Sterling Plumbing 882.00254.00 Blow Back Options Only available on 7/50D Plus systems

Page 76

Name

Description

Options

Default

Partial convey

When this option is enabled, the controller

disabled,

disabled

 

issues a “partial convey” alarm if it has

enabled

 

 

repeatedly attempted to convey material to the

 

 

 

station, and material has moved from the station

 

 

 

into the receiver, but the volume-fill proximity

 

 

 

sensor has never signaled that the station is full.

 

 

 

(The number of attempts is controlled by the

 

 

 

next setting.)

 

 

 

For a volume-fill station, this option should

 

 

 

usually be enabled. At times, you may wish to

 

 

 

disable it during operation as a stopgap

 

 

 

measure for dealing with an alarm. For a time-fill

 

 

 

station, disable this option.

 

 

Alarm Options

 

 

 

# attempts B4 alarm

Number of attempts before alarm: the number of

1–99

3

 

times the controller will attempt to convey

 

 

 

material to a station before it issues a “partial

 

 

 

convey” alarm.

 

 

 

The setting for this option depends on the same

 

 

 

considerations as those given above for number

 

 

 

of attempts before a “no convey” alarm.

 

 

Local alarm

When this option is enabled, the controller turns

disabled,

disabled

 

on the local alarm light for any alarm at this

enabled

 

 

specific station.

 

 

 

Enable this option if and only if your facility has

 

 

 

installed a local alarm light for this station.

 

 

Miscellaneous Options

 

 

 

Receiver low level

When this option is enabled, the controller

disabled,

disabled

 

issues a “receiver level” alarm if material in the

enabled

 

 

receiver drains below the level of the receiver’s

 

 

 

low-level sensor.

 

 

 

Enable this option if and only if your facility has

 

 

 

installed a low-level sensor for this station’s

 

 

 

receiver. At times, you may wish to disable it

 

 

 

during operation as a stopgap measure for

 

 

 

dealing with an alarm.

 

 

Blow Back Options (Only available on 7/50D Plus systems)

 

 

Blow back

When this option is enabled, the controller

disabled,

disabled

 

periodically sends compressed air backward

enabled

 

 

through the station’s air filter to dislodge

 

 

 

accumulated dust and debris.

 

 

 

Enable this option if and only if the station has

 

 

 

the equipment for compressed-air filter cleaning.

 

 

Every n loads

Number of conveying cycles between filter

1–99

5

 

cleanings.

 

 

 

Adjust this setting based on experience. The

 

 

 

more dust and debris in your material line, the

 

 

 

smaller this number needs to be.

 

 

# pulses

Number of pulses of compressed air sent

1–99

5

 

through the station’s filter during cleaning.

 

 

 

If blow-back is not working as desired, the

 

 

 

service department may ask you to change this

 

 

 

setting.

 

 

7/50D Plus or 7/50D Controller

Chapter 6: Configurable Settings

75

Image 76
Contents SCC 7-Pump 50D & D Plus-Station Controllers Parts and Service Department Shipping Information Table of Contents Maintenance Controller Safety Tags How to Use This Manual SafetySafety Symbols Used in this Manual Wear Safety Glasses and Work Gloves Responsibility General ResponsibilityReporting a Safety Defect Maintenance ResponsibilityOperator Responsibility Models Covered in This Manual Functional DescriptionGeneral Description Standard Features Mechanical FeaturesElectrical Features Controller FeaturesOptional Features Safety Devices and InterlocksSafety Circuit Standards Fail Safe OperationSafety Device Lock-Outs Installation System Installation OverviewUncrating Mounting the Control PanelMaking Control Panel Power Drop Wiring Connections Electrical ConnectionsRunning KwikLink Cables About KwikLink Flat CablesInstalling KwikLink Cable Setting Up Mounting Plates Setting Up and Installing Mounting PlatesInstalling Assembled Mounting Plates Terminating Cable Runs Discard the standard resistor cap to eliminate confusionInstalling Inside KwikLink Connectors with Blank Caps Proper Termination ConnectionsAddressing and Installing ArmorBlocks Setting Armorblock AddressesAddressing Armorblocks ArmorBlock Address RangesInstalling ArmorBlocks Using seal block to pierce cableSecuring the Seal Block to the Cable Base Installing KwikLink Connectors Connecting the Controller to the Network Connecting the Remote Interface to the Main ControllerProper Controller and Remote Interface Connections Connecting the Power Supply Enclosure to the Network Proper Power Supply Enclosure Connections Connecting Vacuum Receivers to the Network 50D 4-Connector ArmorBlock ConnectionsPlus Connections Connecting Vacuum Pumps and Filter Chambers to the Network Connecting Vacuum PumpsProper Vacuum Pump Connections Connecting Filter Chambers Proper Filter Chamber ConnectionsConnecting Central Alarms to the Network Proper Central Alarm ConnectionsAlarm Horn C-O1 Setup Basic Menu Flow for SetupSetting Up the System Setting the Number of Stations and the Number of Pumps50D Plus Screen shown Checking Addressing and Wiring for System Components Page Page Setting Up Alarm Silences Setting Up Pump Staging Setting Up Touch Switch DelaySetting Up Stations Setting Up a Single Station50D Plus shown Copying Settings from One Station to Others To copy the selected station’s settings to one other station Setting Up Pumps Setting Up a Single PumpPage Copying Settings from One Pump to Others To copy the selected pump’s settings to one other pumpTo copy the current pump’s settings to all other pumps Finishing Setup Setting Up Passwords Page Initial Startup Overview OperationStarting and Stopping the System Basic Tasks Reviewing Station StatusColor Label Description Reviewing Pump Status Color Label Description Logging On and Logging Off Enabling and Disabling Stations and Pumps Reviewing and Adjusting Basic Station Settings Reaching and Reading the Station Operator ScreensAdjusting Convey Time and Dump Delay Navigating among the Station Operator ScreensActivating and Stopping Priority Convey for a Station Changing the Mixture for a Remote Proportioning ValveAdvanced Tasks Changing the Line with Material ProofingReviewing and Resetting a Pump Hour Meter Transferring Stations to a Standby Pump Page Page Alarms Reviewing AlarmsClearing the Alarm Log Touch ContinueSilencing Alarms Maintenance Preventative MaintenanceCorrective Maintenance Network Scanner Module ConsiderationsOptions for Station Setup Configurable SettingsMemory Module Considerations 50D Plus or 7/50D Controller Configurable Settings Blow Back Options Only available on 7/50D Plus systems Only available on 7/50D Plus systems 50D Plus or 7/50D Controller Configurable Settings Options for Pump Setup 50D Plus or 7/50D Controller Configurable Settings Troubleshooting General TroubleshootingStation Alarms Alarm message Possible causePump Alarms System Alarms Appendix WarrantyOptional Components Drawings and Diagrams Pump 50 station Controller with ??? DisplayTypical System Installation Layout 50D Plus or 7/50D Controller Appendix Spare Parts List Returned Material PolicyAC Voltage DC VoltageSafety Tag Information Warranty ReturnsController Safety Tags Controller Identification Serial Number TagService Department Technical Assistance Contact InformationParts Department Sales Department