Performance Data—Chilled Water Coil Capacities

Table 10 Chilled Water Coil Capacities—4 Row W

 

 

 

 

 

 

 

Entering Dry Bulb/Wet Bulb 80/67 F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entering Water 45 F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water Temperature Rise F 10 F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Without Turbulators

 

 

 

 

 

With Turbulators

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air

 

Total

Sensible

 

 

 

Water

Water

Total

 

Sensible

 

 

Water

Water

Flow

 

capacity

capacity

Leaving

Leaving

 

Flow

PD

Capacity

 

Capacity

Leaving

Leaving

Flow

PD

CFM

FPF

(MBH)

(MBH)

DB (F)

WB (F)

 

GPM

(ft H2O)

(MBH)

 

(MBH)

DB (F)

WB (F)

GPM

(ft H2O)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16000

80

523

378

58.6

56.6

 

104.3

2.5

577

 

400

57.3

55.4

115.1

7.4

 

108

634

443

54.9

54.1

 

126.4

3.5

689

 

466

53.6

52.9

137.3

10.0

 

144

746

500

51.6

51.5

 

148.7

4.7

802

 

525

50.3

50.1

159.8

13.0

 

168

785

518

50.6

50.5

 

156.4

5.2

840

 

542

49.3

49.2

167.4

14.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20000

80

615

452

59.5

57.3

 

122.6

3.3

674

 

476

58.4

56.3

134.3

9.6

 

108

746

531

55.9

55.0

 

148.7

4.7

810

 

558

54.7

53.8

161.5

13.2

 

144

885

604

52.6

52.4

 

176.3

6.4

952

 

632

51.3

51.1

189.7

17.5

 

168

937

628

51.5

51.4

 

186.8

7.1

1005

 

658

50.2

50.1

200.2

19.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

23000

80

677

504

60.1

57.8

 

134.9

4.0

740

 

530

59.1

56.8

147.5

11.3

 

108

823

593

56.6

55.5

 

164.1

5.6

894

 

622

55.5

54.4

178.1

15.7

 

144

981

678

53.3

53.0

 

195.5

7.7

1055

 

709

52.0

51.8

210.3

21.1

 

168

1044

707

52.1

52.0

 

208.0

8.7

1119

 

740

50.8

50.7

223.1

23.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28000

80

771

586

61.0

58.4

 

153.6

5.0

841

 

614

60.1

57.6

167.6

14.1

 

108

941

692

57.6

56.3

 

187.6

7.2

1021

 

724

56.5

55.3

203.4

19.9

 

144

1128

795

54.3

53.9

 

224.8

10.0

1214

 

830

53.1

52.8

241.9

27.0

 

168

1208

833

53.0

52.8

 

240.9

11.3

1296

 

870

51.8

51.6

258.3

30.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33000

80

856

664

61.8

59.0

 

170.6

6.0

932

 

694

60.9

58.2

185.8

16.9

 

108

1048

785

58.4

57.0

 

208.9

8.7

1136

 

820

57.5

56.0

226.4

24.0

 

144

1262

906

55.1

54.6

 

251.6

12.3

1357

 

945

54.0

53.6

270.5

33.1

 

168

1360

953

53.8

53.6

 

271.0

14.1

1457

 

994

52.7

52.4

290.4

37.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38000

80

934

737

62.4

59.4

 

186.1

7.1

1016

 

769

61.7

58.7

202.5

19.7

 

108

1147

873

59.2

57.5

 

228.5

10.3

1241

 

911

58.3

56.7

247.3

28.2

 

144

1386

1011

55.9

55.3

 

276.2

14.6

1488

 

1053

54.9

54.3

296.6

39.0

 

168

-

-

-

-

 

-

-

-

 

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

43000

80

1006

806

63.0

59.8

 

200.6

8.1

1093

 

840

62.3

59.1

217.9

22.4

 

108

1238

958

59.8

58.0

 

246.7

11.8

1338

 

997

59.0

57.2

266.7

32.2

 

144

-

-

-

-

 

-

-

-

 

-

-

-

-

-

 

168

-

-

-

-

 

-

-

-

 

-

-

-

-

-

45000

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1034

833

63.2

60.0

 

206.0

8.5

1123

 

867

62.5

59.3

223.7

23.5

 

108

1272

990

60.0

58.2

 

253.6

12.5

1375

 

1030

59.2

57.4

274.0

33.8

 

144

-

-

-

-

 

-

-

-

 

-

-

-

-

-

 

168

-

-

-

-

 

-

-

-

 

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RT-PRC031-EN

39

Image 39
Contents IntelliPak II Air Handlers Introduction Table of Contents Features and Benefits Standard FeaturesControls Cabinet Mechanical Features and Benefits Optional Features Reliability Features and Benefits Field Installed AccessoriesFeatures Summary Installation and ServiceFeatures and Benefits Application Flexibility Integrated Comfort with Trane Tracer LCISimplifying the Comfort System Features and Benefits InteroperabilityOptimum Building Comfort Control Statitrac Statitrac Direct Space Building Pressurization ControlVariable Frequency Drives VFD Supply Fans with Inlet Guide VanesSupply Air Temperature Controls Supply Air Pressure Control Controls Variable Air Volume VAV OnlyControls Variable Air Volume VAV Only Supply Air Setpoint ResetHeating Zone Temperature Control Gas Heating Two-Stage Controls Constant Volume CV OnlyOccupied Zone Temperature Control HeatingHot Water or Steam Heating Controls Constant Volume CV Only Auto ChangeoverUnoccupied Zone Temperature Control Cooling and HeatingEmergency Override Controls VAV and CVSpace Pressure Control Statitrac Morning Warm-up OptionsVentilation Override Module VOM Controls VAV and CVHuman Interface Panel HI Generic Building Automation System Module Gbas 0-5 vdcHuman Interface Panel Main Menu Night Setback Sensors Generic Building Automation System Module Gbas 0-10 vdcChilled Water Coil Freeze Stat Steam and Hot Water Coil Freeze AvoidanceTimed Override Activation Dry Bulb Temperature Control of EconomizerOccupied/Unoccupied input on the RTM Trane Tracer or BAS SystemTwinning Humidification ControlLonTalk Building Automation System Return Fan ControlAdvantages Applications ConsiderationsExhaust/Return Fan Options Application RecommendationsApplications Considerations Supply and Return Airflow ConfigurationsCartridge Supply Airflow ConfigurationReturn Airflow Configuration With BagAcoustical Considerations Corrosive AtmospheresVentilation Override Sequences Natural Gas Heating ConsiderationsClearance Requirements Unit PlacementDuct Design Protecting Hydronic Coils From FreezingExternal Piping Enclosure Selection Procedure Selection Procedure Altitude Corrections Exhaust Fan Motor SizingReturn Fan Motor Sizing Unit Electrical RequirementsDigit 7 Chilled Water Coil FIN Series Model Number DescriptionDigit 20 System Control Selection Model Number DescriptionDigit 38 Belt Guards Burglar BARS/MARINE Lights General Data General Data All dimensions in inchesGeneral Data Standard Damper Optional Low Leak Damper Gas Heat Inputs/Input RangesEconomizer Outdoor Air Damper Leakage at rated airflowi Inputs MBH Input MBH Range MBHGas Heating Capacity Altitude Correction Factors Performance Adjustment FactorsWet Bulb Temperature Btu per Pound Enthalpy of Saturated AirPerformance Data-Chilled Water Coil Capacities Chilled Water Coil Capacities-2 Row 5WDB F WB F Chilled Water Coil Capacities-4 Row W Performance Data-Chilled Water Coil CapacitiesChilled Water Coil Capacities-6 Row WD Chilled Water Coil Capacities-8 Row WD Total Static Pressure Std Air Supply Fan Performance Standard CFM Casing a1644 Supply Fan w/o IGV 931 Supply Fan Performance Standard CFM -Casing B1117 Supply Fan Performance Standard CFM-Casing B 749 Supply Fan Performance Standard CFM Casing C1019 Std Air Total Static PressurePerformance Data Supply Fan with Inlet Guide Vanes Performance Data Supply Fan with Inlet Guide Vanes Supply Fan Performance Standard CFM-Casing a Supply Fan Performance Standard CFM Casing B 1093 1600 RPM 1500 RPM 779 1021 1283 Negative Static Pressure Std Air Performance Data-Exhaust FanStatic PresureInWC Performance Data-Exhaust Fan237i Wocfm 415 Exhaust Fan Performance Standard CFM-Case C 32 Fan0 R P M Return Fan Performance Standard CFM-Case a 36.5 Fan Performance Data-Return FanReturn Fan Performance Performance Data-Return FanReturn Fan Performance Standard CFM-Case B and Case C 40 Fan Return Fan Performance Electric Heat kw Ranges Electric Heat Air Temperature RisePerformance Data-Heat Natural Gas Heating Capacities1Properties of Steam Performance Data-HeatHot Water Coil Heating Capacities Q/ITD Steam Coil Heating Capacities Q/ITDComponent Static Pressure Drops in. H2O Chilled Water Coil Airside Pressure Drop in H20High Low PD Cartridge Bag Filters Cartridge Filters Throw Temp Hi Temp Away Prefilter CasingFilters Prefilter Drive No Supply Air Fan Drive Selections15 HP 20 HP 25 HP 30 HP 40 HP Drive No Horse Power HP Low Casing StdExhaust Air Fan Drive Selections Return Air Fan Drive SelectionsSet 2. Cooling with Electric Heat Electrical Service SizingElectrical Data Set 1. Cooling with Gas Heat Air Handling UnitsElectrical Service Sizing Data-Motors Nominal Tons Voltage 460 575 FLA Add 90-150 Electrical DataVoltage Utilization Range Unit VoltageUnit Top/Front View Dimensional DataDimensional Data Unit Dimensions In.-One-Piece UnitReturn Exhaust Unit Height Fan Casing Downflow/Horizontal Airflow Configuration Dimensions OpeningSupply Opening Blank Casing Gas Heat Section Electrical Entry Details Piping Chilled Water Piping Locations Exh Box Minimum Required ClearanceUnit Option Selection Door Swing Ft. Standard Minimum Required Clearance Ft ControlDimensions Blank Casing Section Blank Casing SectionCross Member Location Blank Casing Section Field Installed Sensors Variable Air Volume VAV Field Installed Sensors Constant Volume CV Field Installed Sensors VAV and CV Wireless Zone Sensor Wall or Duct Mount CO2 Zone Sensors Weights Approximate Operating Weights LbsComponent Weights Lbs Weights Roof Curb Weights Installed Shipping Casing Blank WeightSize Wt lbs Control Box Main 454 Convenience Outlet Options Filters OptionsSystem Control Fresh AirMiscellaneous Options Agency ApprovalElectronic Zone Sensors Field Installed AccessoriesRoof Curb Mechanical Specifications GeneralElectrical System Air Handling System Mechanical Specifications Cooling System Chilled Water CoilWater Valve External Piping EnclosureMechanical Specifications Filters Percent Modulating Exhaust Fan Option Mechanical SpecificationsExhaust Air No Relief StandardFresh Air Mechanical Specifications Return AirHeating System CO2 Sensing Page RT-PRC031-EN