Trane RT-PRC031-EN manual Performance Data Supply Fan with Inlet Guide Vanes

Page 51

Performance Data — Supply Fan with Inlet Guide Vanes

Table 18 Supply Fan Performance STANDARD CFM — Casing A (25")

CFM

 

 

 

 

 

 

 

 

Total Static Pressure

 

 

 

 

 

 

 

 

Std.

0.25

0.50

0.75

1.00

1.25

1.50

1.75

2.00

Air

RPM

BHP

 

RPM

BHP

 

RPM

BHP

RPM

BHP

 

RPM

BHP

RPM

BHP

RPM

BHP

 

RPM

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16000

1064(i)

7.01

1095

7.69

1125

8.35

1154

9.02

1183

9.69

1211

10.38

1240

11.10

1267

11.80

17000

1127

8.31

1157

9.04

1185

9.75

1213

10.46

1239

11.16

1266

11.88

1293

12.62

1320

13.38

18000

1190

9.77

1218

10.54

1245

11.30

1271

12.05

1297

12.79

1323

13.55

1348

14.33

 

 

 

 

1373

15.11

19000

1252

11.40

1280

12.22

1306

13.02

1331

13.81

 

 

 

 

 

 

 

 

1428

17.02

 

1355

14.60

1379

15.38

1403

16.18

 

20000

1316

13.20

1341

14.07

 

 

 

 

 

 

1414

16.58

1437

17.40

1460

18.23

1483

19.08

 

1366

14.92

1391

15.76

 

21000

1379

15.19

 

 

 

 

1427

16.99

1451

17.87

1473

18.75

1496

19.62

1518

20.49

1539

21.36

 

1404

16.10

 

22000

 

 

 

1466

18.32

1489

19.27

1511

20.20

1533

21.11

1554

22.01

1575

22.92

1596

23.83

1442

17.37

 

23000

1505

19.76

1528

20.76

1550

21.74

1572

22.71

1593

23.67

1614

24.63

1634

25.58

1654

26.53

24000

1569

22.35

1591

23.40

1612

24.43

1633

25.45

1653

26.46

1673

27.45

1693

28.44

1712

29.42

25000

1633

25.17

1654

26.27

1674

27.34

1694

28.41

1714

29.45

1733

30.50

1752

31.53

1771

32.56

26000

1696

28.22

1717

29.36

1736

30.48

1756

31.60

1775

32.70

1794

33.78

1812

34.87

1830

35.93

27000

1760

31.52

1780

32.70

1799

33.86

1817

35.01

1836

36.17

1854

37.31

1872

38.42

1890

39.56

28000

1824

35.05

1843

36.28

1861

37.50

1879

38.70

1897

39.89

1915

41.07

1932

42.23

1949

43.41

29000

1887

38.85

1906

40.12

1924

41.39

1941

42.63

1959

43.86

1976

45.10

1993

46.31

2009

47.53

30000

1951

42.92

1969

44.24

1986

45.54

2004

46.82

 

 

 

 

 

 

 

 

 

 

31000

2015

47.26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

Total Static Pressure

 

 

 

 

 

 

 

 

Std.

2.25

2.50

2.75

3.00

3.25

3.50

3.75

4.00

Air

RPM

BHP

 

RPM

BHP

 

RPM

BHP

RPM

BHP

 

RPM

BHP

RPM

BHP

RPM

BHP

 

RPM

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16000

1294(ii)

12.49

1320

13.19

 

1345

13.89

1368

14.53

1390

15.19

1412

15.86

1434

16.53

1456

17.21

17000

1346

14.13

 

 

 

 

1395

15.61

1419

16.34

1441

17.04

1462

17.74

1484

18.45

1505

19.16

 

1371

14.89

 

18000

 

 

 

1422

16.69

1447

17.49

1470

18.28

1493

19.07

1514

19.81

1534

20.55

1555

21.29

1398

15.90

 

19000

1452

17.86

1475

18.67

1499

19.53

1521

20.37

1544

21.21

1565

22.01

1586

22.82

1606

23.62

20000

1506

19.95

1528

20.83

1551

21.71

1573

22.59

1595

23.48

1616

24.36

1637

25.24

1658

26.12

21000

1561

22.27

1583

23.17

1605

24.11

1626

25.05

1647

25.94

1667

26.86

1689

27.82

1709

28.73

22000

1617

24.77

1637

25.69

1659

26.69

1679

27.63

1700

28.61

1720

29.58

1741

30.58

1760

31.51

23000

1674

27.50

1694

28.46

1714

29.46

1733

30.44

1753

31.46

1773

32.47

1793

33.51

1812

34.54

24000

1732

30.44

1751

31.45

1769

32.44

1788

33.47

1808

34.53

1827

35.57

1846

36.65

1864

37.70

25000

1790

33.61

1808

34.63

1826

35.69

1844

36.73

1863

37.83

1881

38.90

1899

40.01

1917

41.08

26000

1848

37.02

1866

38.08

1883

39.15

1901

40.25

1919

41.38

1936

42.48

1954

43.61

1972

44.78

27000

1907

40.66

1924

41.76

1941

42.89

1958

44.02

1975

45.15

1992

46.27

 

 

 

 

 

28000

1966

44.55

1983

45.71

1999

46.87

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

Total Static Pressure

 

 

 

 

 

 

 

 

Std.

4.25

4.50

4.75

5.00

5.25

5.50

5.75

6.00

Air

RPM

BHP

 

RPM

BHP

 

RPM

BHP

RPM

BHP

 

RPM

BHP

RPM

BHP

RPM

BHP

 

RPM

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16000

1479

17.93

1502

18.68

1523

19.40

1546

20.15

1569

20.94

1592

21.77

1614

22.55

1636

23.33

17000

1526

19.90

1547

20.65

1568

21.39

1589

22.16

1609

22.92

1630

23.72

1652

24.54

1674

25.41

18000

1574

22.02

1594

22.78

1614

23.54

1634

24.33

1654

25.15

1673

25.91

1693

26.75

1714

27.62

19000

1625

24.38

1644

25.17

1663

25.94

1682

26.75

1701

27.58

1720

28.40

1739

29.25

1757

30.08

20000

1677

26.94

1696

27.80

1714

28.59

1732

29.41

1750

30.26

1767

31.03

1786

31.94

1803

32.77

21000

1728

29.62

1747

30.55

1765

31.40

1783

32.29

1801

33.15

1817

33.98

1835

34.90

1851

35.72

22000

1779

32.48

1799

33.48

1817

34.41

1835

35.36

1852

36.23

1868

37.13

1885

38.05

1903

39.00

23000

1831

35.53

1850

36.56

1868

37.55

1885

38.52

1904

39.58

1921

40.55

1937

41.47

1953

42.42

24000

1883

38.78

1901

39.83

1919

40.91

1937

41.95

1955

43.03

1972

44.06

1988

45.05

2005

46.07

25000

1935

42.19

1953

43.33

1971

44.43

1989

45.55

2006

46.63

 

 

 

 

 

 

 

26000

1989

45.91

2006

47.06

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RT-PRC031-EN

51

Image 51
Contents IntelliPak II Air Handlers Introduction Table of Contents Features and Benefits Standard FeaturesControls Cabinet Mechanical Features and Benefits Optional Features Reliability Features and Benefits Field Installed AccessoriesFeatures Summary Installation and ServiceFeatures and Benefits Application Flexibility Integrated Comfort with Trane Tracer LCISimplifying the Comfort System Features and Benefits InteroperabilityOptimum Building Comfort Control Statitrac Statitrac Direct Space Building Pressurization ControlVariable Frequency Drives VFD Supply Fans with Inlet Guide VanesSupply Air Temperature Controls Supply Air Pressure Control Controls Variable Air Volume VAV OnlyControls Variable Air Volume VAV Only Supply Air Setpoint ResetHeating Zone Temperature Control Gas Heating Two-Stage Controls Constant Volume CV OnlyOccupied Zone Temperature Control HeatingHot Water or Steam Heating Controls Constant Volume CV Only Auto ChangeoverUnoccupied Zone Temperature Control Cooling and HeatingEmergency Override Controls VAV and CVSpace Pressure Control Statitrac Morning Warm-up OptionsVentilation Override Module VOM Controls VAV and CVHuman Interface Panel HI Generic Building Automation System Module Gbas 0-5 vdcHuman Interface Panel Main Menu Night Setback Sensors Generic Building Automation System Module Gbas 0-10 vdcChilled Water Coil Freeze Stat Steam and Hot Water Coil Freeze AvoidanceTimed Override Activation Dry Bulb Temperature Control of EconomizerOccupied/Unoccupied input on the RTM Trane Tracer or BAS SystemTwinning Humidification ControlLonTalk Building Automation System Return Fan ControlAdvantages Applications ConsiderationsExhaust/Return Fan Options Application RecommendationsApplications Considerations Supply and Return Airflow ConfigurationsCartridge Supply Airflow ConfigurationReturn Airflow Configuration With BagAcoustical Considerations Corrosive AtmospheresVentilation Override Sequences Natural Gas Heating ConsiderationsClearance Requirements Unit PlacementDuct Design Protecting Hydronic Coils From FreezingExternal Piping Enclosure Selection Procedure Selection Procedure Altitude Corrections Exhaust Fan Motor SizingReturn Fan Motor Sizing Unit Electrical RequirementsDigit 7 Chilled Water Coil FIN Series Model Number DescriptionDigit 20 System Control Selection Model Number DescriptionDigit 38 Belt Guards Burglar BARS/MARINE Lights General Data General Data All dimensions in inchesGeneral Data Standard Damper Optional Low Leak Damper Gas Heat Inputs/Input RangesEconomizer Outdoor Air Damper Leakage at rated airflowi Inputs MBH Input MBH Range MBHGas Heating Capacity Altitude Correction Factors Performance Adjustment FactorsWet Bulb Temperature Btu per Pound Enthalpy of Saturated AirPerformance Data-Chilled Water Coil Capacities Chilled Water Coil Capacities-2 Row 5WDB F WB F Chilled Water Coil Capacities-4 Row W Performance Data-Chilled Water Coil CapacitiesChilled Water Coil Capacities-6 Row WD Chilled Water Coil Capacities-8 Row WD Total Static Pressure Std Air Supply Fan Performance Standard CFM Casing a1644 Supply Fan w/o IGV 931 Supply Fan Performance Standard CFM -Casing B1117 Supply Fan Performance Standard CFM-Casing B 749 Supply Fan Performance Standard CFM Casing C1019 Std Air Total Static PressurePerformance Data Supply Fan with Inlet Guide Vanes Performance Data Supply Fan with Inlet Guide Vanes Supply Fan Performance Standard CFM-Casing a Supply Fan Performance Standard CFM Casing B 1093 1600 RPM 1500 RPM 779 1021 1283 Negative Static Pressure Std Air Performance Data-Exhaust FanStatic PresureInWC Performance Data-Exhaust Fan237i Wocfm 415 Exhaust Fan Performance Standard CFM-Case C 32 Fan0 R P M Return Fan Performance Standard CFM-Case a 36.5 Fan Performance Data-Return FanReturn Fan Performance Performance Data-Return FanReturn Fan Performance Standard CFM-Case B and Case C 40 Fan Return Fan Performance Electric Heat kw Ranges Electric Heat Air Temperature RisePerformance Data-Heat Natural Gas Heating Capacities1Properties of Steam Performance Data-HeatHot Water Coil Heating Capacities Q/ITD Steam Coil Heating Capacities Q/ITDComponent Static Pressure Drops in. H2O Chilled Water Coil Airside Pressure Drop in H20High Low PD Cartridge Bag Filters Cartridge Filters Throw Temp Hi Temp Away Prefilter CasingFilters Prefilter Drive No Supply Air Fan Drive Selections15 HP 20 HP 25 HP 30 HP 40 HP Drive No Horse Power HP Low Casing StdExhaust Air Fan Drive Selections Return Air Fan Drive SelectionsSet 2. Cooling with Electric Heat Electrical Service SizingElectrical Data Set 1. Cooling with Gas Heat Air Handling UnitsElectrical Service Sizing Data-Motors Nominal Tons Voltage 460 575 FLA Add 90-150 Electrical DataVoltage Utilization Range Unit VoltageUnit Top/Front View Dimensional DataDimensional Data Unit Dimensions In.-One-Piece UnitReturn Exhaust Unit Height Fan Casing Downflow/Horizontal Airflow Configuration Dimensions OpeningSupply Opening Blank Casing Gas Heat Section Electrical Entry Details Piping Chilled Water Piping Locations Exh Box Minimum Required ClearanceUnit Option Selection Door Swing Ft. Standard Minimum Required Clearance Ft ControlDimensions Blank Casing Section Blank Casing SectionCross Member Location Blank Casing Section Field Installed Sensors Variable Air Volume VAV Field Installed Sensors Constant Volume CV Field Installed Sensors VAV and CV Wireless Zone Sensor Wall or Duct Mount CO2 Zone Sensors Weights Approximate Operating Weights LbsComponent Weights Lbs Weights Roof Curb Weights Installed Shipping Casing Blank WeightSize Wt lbs Control Box Main 454 Convenience Outlet Options Filters OptionsSystem Control Fresh AirMiscellaneous Options Agency ApprovalElectronic Zone Sensors Field Installed AccessoriesRoof Curb Mechanical Specifications GeneralElectrical System Air Handling System Mechanical Specifications Cooling System Chilled Water CoilWater Valve External Piping EnclosureMechanical Specifications Filters Percent Modulating Exhaust Fan Option Mechanical SpecificationsExhaust Air No Relief StandardFresh Air Mechanical Specifications Return AirHeating System CO2 Sensing Page RT-PRC031-EN