Trane RT-PRC031-EN manual Chilled Water Coil Capacities-8 Row WD

Page 41

Performance Data—Chilled Water Coil Capacities

Table 12 Chilled Water Coil Capacities—8 Row WD

 

 

 

 

 

 

 

Entering Dry Bulb/Wet Bulb 80/67 F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entering Water 45 F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water Temperature Rise F 10 F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Without Turbulators

 

 

 

 

 

With Turbulators

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air

 

Total

Sensible

 

 

 

Water

Water

Total

 

Sensible

 

 

Water

Water

Flow

 

capacity

capacity

Leaving

Leaving

 

Flow

PD

Capacity

 

Capacity

Leaving

Leaving

Flow

PD

CFM

FPF

(MBH)

(MBH)

DB (F)

WB (F)

 

GPM

(ft H2O)

(MBH)

 

(MBH)

DB (F)

WB (F)

GPM

(ft H2O)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16000

80

712

483

52.6

52.3

 

141.9

2.0

795

 

519

50.6

50.3

158.5

4.9

 

108

803

526

50.2

50.1

 

160.1

2.5

876

 

559

48.3

48.2

174.5

5.8

 

144

877

559

48.3

48.2

 

174.9

3.0

936

 

587

46.7

46.6

186.6

6.5

 

168

899

569

47.7

47.6

 

179.1

3.1

953

 

594

46.3

46.2

189.9

6.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20000

80

866

592

53.1

52.8

 

172.6

2.9

954

 

630

51.4

51.1

190.1

6.7

 

108

981

647

50.6

50.5

 

195.5

3.7

1060

 

683

49.0

48.9

211.4

8.1

 

144

1077

690

48.7

48.6

 

214.6

4.4

1145

 

721

47.3

47.2

228.2

9.2

 

168

1107

704

48.1

48.0

 

220.7

4.6

1171

 

733

46.7

46.6

233.3

9.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

23000

80

973

671

53.6

53.1

 

194.0

3.6

1065

 

710

52.0

51.6

212.3

8.2

 

108

1106

735

51.0

50.9

 

220.4

4.6

1192

 

773

49.5

49.4

237.5

9.9

 

144

1219

785

49.1

49.0

 

242.9

5.5

1295

 

820

47.7

47.6

258.2

11.5

 

168

1257

802

48.4

48.3

 

250.5

5.9

1329

 

835

47.1

47.0

264.8

12.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28000

80

1139

795

54.3

53.8

 

227.1

4.9

1239

 

837

52.9

52.4

247.0

10.7

 

108

1300

874

51.7

51.6

 

259.1

6.3

1399

 

917

50.3

50.2

278.8

13.2

 

144

1442

936

49.7

49.6

 

287.3

7.6

1534

 

978

48.3

48.2

305.8

15.6

 

168

1493

960

48.9

48.8

 

297.6

8.1

1582

 

1000

47.6

47.5

315.3

16.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33000

80

1291

912

54.9

54.3

 

257.4

6.2

1401

 

958

53.7

53.1

279.3

13.3

 

108

1479

1006

52.3

52.2

 

294.9

8.0

1593

 

1055

51.0

50.9

317.4

16.7

 

144

1651

1082

50.3

50.2

 

329.0

9.8

1760

 

1131

48.9

48.8

350.7

20.0

 

168

1717

1112

49.4

49.3

 

342.3

10.6

1823

 

1160

48.1

48.0

363.3

21.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38000

80

1432

1025

55.5

54.9

 

285.4

7.5

1552

 

1074

54.4

53.7

309.4

15.9

 

108

1648

1133

53.0

52.7

 

328.4

9.8

1774

 

1187

51.7

51.5

353.7

20.3

 

144

1849

1223

50.8

50.7

 

368.4

12.2

1973

 

1278

49.5

49.4

393.3

24.6

 

168

-

-

-

-

 

-

-

-

 

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

43000

80

1563

1132

56.1

55.3

 

311.5

8.9

1694

 

1186

55.0

54.2

337.6

18.7

 

108

1806

1256

53.5

53.3

 

360.0

11.7

1946

 

1315

52.3

52.0

387.8

24.0

 

144

-

-

-

-

 

-

-

-

 

-

-

-

-

-

 

168

-

-

-

-

 

-

-

-

 

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45000

80

1613

1174

56.3

55.5

 

321.5

9.4

1748

 

1230

55.2

54.4

348.5

19.8

 

108

1868

1304

53.7

53.4

 

372.2

12.4

2012

 

1365

52.5

52.2

401.0

25.5

 

144

-

-

-

-

 

-

-

-

 

-

-

-

-

-

 

168

-

-

-

-

 

-

-

-

 

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RT-PRC031-EN

41

Image 41
Contents IntelliPak II Air Handlers Introduction Table of Contents Controls Cabinet Mechanical Features and BenefitsStandard Features Features and Benefits Optional Features Features Summary Features and Benefits Field Installed AccessoriesInstallation and Service ReliabilitySimplifying the Comfort System Features and Benefits Application FlexibilityIntegrated Comfort with Trane Tracer LCI Optimum Building Comfort Control Features and BenefitsInteroperability Statitrac Statitrac Direct Space Building Pressurization ControlVariable Frequency Drives VFD Supply Fans with Inlet Guide VanesSupply Air Temperature Controls Supply Air Pressure Control Controls Variable Air Volume VAV OnlyHeating Controls Variable Air Volume VAV OnlySupply Air Setpoint Reset Zone Temperature Control Occupied Zone Temperature Control Controls Constant Volume CV OnlyHeating Gas Heating Two-StageUnoccupied Zone Temperature Control Controls Constant Volume CV Only Auto ChangeoverCooling and Heating Hot Water or Steam HeatingSpace Pressure Control Statitrac Controls VAV and CVMorning Warm-up Options Emergency OverrideVentilation Override Module VOM Controls VAV and CVHuman Interface Panel Main Menu Human Interface Panel HIGeneric Building Automation System Module Gbas 0-5 vdc Chilled Water Coil Freeze Stat Generic Building Automation System Module Gbas 0-10 vdcSteam and Hot Water Coil Freeze Avoidance Night Setback SensorsOccupied/Unoccupied input on the RTM Dry Bulb Temperature Control of EconomizerTrane Tracer or BAS System Timed Override ActivationLonTalk Building Automation System Humidification ControlReturn Fan Control TwinningExhaust/Return Fan Options Applications ConsiderationsApplication Recommendations AdvantagesApplications Considerations Supply and Return Airflow ConfigurationsReturn Airflow Configuration Supply Airflow ConfigurationWith Bag CartridgeVentilation Override Sequences Corrosive AtmospheresNatural Gas Heating Considerations Acoustical ConsiderationsClearance Requirements Unit PlacementExternal Piping Enclosure Duct DesignProtecting Hydronic Coils From Freezing Selection Procedure Selection Procedure Return Fan Motor Sizing Exhaust Fan Motor SizingUnit Electrical Requirements Altitude CorrectionsDigit 7 Chilled Water Coil FIN Series Model Number DescriptionDigit 20 System Control Selection Model Number DescriptionDigit 38 Belt Guards Burglar BARS/MARINE Lights General Data General Data All dimensions in inchesGeneral Data Economizer Outdoor Air Damper Leakage at rated airflowi Gas Heat Inputs/Input RangesInputs MBH Input MBH Range MBH Standard Damper Optional Low Leak DamperWet Bulb Temperature Btu per Pound Performance Adjustment FactorsEnthalpy of Saturated Air Gas Heating Capacity Altitude Correction FactorsDB F WB F Performance Data-Chilled Water Coil CapacitiesChilled Water Coil Capacities-2 Row 5W Chilled Water Coil Capacities-4 Row W Performance Data-Chilled Water Coil CapacitiesChilled Water Coil Capacities-6 Row WD Chilled Water Coil Capacities-8 Row WD Total Static Pressure Std Air Supply Fan Performance Standard CFM Casing a1644 Supply Fan w/o IGV 931 Supply Fan Performance Standard CFM -Casing B1117 Supply Fan Performance Standard CFM-Casing B 749 Supply Fan Performance Standard CFM Casing C1019 Std Air Total Static PressurePerformance Data Supply Fan with Inlet Guide Vanes Performance Data Supply Fan with Inlet Guide Vanes Supply Fan Performance Standard CFM-Casing a Supply Fan Performance Standard CFM Casing B 1093 1600 RPM 1500 RPM 779 1021 1283 Negative Static Pressure Std Air Performance Data-Exhaust FanStatic PresureInWC Performance Data-Exhaust Fan237i Wocfm 415 Exhaust Fan Performance Standard CFM-Case C 32 Fan0 R P M Return Fan Performance Standard CFM-Case a 36.5 Fan Performance Data-Return FanReturn Fan Performance Performance Data-Return FanReturn Fan Performance Standard CFM-Case B and Case C 40 Fan Return Fan Performance Performance Data-Heat Electric Heat Air Temperature RiseNatural Gas Heating Capacities1 Electric Heat kw RangesHot Water Coil Heating Capacities Q/ITD Performance Data-HeatSteam Coil Heating Capacities Q/ITD Properties of SteamComponent Static Pressure Drops in. H2O Chilled Water Coil Airside Pressure Drop in H20Filters Prefilter High Low PD Cartridge Bag FiltersCartridge Filters Throw Temp Hi Temp Away Prefilter Casing Drive No Supply Air Fan Drive SelectionsExhaust Air Fan Drive Selections Horse Power HP Low Casing StdReturn Air Fan Drive Selections 15 HP 20 HP 25 HP 30 HP 40 HP Drive NoElectrical Data Electrical Service SizingSet 1. Cooling with Gas Heat Air Handling Units Set 2. Cooling with Electric HeatElectrical Service Sizing Data-Motors Voltage Utilization Range Electrical DataUnit Voltage Nominal Tons Voltage 460 575 FLA Add 90-150Unit Top/Front View Dimensional DataReturn Exhaust Unit Height Fan Casing Dimensional DataUnit Dimensions In.-One-Piece Unit Supply Opening Blank Casing Gas Heat Section Downflow/Horizontal Airflow Configuration DimensionsOpening Electrical Entry Details Piping Chilled Water Piping Locations Unit Option Selection Door Swing Ft. Standard Minimum Required ClearanceMinimum Required Clearance Ft Control Exh BoxCross Member Location Blank Casing Section Dimensions Blank Casing SectionBlank Casing Section Field Installed Sensors Variable Air Volume VAV Field Installed Sensors Constant Volume CV Field Installed Sensors VAV and CV Wireless Zone Sensor Wall or Duct Mount CO2 Zone Sensors Component Weights Lbs WeightsApproximate Operating Weights Lbs Weights Size Wt lbs Control Box Main 454 Convenience Outlet Roof Curb WeightsInstalled Shipping Casing Blank Weight Options Filters OptionsSystem Control Fresh AirMiscellaneous Options Agency ApprovalElectronic Zone Sensors Field Installed AccessoriesRoof Curb Electrical System Mechanical SpecificationsGeneral Water Valve Mechanical Specifications Cooling System Chilled Water CoilExternal Piping Enclosure Air Handling SystemMechanical Specifications Filters Exhaust Air Mechanical SpecificationsNo Relief Standard Percent Modulating Exhaust Fan OptionFresh Air Mechanical Specifications Return AirHeating System CO2 Sensing Page RT-PRC031-EN