Sterling Plumbing 882.00254.00 specifications

Page 40

The DeviceNet Input Status screen appears:

Station numbers are stacked vertically as column headings in this screen.

2.Check that all inputs are on (green) or off (black) as expected and that they switch on and off as required:

a.Station demand switch: In a new installation, the box labeled Demand Switch should be green for every station (vacuum hopper) in the system. (All other boxes for demand switches will be black.) In a retrofit at an existing installation, each station’s Demand Switch box should be green unless the receiver bin under the station is in fact full.

b.Station volume-fill proximity switch: For each time-fill station, the box labeled Volume Fill Prox should be black; no further check is needed for these stations. For each volume-fill station, you should calibrate the sensor now and, at the same time, check this input. To calibrate the sensor, remove the station’s cover, extract the volume-fill proximity switch, and place the switch in a container of the material that you will be using at this station. Adjust the sensor according to the procedure given in the manufacturer’s documentation for the switch. While you are doing this, check that:

1.The box on this screen is green when the sensor indicates that no material is present, and

2.The box is black when the sensor indicates that material is present.

Then reinstall the switch in the station.

7/50D Plus or 7/50D Controller

Chapter 3: Installation

39

Image 40
Contents SCC 7-Pump 50D & D Plus-Station Controllers Parts and Service Department Shipping Information Table of Contents Maintenance Controller Safety Tags How to Use This Manual SafetySafety Symbols Used in this Manual Wear Safety Glasses and Work Gloves Responsibility General ResponsibilityReporting a Safety Defect Maintenance ResponsibilityOperator Responsibility Models Covered in This Manual Functional DescriptionGeneral Description Standard Features Mechanical FeaturesElectrical Features Controller FeaturesOptional Features Safety Devices and InterlocksSafety Circuit Standards Fail Safe OperationSafety Device Lock-Outs Installation System Installation OverviewUncrating Mounting the Control PanelMaking Control Panel Power Drop Wiring Connections Electrical ConnectionsRunning KwikLink Cables About KwikLink Flat CablesInstalling KwikLink Cable Setting Up Mounting Plates Setting Up and Installing Mounting PlatesInstalling Assembled Mounting Plates Terminating Cable Runs Discard the standard resistor cap to eliminate confusionInstalling Inside KwikLink Connectors with Blank Caps Proper Termination ConnectionsAddressing and Installing ArmorBlocks Setting Armorblock AddressesAddressing Armorblocks ArmorBlock Address RangesInstalling ArmorBlocks Using seal block to pierce cableSecuring the Seal Block to the Cable Base Installing KwikLink Connectors Connecting the Controller to the Network Connecting the Remote Interface to the Main ControllerProper Controller and Remote Interface Connections Connecting the Power Supply Enclosure to the Network Proper Power Supply Enclosure Connections Connecting Vacuum Receivers to the Network 50D 4-Connector ArmorBlock ConnectionsPlus Connections Connecting Vacuum Pumps and Filter Chambers to the Network Connecting Vacuum PumpsProper Vacuum Pump Connections Connecting Filter Chambers Proper Filter Chamber ConnectionsConnecting Central Alarms to the Network Proper Central Alarm ConnectionsAlarm Horn C-O1 Setup Basic Menu Flow for SetupSetting Up the System Setting the Number of Stations and the Number of Pumps50D Plus Screen shown Checking Addressing and Wiring for System Components Page Page Setting Up Alarm Silences Setting Up Pump Staging Setting Up Touch Switch DelaySetting Up Stations Setting Up a Single Station50D Plus shown Copying Settings from One Station to Others To copy the selected station’s settings to one other station Setting Up Pumps Setting Up a Single PumpPage Copying Settings from One Pump to Others To copy the selected pump’s settings to one other pumpTo copy the current pump’s settings to all other pumps Finishing Setup Setting Up Passwords Page Initial Startup Overview OperationStarting and Stopping the System Basic Tasks Reviewing Station StatusColor Label Description Reviewing Pump Status Color Label Description Logging On and Logging Off Enabling and Disabling Stations and Pumps Reviewing and Adjusting Basic Station Settings Reaching and Reading the Station Operator ScreensAdjusting Convey Time and Dump Delay Navigating among the Station Operator ScreensActivating and Stopping Priority Convey for a Station Changing the Mixture for a Remote Proportioning ValveAdvanced Tasks Changing the Line with Material ProofingReviewing and Resetting a Pump Hour Meter Transferring Stations to a Standby Pump Page Page Alarms Reviewing AlarmsClearing the Alarm Log Touch ContinueSilencing Alarms Maintenance Preventative MaintenanceCorrective Maintenance Network Scanner Module ConsiderationsOptions for Station Setup Configurable SettingsMemory Module Considerations 50D Plus or 7/50D Controller Configurable Settings Blow Back Options Only available on 7/50D Plus systems Only available on 7/50D Plus systems 50D Plus or 7/50D Controller Configurable Settings Options for Pump Setup 50D Plus or 7/50D Controller Configurable Settings Troubleshooting General TroubleshootingStation Alarms Alarm message Possible causePump Alarms System Alarms Appendix WarrantyOptional Components Drawings and Diagrams Pump 50 station Controller with ??? DisplayTypical System Installation Layout 50D Plus or 7/50D Controller Appendix Spare Parts List Returned Material PolicyAC Voltage DC VoltageSafety Tag Information Warranty ReturnsController Safety Tags Controller Identification Serial Number TagService Department Technical Assistance Contact InformationParts Department Sales Department