Lennox International Inc SL280UH090V48B, SL280UH070V36A, SL280UH090V36B Filters, Duct System

Page 12

Horizontal Application

 

Unit Installed on Platform

 

Line contact is permissible

 

See the unit nameplate for

 

clearances.

 

GAS

VENT

ENTRY

 

PIPE

SERVICE PLATFORM

 

FIGURE 13

WARNING

Improper installation of the furnace can result in per- sonal injury or death. Combustion and flue products must never be allowed to enter the return air system or the living space. Use screws and joint tape to seal the return air system to the furnace.

In platform installations with bottom return air, the furnace should be sealed airtight to the return air ple- num. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Al- low absolutely no sagging, cracks, gaps, etc.

The return and supply air duct systems must never be connected to or from other heating devices such as a fireplace or stove, etc. Fire, explosion, carbon monoxide poisoning, personal injury and/or proper- ty damage could result.

WARNING

The inner blower panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal inju- ry or death.

Filters

This unit is not equipped with a filter or rack. A field−pro- vided high−velocity filter is required for the unit to operate properly. Table 1 lists recommended filter sizes.

A filter must be in place any time the unit is operating.

TABLE 1

Furnace

Filter Size

Cabinet Width

Side Return

Bottom Return

 

 

 

 

 

 

 

14−1/2"

16 X 25 X 1 (1)

14 X 25 X 1 (1)

17−1/2"

16 X 25 X 1 (1)

16 X 25 X 1 (1)

21"

16 X 25 X 1 (1)

20 X 25 X 1 (1)

24−1/2"

16 X 25 X 1 (2)

24 X 25 X 1 (1)

Duct System

Use industry-approved standards (such as those pub- lished by Air Conditioning Contractors of America or Ameri- can Society of Heating, Refrigerating and Air Conditioning Engineers) to size and install the supply and return air duct system. This will result in a quiet and low-static system that has uniform air distribution.

NOTE − Do not operate the furnace in the heating mode with an external static pressure that exceeds 0.8 inches w.c. Higher external static pressures may cause erratic lim- it operation.

Supply Air Plenum

If the furnace is installed without a cooling coil, a removable access panel must be installed in the supply air duct. The access panel should be large enough to permit inspection (either by smoke or reflected light) of the heat exchanger for leaks after the furnace is installed. The furnace access panel must always be in place when the furnace is operat- ing and it must not allow leaks into the supply air duct sys- tem.

Return Air Plenum

NOTE − Return air must not be drawn from a room where this furnace, or any other gas−fueled appliance (i.e., water heater), or carbon monoxide− producing de- vice (i.e., wood fireplace) is installed.

When return air is drawn from a room, a negative pres- sure is created in the room. If a gas appliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in incomplete com- bustion and the formation of carbon monoxide gas. This toxic gas might then be distributed throughout the house by the furnace duct system.

In upflow applications, the return air can be brought in through the bottom or either side of the furnace. If a fur- nace with bottom return air is installed on a platform, make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely. Use fiberglass sealing strips, caulking, or equiva- lent sealing method between the plenum and the furnace cabinet to ensure a tight seal. If a filter is installed, size the return air duct to fit the filter frame.

Page 12

Image 12
Contents Installation Instructions SL280UHV Table of ContentsUnit Dimensions − inches mm Return air from both sidesSide Return Air Opening Either SideAccess Panel Blower Assembly Parts ArrangementSight Glass Safety Information SL280UHV Gas FurnaceShipping and Packing List Use of Furnace as Construction Heater GeneralAir Handler Unit EvaporatorCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from InsideEquipment in Confined Space ALL AIR from Outside Equipment in Confined SpaceEquipment Confined Space ALL AIR from Outside Setting Equipment BottomBlower Motor Rigid LEG 20 X 25 X Furnace FrontIndoor AIR Return AIR BaseHorizontal Application Installation Clearances Top Left RightEnd Bottom Typical Horizontal ApplicationFilters Duct SystemVenting Upflow PositionTop Vent Discharge Left Side Vent DischargeHorizontal Left Position Horizontal Right PositionSide Vent Discharge Common Venting Using Metal−Lined Masonry Chimney Disconnected VentSticker Vent PipeVent Connector Through an unused masonry chimney flue is not considered102 127 −1/2 152 178 10−1/2 MIN MAX Feet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard Ers or straps. Install a drip leg in vertical pipe runs to − In some localities, codes may require the installationGas Piping Every 8 to 10 feet 2.44 to 3.01 m with suitable hangHorizontal Application Left−Side Air DischargeRight−Side Air Discharge Interior MAKE−UP BOX Installation ElectricalElectrostatic Discharge ESD BOXNon−Communicating CommunicatingIcomfortt Integrated Control Outdoor Unit Icomfort Touch NON−COMMUNICATING System Wiring Communicating System Wiring120V Connections ApplicationsDIP Switch Settings and On−Board Links See figure OFF Single Stage Thermostat w Dual fuel capa Bilities SL280UHV Schematic Wiring Diagram Typical SL280UHV Field Wiring Diagram Integrated Control RS−BUS Link TB82, future use+ = Data High Connection − = Data LOW Connection −10% approx OFF On−Board Links 1045 985940 880SL280UH090V36B Blower Performance less filter 1280 12201155 10951295 12351170 11101360 12301165 11001290 12251160 1380+18% 1605 SL280UH110V60C Blower Performance less filter +18% 1785 SL280UH135V60D Blower Performance less filter Operating Sequence Compressor Thermostat energizes Y2For Your Safety Read Before Lighting Unit Start−UpWhite Rodgers GAS Valve Honeywell GAS ValveGas Pressure Adjustment GAS Meter Clocking ChartProper Combustion DialHigh Altitude Other Unit Adjustments Heating Sequence of OperationHeating Operation with TWO−STAGE Thermostat Heating Operation with Single Stage ThermostatSEC Service Electrical SHOCK, Fire Or Explosion HazardSL280UHV BURNER, Combustion AIR Inducer Assembly 13− To clean the combustion air inducer visually inspect11− Back wash using steam. Begin from the burner opening 17− Reinstall burner box, manifold assembly and burner boxSL280UHV NOX Inserts Planned Service Repair Parts ListIntegrated Control Diagnostic Modes Integrated Control Diagnostic CodesNormal operation 5 seconds after fault recovered Furnace / air handler. Clears after fault recoveredPower at the thermostat. Alert stops all services Equipment is unable to communicate. IndicatesReconfigure the system. Replace control if heating Missioning and Execute ’Set Factory Default mode’Control will still operate on default parameter set Ate feature will be set as ’installed’ and that couldLow pressure switch failed open Sumes normal operation after fault is clearedFault is cleared Tion after fault is clearedOpen or not within specifications −hour soft lock Out. Clears when flame has been proven stableSoft lockout or reset To flame failurePair/add duct. Cleared after the current service de Is not running. Check power to outdoor unit. ClearsError after current is sensed in both RUN Vice is removed, or after power resetSor run cycle, or after power reset Program Unit Capacity/Size Mode FinishedTroubleshooting Heating Sequence of Operation Call for FIRST−STAGE HeatCall for SECOND−STAGE Heat Call for Heat SatisfiedCall for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE Heat 2ND Stage HeatTroubleshooting Cooling Sequence of Operation Call for CoolingTroubleshooting Continuous Fan Sequence of Operation Call for FAN