Sterling Plumbing 882.00254.00 specifications Navigating among the Station Operator Screens

Page 63

Navigating among the Station Operator Screens

The controls in the upper right-hand corner of the screen enable you to move among the Station Operator screens:

1.To display the screen for the next lower-numbered station (for example, to move from the screen for Station 15 to the screen for Station 14), touch ◄ Back.

2.To display the screen for the next higher-numbered station (for example, to move from the screen for Station 15 to the screen for Station 16), touch Next ►.

3.To display the screen for a specific station, touch Goto. A keypad pops up. Enter the number for the desired station. Use ← to erase any mistakes. Use ↵ to enter the value.

4.To exit to the Station Summary (or Pump Summary) screen, touch Stations (or

Pumps).

Adjusting Convey Time and Dump Delay

Convey time is the length of time the station’s vacuum valve remains open to allow material to be drawn in. (For a volume-fill station, the valve closes when material covers the station’s volume-fill proximity sensor or this time elapses, whichever comes first.)

Dump delay is the length of time allowed for material to drain from the station into its receiver. During this time, the controller does not attempt to deliver any more material to the station.

The settings for convey time and dump delay should match the times actually required to fill and empty the station. The following problems may occur if these settings are incorrect:

1.Material is backing up and causing “high vacuum” alarms (for time-fill stations only): Convey time is too long.

2.System is not keeping up with the demand for material: Convey time is too short, or dump delay is too long.

For your reference, the Station n Operator screen shows the length of time the controller actually spent conveying material during the most recent delivery under Last Convey Time.

To adjust a station’s convey time (or the dump delay):

1.Go to the Station n Operator screen (as described on p. 61), or go to the Station n Setup screen.

2.Touch Convey Time (or Dump Delay). A keypad pops up.

3.Enter the number of seconds desired. Use ← to erase any mistakes. Use ↵ to enter the value.

The new setting appears under Convey Time (or Dump Delay).

Note: If you change convey time by more than a few seconds for a station with a remote proportioning valve (RPV), notify the setup personnel at your facility. The setting for the RPV’s cycle time should be adjusted to divide evenly into the new convey time (see pp. 43 and 77).

7/50D Plus or 7/50D Controller

Chapter 4: Operation

62

Image 63
Contents SCC 7-Pump 50D & D Plus-Station Controllers Parts and Service Department Shipping Information Table of Contents Maintenance Controller Safety Tags Safety How to Use This ManualSafety Symbols Used in this Manual Wear Safety Glasses and Work Gloves General Responsibility ResponsibilityMaintenance Responsibility Reporting a Safety DefectOperator Responsibility Functional Description Models Covered in This ManualGeneral Description Controller Features Standard FeaturesMechanical Features Electrical FeaturesFail Safe Operation Optional FeaturesSafety Devices and Interlocks Safety Circuit StandardsSafety Device Lock-Outs Mounting the Control Panel InstallationSystem Installation Overview UncratingAbout KwikLink Flat Cables Making Control Panel Power Drop Wiring ConnectionsElectrical Connections Running KwikLink CablesInstalling KwikLink Cable Setting Up and Installing Mounting Plates Setting Up Mounting PlatesInstalling Assembled Mounting Plates Discard the standard resistor cap to eliminate confusion Terminating Cable RunsProper Termination Connections Installing Inside KwikLink Connectors with Blank CapsArmorBlock Address Ranges Addressing and Installing ArmorBlocksSetting Armorblock Addresses Addressing ArmorblocksUsing seal block to pierce cable Installing ArmorBlocksSecuring the Seal Block to the Cable Base Installing KwikLink Connectors Connecting the Remote Interface to the Main Controller Connecting the Controller to the NetworkProper Controller and Remote Interface Connections Connecting the Power Supply Enclosure to the Network Proper Power Supply Enclosure Connections 50D 4-Connector ArmorBlock Connections Connecting Vacuum Receivers to the NetworkPlus Connections Connecting Vacuum Pumps Connecting Vacuum Pumps and Filter Chambers to the NetworkProper Vacuum Pump Connections Proper Filter Chamber Connections Connecting Filter ChambersProper Central Alarm Connections Connecting Central Alarms to the NetworkAlarm Horn C-O1 Basic Menu Flow for Setup SetupSetting the Number of Stations and the Number of Pumps Setting Up the System50D Plus Screen shown Checking Addressing and Wiring for System Components Page Page Setting Up Alarm Silences Setting Up Touch Switch Delay Setting Up Pump StagingSetting Up a Single Station Setting Up Stations50D Plus shown Copying Settings from One Station to Others To copy the selected station’s settings to one other station Setting Up a Single Pump Setting Up PumpsPage To copy the selected pump’s settings to one other pump Copying Settings from One Pump to OthersTo copy the current pump’s settings to all other pumps Finishing Setup Setting Up Passwords Page Initial Startup Operation OverviewStarting and Stopping the System Reviewing Station Status Basic TasksColor Label Description Reviewing Pump Status Color Label Description Logging On and Logging Off Enabling and Disabling Stations and Pumps Reaching and Reading the Station Operator Screens Reviewing and Adjusting Basic Station SettingsNavigating among the Station Operator Screens Adjusting Convey Time and Dump DelayChanging the Mixture for a Remote Proportioning Valve Activating and Stopping Priority Convey for a StationChanging the Line with Material Proofing Advanced TasksReviewing and Resetting a Pump Hour Meter Transferring Stations to a Standby Pump Page Page Reviewing Alarms AlarmsTouch Continue Clearing the Alarm LogSilencing Alarms Network Scanner Module Considerations MaintenancePreventative Maintenance Corrective MaintenanceConfigurable Settings Options for Station SetupMemory Module Considerations 50D Plus or 7/50D Controller Configurable Settings Blow Back Options Only available on 7/50D Plus systems Only available on 7/50D Plus systems 50D Plus or 7/50D Controller Configurable Settings Options for Pump Setup 50D Plus or 7/50D Controller Configurable Settings General Troubleshooting TroubleshootingAlarm message Possible cause Station AlarmsPump Alarms System Alarms Warranty AppendixOptional Components Pump 50 station Controller with ??? Display Drawings and DiagramsTypical System Installation Layout 50D Plus or 7/50D Controller Appendix DC Voltage Spare Parts ListReturned Material Policy AC VoltageController Identification Serial Number Tag Safety Tag InformationWarranty Returns Controller Safety TagsSales Department Service DepartmentTechnical Assistance Contact Information Parts Department