoilWater Valve Air Handling SystemMechanical Specifications Filters No Relief Standard Mechanical SpecificationsExhaust Air Percent Modulating Exhaust Fan OptionMechanical Specifications Return Air Fresh AirHeating System CO2 Sensing Page RT-PRC031-EN