
Controls Variable Air Volume (VAV) Only
overheat. The supply air temperature setpoint is adjusted based on the temperature of the critical zone(s). This can have the effect of improving comfort and/or lowering energy usage. The
Supply Air Tempering
Modulating gas, electric, hot water and steam heat units
Zone Temperature
Control
Unoccupied Zone Heating and Cooling
During Unoccupied mode, the unit is operated as a CV unit. Inlet guide vanes are driven full open, VFDs operate at 100%, and VAV boxes are driven full open. The unit controls zone temperature within the Unoccupied zone cooling and heating (heating units only) setpoints.
Daytime warm-up
This feature is available on all types of heating units. During Occupied mode, if the zone temperature falls to a preset,
Fresh Air Measurement
Trane air quality (TRAQ™) fresh air measurement damper system utilizes velocity pressure sensing rings. Based on unit design CFM, the ventilation control module (VCM) monitors and controls the quantity of fresh outside air entering the unit. The outside airflow can be calibrated to accommodate for altitude.
a.An optional temperature sensor may be connected to the ventilation control module to enable it to control a
b.An optional CO2 sensor may be connected to the ventilation control module to control fresh air based on CO2 Demand Control Ventilation (DCV).
Outside Air CFM
Compensation
As the supply fan (IGV or VFD) modulates, this function proportionally adjusts the economizer minimum position to compensate for the change in total airflow, in order to maintain a constant percent of outside air. The modified economizer minimum position is computed as a linear function, based on IGV or VFD position, given the two endpoints,
a.Minimum Position with IGV/ VFD @ 0%
b.Minimum Position with IGV/ VFD @ 100%
which are user adjustable at the Human Interface Panel.
13 |