Trane RT-PRC031-EN manual Performance Data-Chilled Water Coil Capacities, Db F Wb F

Page 38

Performance Data—Chilled Water

Coil Capacities

Table 9 Chilled Water Coil Capacities—2 Row 5W

 

 

 

 

 

 

 

Entering Dry Bulb/Wet Bulb 80/67 F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entering Water 45 F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water Temperature Rise F 10 F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Without Turbulators

 

 

 

 

 

With Turbulators

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air

 

Total

Sensible

 

 

 

Water

Water

Total

 

Sensible

 

 

Water

Water

Flow

 

capacity

capacity

Leaving

Leaving

 

Flow

PD

Capacity

 

Capacity

Leaving

Leaving

Flow

PD

CFM

FPF

(MBH)

(MBH)

DB (F)

WB (F)

 

GPM

(ft H2O)

(MBH)

 

(MBH)

DB (F)

WB (F)

GPM

(ft H2O)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16000

80

179

179

69.9

63.7

 

35.7

0.2

333

 

253

65.7

60.7

66.4

1.8

 

108

308

275

64.4

61.2

 

61.3

0.6

425

 

320

61.9

58.8

84.7

2.6

 

144

428

351

60.1

58.7

 

85.4

1.1

540

 

395

57.6

56.3

107.7

3.8

 

168

472

375

58.8

57.7

 

94.1

1.3

587

 

420

56.2

55.2

117.0

4.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20000

80

256

250

68.7

63.2

 

51.0

0.4

380

 

296

66.6

61.3

75.8

2.2

 

108

372

332

65.0

61.4

 

74.1

0.8

486

 

375

63.0

59.5

96.8

3.2

 

144

503

421

60.9

59.2

 

100.3

1.4

618

 

465

58.9

57.3

123.2

4.7

 

168

555

451

59.6

58.3

 

110.7

1.7

676

 

498

57.4

56.3

134.7

5.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

23000

80

294

283

68.8

63.2

 

58.6

0.5

412

 

327

67.1

61.6

82.1

2.5

 

108

413

370

65.4

61.6

 

82.3

1.0

526

 

413

63.7

60.0

104.9

3.6

 

144

552

469

61.5

59.6

 

110.0

1.7

670

 

514

59.7

57.9

133.6

5.4

 

168

610

504

60.1

58.8

 

121.6

2.1

736

 

552

58.2

56.9

146.7

6.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28000

80

348

333

69.2

63.3

 

69.4

0.7

460

 

375

67.9

62.1

91.7

2.9

 

108

473

430

66.1

61.9

 

94.2

1.3

587

 

473

64.7

60.6

117.1

4.3

 

144

623

543

62.4

60.2

 

124.2

2.1

748

 

590

60.9

58.7

149.1

6.5

 

168

690

586

61.0

59.4

 

137.5

2.6

825

 

638

59.3

57.8

164.5

7.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33000

80

394

379

69.6

63.5

 

78.4

0.9

503

 

419

68.5

62.4

100.3

3.4

 

108

525

485

66.7

62.2

 

104.6

1.6

641

 

529

65.5

61.1

127.8

5.0

 

144

684

612

63.2

60.7

 

136.4

2.5

816

 

661

61.8

59.4

162.7

7.6

 

168

759

663

61.8

59.9

 

151.3

3.1

904

 

717

60.3

58.5

180.2

9.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38000

80

433

421

70.0

63.6

 

86.4

1.1

542

 

461

69.0

62.7

108.1

3.8

 

108

571

536

67.2

62.5

 

113.8

1.8

690

 

581

66.1

61.5

137.6

5.7

 

144

739

676

63.9

61.1

 

147.3

2.9

878

 

727

62.6

59.9

174.9

8.6

 

168

-

-

-

-

 

-

-

-

 

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

43000

80

469

461

70.3

63.8

 

93.5

1.3

578

 

500

69.4

63.0

115.2

4.2

 

108

612

585

67.7

62.7

 

122.0

2.1

735

 

630

66.7

61.9

146.4

6.3

 

144

-

-

-

-

 

-

-

-

 

-

-

-

-

-

 

168

-

-

-

-

 

-

-

-

 

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45000

80

482

476

70.4

63.8

 

96.2

1.3

591

 

515

69.6

63.1

117.9

4.4

 

108

628

603

67.8

62.8

 

125.1

2.2

751

 

649

66.9

62.0

149.8

6.6

 

144

-

-

-

-

 

-

-

-

 

-

-

-

-

-

 

168

-

-

-

-

 

-

-

-

 

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38

RT-PRC031-EN

Image 38
Contents IntelliPak II Air Handlers Introduction Table of Contents Controls Cabinet Mechanical Features and BenefitsStandard Features Features and Benefits Optional Features Installation and Service Features and Benefits Field Installed AccessoriesFeatures Summary ReliabilitySimplifying the Comfort System Features and Benefits Application FlexibilityIntegrated Comfort with Trane Tracer LCI Optimum Building Comfort Control Features and BenefitsInteroperability Statitrac Direct Space Building Pressurization Control StatitracSupply Fans with Inlet Guide Vanes Variable Frequency Drives VFDControls Variable Air Volume VAV Only Supply Air Temperature Controls Supply Air Pressure ControlHeating Controls Variable Air Volume VAV OnlySupply Air Setpoint Reset Zone Temperature Control Heating Controls Constant Volume CV OnlyOccupied Zone Temperature Control Gas Heating Two-StageCooling and Heating Controls Constant Volume CV Only Auto ChangeoverUnoccupied Zone Temperature Control Hot Water or Steam HeatingMorning Warm-up Options Controls VAV and CVSpace Pressure Control Statitrac Emergency OverrideControls VAV and CV Ventilation Override Module VOMHuman Interface Panel Main Menu Human Interface Panel HIGeneric Building Automation System Module Gbas 0-5 vdc Steam and Hot Water Coil Freeze Avoidance Generic Building Automation System Module Gbas 0-10 vdcChilled Water Coil Freeze Stat Night Setback SensorsTrane Tracer or BAS System Dry Bulb Temperature Control of EconomizerOccupied/Unoccupied input on the RTM Timed Override ActivationReturn Fan Control Humidification ControlLonTalk Building Automation System TwinningApplication Recommendations Applications ConsiderationsExhaust/Return Fan Options AdvantagesSupply and Return Airflow Configurations Applications ConsiderationsWith Bag Supply Airflow ConfigurationReturn Airflow Configuration CartridgeNatural Gas Heating Considerations Corrosive AtmospheresVentilation Override Sequences Acoustical ConsiderationsUnit Placement Clearance RequirementsExternal Piping Enclosure Duct DesignProtecting Hydronic Coils From Freezing Selection Procedure Selection Procedure Unit Electrical Requirements Exhaust Fan Motor SizingReturn Fan Motor Sizing Altitude CorrectionsModel Number Description Digit 7 Chilled Water Coil FIN SeriesModel Number Description Digit 20 System Control SelectionDigit 38 Belt Guards Burglar BARS/MARINE Lights General Data All dimensions in inches General DataGeneral Data Inputs MBH Input MBH Range MBH Gas Heat Inputs/Input RangesEconomizer Outdoor Air Damper Leakage at rated airflowi Standard Damper Optional Low Leak DamperEnthalpy of Saturated Air Performance Adjustment FactorsWet Bulb Temperature Btu per Pound Gas Heating Capacity Altitude Correction FactorsDB F WB F Performance Data-Chilled Water Coil CapacitiesChilled Water Coil Capacities-2 Row 5W Performance Data-Chilled Water Coil Capacities Chilled Water Coil Capacities-4 Row WChilled Water Coil Capacities-6 Row WD Chilled Water Coil Capacities-8 Row WD Supply Fan Performance Standard CFM Casing a Total Static Pressure Std Air1644 Supply Fan w/o IGV Supply Fan Performance Standard CFM -Casing B 9311117 Supply Fan Performance Standard CFM-Casing B Supply Fan Performance Standard CFM Casing C 7491019 Total Static Pressure Std AirPerformance Data Supply Fan with Inlet Guide Vanes Performance Data Supply Fan with Inlet Guide Vanes Supply Fan Performance Standard CFM-Casing a Supply Fan Performance Standard CFM Casing B 1093 1600 RPM 1500 RPM 779 1021 1283 Performance Data-Exhaust Fan Negative Static Pressure Std AirPerformance Data-Exhaust Fan Static PresureInWC237i Wocfm Exhaust Fan Performance Standard CFM-Case C 32 Fan 4150 R P M Performance Data-Return Fan Return Fan Performance Standard CFM-Case a 36.5 FanPerformance Data-Return Fan Return Fan PerformanceReturn Fan Performance Standard CFM-Case B and Case C 40 Fan Return Fan Performance Natural Gas Heating Capacities1 Electric Heat Air Temperature RisePerformance Data-Heat Electric Heat kw RangesSteam Coil Heating Capacities Q/ITD Performance Data-HeatHot Water Coil Heating Capacities Q/ITD Properties of SteamChilled Water Coil Airside Pressure Drop in H20 Component Static Pressure Drops in. H2OFilters Prefilter High Low PD Cartridge Bag FiltersCartridge Filters Throw Temp Hi Temp Away Prefilter Casing Supply Air Fan Drive Selections Drive NoReturn Air Fan Drive Selections Horse Power HP Low Casing StdExhaust Air Fan Drive Selections 15 HP 20 HP 25 HP 30 HP 40 HP Drive NoSet 1. Cooling with Gas Heat Air Handling Units Electrical Service SizingElectrical Data Set 2. Cooling with Electric HeatElectrical Service Sizing Data-Motors Unit Voltage Electrical DataVoltage Utilization Range Nominal Tons Voltage 460 575 FLA Add 90-150Dimensional Data Unit Top/Front ViewReturn Exhaust Unit Height Fan Casing Dimensional DataUnit Dimensions In.-One-Piece Unit Supply Opening Blank Casing Gas Heat Section Downflow/Horizontal Airflow Configuration DimensionsOpening Electrical Entry Details Piping Chilled Water Piping Locations Minimum Required Clearance Ft Control Minimum Required ClearanceUnit Option Selection Door Swing Ft. Standard Exh BoxCross Member Location Blank Casing Section Dimensions Blank Casing SectionBlank Casing Section Field Installed Sensors Variable Air Volume VAV Field Installed Sensors Constant Volume CV Field Installed Sensors VAV and CV Wireless Zone Sensor Wall or Duct Mount CO2 Zone Sensors Component Weights Lbs WeightsApproximate Operating Weights Lbs Weights Size Wt lbs Control Box Main 454 Convenience Outlet Roof Curb WeightsInstalled Shipping Casing Blank Weight Options Options FiltersFresh Air System ControlAgency Approval Miscellaneous OptionsField Installed Accessories Electronic Zone SensorsRoof Curb Electrical System Mechanical SpecificationsGeneral External Piping Enclosure Mechanical Specifications Cooling System Chilled Water CoilWater Valve Air Handling SystemMechanical Specifications Filters No Relief Standard Mechanical SpecificationsExhaust Air Percent Modulating Exhaust Fan OptionMechanical Specifications Return Air Fresh AirHeating System CO2 Sensing Page RT-PRC031-EN