Sterling Plumbing 882.00254.00 specifications System Alarms

Page 84

Alarm message

Possible cause

Output power failure

Power flat cable for network is not installed in ArmorBlock base

(Critical)

properly

Pump failure

Circuit breaker or overload protector has tripped.

(Critical)

Contactor has malfunctioned.

Pump fault #1

(Function determined by your facility.)

Pump fault #2

(Function determined by your facility.)

Pump starter output failure

Patch cord for contactor is disconnected.

Patch cord for contactor has been cut.

(Critical)

Contactor coil is defective.

 

Vent solenoid output failure

Patch cord for vent is disconnected.

Patch cord for vent has been cut.

(Critical)

Vent solenoid valve has malfunctioned.

 

System Alarms

Alarm message

Possible cause

Central alarm failure

Patch cord for horn or strobe light is disconnected.

Patch cord for horn or strobe light has been cut.

 

All horns and strobe lights for this central alarm are defective.

 

Power supply for a centralized purge valve is not turned on.

Centralized purge output power

Power supply for a centralized purge is not connected properly.

An ArmorBlock for centralized purge valves is defective.

failure

Base of an ArmorBlock for centralized purge valves is defective.

(Critical)

Power flat cable for network is not properly installed in the base of an

 

 

ArmorBlock for centralized purge valves.

 

Patch cord for a centralized purge valve is disconnected.

 

Patch cord for a centralized purge valve has been cut.

 

Solenoid for a centralized purge valve has malfunctioned.

 

An ArmorBlock for centralized purge valves is defective.

 

Base of an ArmorBlock for centralized purge valves is defective.

Centralized purge valve failure

Network flat cable is not properly installed in the base of an

ArmorBlock for centralized purge valves.

(Critical)

 

Note: Once you have found and corrected the cause of this alarm,

 

enable a station (p. 60) that uses the purge valve for which the alarm

 

occurred. (To identify such a station, go to a Station Operator screen

 

(p. 61) and navigate among the stations (p. 62) until you find a

 

station assigned to this purge valve.) Once the system successfully

 

uses this purge valve, it clears the alarm and enables all other

 

stations that use this valve.

PLC low battery

Battery for the controller is defective.

Battery for the controller is old and drained.

 

Scanner communication failure

Power supply for network is not turned on.

Power supply for network is not connected properly.

(Critical)

Main enclosure is not connected properly.

 

DeviceNet scanner is defective.

Scanner duplicate node

Two nodes (stations, pumps, central alarms, or centralized purge

(Critical)

valves) are assigned the same address.

Scanner incorrect node

The ArmorBlock for a pump has an address for a station.

assignment

The ArmorBlock for a central alarm has an address for a station.

(Critical)

The ArmorBlock for a station has an address for a pump.

7/50D Plus or 7/50D Controller

Chapter 7: Troubleshooting

83

Image 84
Contents SCC 7-Pump 50D & D Plus-Station Controllers Parts and Service Department Shipping Information Table of Contents Maintenance Controller Safety Tags Safety How to Use This ManualSafety Symbols Used in this Manual Wear Safety Glasses and Work Gloves Responsibility General ResponsibilityMaintenance Responsibility Reporting a Safety DefectOperator Responsibility Functional Description Models Covered in This ManualGeneral Description Standard Features Mechanical FeaturesElectrical Features Controller FeaturesOptional Features Safety Devices and InterlocksSafety Circuit Standards Fail Safe OperationSafety Device Lock-Outs Installation System Installation OverviewUncrating Mounting the Control PanelMaking Control Panel Power Drop Wiring Connections Electrical ConnectionsRunning KwikLink Cables About KwikLink Flat CablesInstalling KwikLink Cable Setting Up and Installing Mounting Plates Setting Up Mounting PlatesInstalling Assembled Mounting Plates Terminating Cable Runs Discard the standard resistor cap to eliminate confusionInstalling Inside KwikLink Connectors with Blank Caps Proper Termination ConnectionsAddressing and Installing ArmorBlocks Setting Armorblock AddressesAddressing Armorblocks ArmorBlock Address RangesInstalling ArmorBlocks Using seal block to pierce cableSecuring the Seal Block to the Cable Base Installing KwikLink Connectors Connecting the Controller to the Network Connecting the Remote Interface to the Main ControllerProper Controller and Remote Interface Connections Connecting the Power Supply Enclosure to the Network Proper Power Supply Enclosure Connections Connecting Vacuum Receivers to the Network 50D 4-Connector ArmorBlock ConnectionsPlus Connections Connecting Vacuum Pumps and Filter Chambers to the Network Connecting Vacuum PumpsProper Vacuum Pump Connections Connecting Filter Chambers Proper Filter Chamber ConnectionsConnecting Central Alarms to the Network Proper Central Alarm ConnectionsAlarm Horn C-O1 Setup Basic Menu Flow for SetupSetting Up the System Setting the Number of Stations and the Number of Pumps50D Plus Screen shown Checking Addressing and Wiring for System Components Page Page Setting Up Alarm Silences Setting Up Pump Staging Setting Up Touch Switch DelaySetting Up Stations Setting Up a Single Station50D Plus shown Copying Settings from One Station to Others To copy the selected station’s settings to one other station Setting Up Pumps Setting Up a Single PumpPage Copying Settings from One Pump to Others To copy the selected pump’s settings to one other pumpTo copy the current pump’s settings to all other pumps Finishing Setup Setting Up Passwords Page Initial Startup Operation OverviewStarting and Stopping the System Basic Tasks Reviewing Station StatusColor Label Description Reviewing Pump Status Color Label Description Logging On and Logging Off Enabling and Disabling Stations and Pumps Reviewing and Adjusting Basic Station Settings Reaching and Reading the Station Operator ScreensAdjusting Convey Time and Dump Delay Navigating among the Station Operator ScreensActivating and Stopping Priority Convey for a Station Changing the Mixture for a Remote Proportioning ValveAdvanced Tasks Changing the Line with Material ProofingReviewing and Resetting a Pump Hour Meter Transferring Stations to a Standby Pump Page Page Alarms Reviewing AlarmsClearing the Alarm Log Touch ContinueSilencing Alarms Maintenance Preventative MaintenanceCorrective Maintenance Network Scanner Module ConsiderationsConfigurable Settings Options for Station SetupMemory Module Considerations 50D Plus or 7/50D Controller Configurable Settings Blow Back Options Only available on 7/50D Plus systems Only available on 7/50D Plus systems 50D Plus or 7/50D Controller Configurable Settings Options for Pump Setup 50D Plus or 7/50D Controller Configurable Settings Troubleshooting General TroubleshootingStation Alarms Alarm message Possible causePump Alarms System Alarms Warranty AppendixOptional Components Drawings and Diagrams Pump 50 station Controller with ??? DisplayTypical System Installation Layout 50D Plus or 7/50D Controller Appendix Spare Parts List Returned Material PolicyAC Voltage DC VoltageSafety Tag Information Warranty ReturnsController Safety Tags Controller Identification Serial Number TagService Department Technical Assistance Contact InformationParts Department Sales Department