General Data
Table 4 Gas Heat Inputs/Input Ranges
| |||
|
|
|
|
Standard Gas |
|
| Modulating |
Heat Input | Low Gas Heat | High Fire Heat | Gas Heat |
(MBH) | Inputs (MBH) | Input (MBH) | Range (MBH) |
|
|
|
|
850 | 425 | 850 | |
|
|
|
|
1100 | 550 | 1100 | |
|
|
|
|
1800 | 900 | 1800 | |
|
|
|
|
Table 5 Economizer Outdoor Air Damper Leakage (at rated airflow)(i)
Standard Damper | 20 |
|
|
Optional “Low Leak" Damper | 10 (Class 2 AMCA |
|
|
Optional “Ultra Low Leak” Damper | 4 (Class 1 AMCA |
|
|
(i)Leakage/ft^2 at 1.0 in WC pressure difference
36 |