Removing the Bottom Panel

Remove the two screws that secure the bottom cap to the furnace. Pivot the bottom cap down to release the bottom panel. Once the bottom panel has been removed, reinstall the bottom cap. See figure 10.

Removing the Bottom Panel

Screw

Bottom Cap

Bottom Panel

FIGURE 10

Horizontal Application

Installation Clearances

Top

Left

 

FLOW

Right

 

AIR

 

 

 

End

 

 

End

 

Bottom

 

 

Vent Connector

Type C

 

Type B1

Type

 

 

 

 

Top

0

 

0

*Front

2−1/4 in. (57 mm)**

2−14 in. (57 mm)

 

 

 

Back

0

0

 

 

 

Ends

2 in. (51 mm)

2 in. (51 mm)

 

 

 

Vent

6 in. (152 mm)

1 in. (25 mm)

 

 

 

Floor

0‡

0‡

*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. ** 3−1/4 in. if single wall vent pipe is used.

‡For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.

FIGURE 11

Horizontal Applications

The SL280UHV furnace can be installed in horizontal ap- plications. Order kit number 51W10 (or use equivalent) from Lennox.

Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or al- cove installations are shown in figure 11.

This furnace may be installed in either an attic or a crawl- space. Either suspend the furnace from roof rafters or floor joists, as shown in figure 12, or install the furnace on a platform, as shown in figure 13.

Typical Horizontal Application

Unit Suspended in Attic or Crawlspace

Bracket

Metal Strap

Bottom Cap

3/16 inch

Air Flow

FIGURE 12

NOTE − Heavy−gauge perforated sheet metal straps may be used to suspend the unit from roof rafters or ceiling joists. When straps are used to suspend the unit in this way, support must be provided for both the ends. The straps must not interfere with the plenum or exhaust pip- ing installation. Cooling coils and supply and return air plenums must be supported separately.

NOTE − When the furnace is installed on a platform in a crawlspace, it must be elevated enough to avoid water damage and to allow the evaporator coil to drain.

Return Air −− Horizontal Applications

Return air must be brought in through the end of a furnace installed in a horizontal application. The furnace is equipped with a removable bottom panel to facilitate installation. See figure 10.

Page 11

Image 11
Contents Table of Contents Installation Instructions SL280UHVEither Side Unit Dimensions − inches mmReturn air from both sides Side Return Air OpeningSight Glass Access Panel Blower AssemblyParts Arrangement Shipping and Packing List Safety InformationSL280UHV Gas Furnace Evaporator Use of Furnace as Construction HeaterGeneral Air Handler UnitCombustion, Dilution & Ventilation Air Space ALL AIR from Inside Equipment in ConfinedEquipment Confined Space ALL AIR from Outside Equipment in Confined Space ALL AIR from OutsideEquipment in Confined Space Blower Motor Rigid LEG Setting EquipmentBottom Return AIR Base 20 X 25 XFurnace Front Indoor AIRTypical Horizontal Application Horizontal Application Installation Clearances Top LeftRight End BottomDuct System FiltersLeft Side Vent Discharge VentingUpflow Position Top Vent DischargeSide Vent Discharge Horizontal Left PositionHorizontal Right Position Vent Pipe Common Venting Using Metal−Lined Masonry ChimneyDisconnected Vent StickerThrough an unused masonry chimney flue is not considered Vent Connector102 127 −1/2 152 178 10−1/2 MIN MAX Feet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard Every 8 to 10 feet 2.44 to 3.01 m with suitable hang Ers or straps. Install a drip leg in vertical pipe runs to− In some localities, codes may require the installation Gas PipingRight−Side Air Discharge Horizontal ApplicationLeft−Side Air Discharge BOX Interior MAKE−UP BOX InstallationElectrical Electrostatic Discharge ESDCommunicating Non−CommunicatingIcomfortt Integrated Control Outdoor Unit Icomfort Touch Applications NON−COMMUNICATING System WiringCommunicating System Wiring 120V ConnectionsDIP Switch Settings and On−Board Links See figure OFF Single Stage Thermostat w Dual fuel capa Bilities SL280UHV Schematic Wiring Diagram Typical SL280UHV Field Wiring Diagram + = Data High Connection − = Data LOW Connection Integrated ControlRS−BUS Link TB82, future use −10% approx OFF On−Board Links 880 1045985 940SL280UH090V36B Blower Performance less filter 1095 12801220 11551110 12951235 11701100 13601230 11651380 12901225 1160+18% 1605 SL280UH110V60C Blower Performance less filter +18% 1785 SL280UH135V60D Blower Performance less filter Operating Sequence Thermostat energizes Y2 CompressorHoneywell GAS Valve For Your Safety Read Before LightingUnit Start−Up White Rodgers GAS ValveDial Gas Pressure AdjustmentGAS Meter Clocking Chart Proper CombustionHigh Altitude Heating Sequence of Operation Other Unit AdjustmentsSEC Heating Operation with TWO−STAGE ThermostatHeating Operation with Single Stage Thermostat Electrical SHOCK, Fire Or Explosion Hazard Service17− Reinstall burner box, manifold assembly and burner box SL280UHV BURNER, Combustion AIR Inducer Assembly13− To clean the combustion air inducer visually inspect 11− Back wash using steam. Begin from the burner openingSL280UHV NOX Inserts Repair Parts List Planned ServiceIntegrated Control Diagnostic Codes Integrated Control Diagnostic ModesEquipment is unable to communicate. Indicates Normal operation 5 seconds after fault recoveredFurnace / air handler. Clears after fault recovered Power at the thermostat. Alert stops all servicesAte feature will be set as ’installed’ and that could Reconfigure the system. Replace control if heatingMissioning and Execute ’Set Factory Default mode’ Control will still operate on default parameter setTion after fault is cleared Low pressure switch failed openSumes normal operation after fault is cleared Fault is clearedTo flame failure Open or not within specifications −hour soft lockOut. Clears when flame has been proven stable Soft lockout or resetVice is removed, or after power reset Pair/add duct. Cleared after the current service deIs not running. Check power to outdoor unit. Clears Error after current is sensed in both RUNSor run cycle, or after power reset Finished Program Unit Capacity/Size ModeCall for FIRST−STAGE Heat Troubleshooting Heating Sequence of OperationCall for Heat Satisfied Call for SECOND−STAGE Heat2ND Stage Heat Call for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE HeatCall for Cooling Troubleshooting Cooling Sequence of OperationCall for FAN Troubleshooting Continuous Fan Sequence of Operation