Lennox International Inc SL280UH090V48B Heating Operation with TWO−STAGE Thermostat, Sec

Page 55

Applications Using A Single−Stage Thermostat See figure 38 for ignition control sequence

B − Heating Sequence −− Integrated Control Thermostat Selection DIP Switch 1 ON in tage" Position

NOTE − In these applications, two−stage heat will be initi- ated by the integrated control if heating demand has not been satisfied after the field adjustable period (7 or 12 min- utes).

1 − On a call for heat, thermostat first−stage contacts close sending a signal to the integrated control. The inte- grated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts. The combustion air inducer is ener- gized at low speed.

2 − Once the control receives a signal that the low pres- sure switch has closed, the combustion air inducer be- gins a 15−second pre−purge in low speed.

NOTE − If the low fire pressure switch does not close the combustion air inducer will switch to high fire. After a 15 second pre−purge the high fire pressure switch will close and the unit will begin operation on high fire. After 10 to 20 seconds of high fire operation the unit will switch to low fire.

3 − After the pre−purge is complete, a 20−second initial ig- nitor warm−up period begins. The combustion air in- ducer continues to operate at low speed.

4 − After the 20−second warm−up period has ended, the gas valve is energized on low fire (first stage) and ignition oc- curs. At the same time, the control module sends a sig- nal to begin an indoor blower 30−second ON−delay. When the delay ends, the indoor blower motor is ener- gized on the low fire heating speed and the HUM con- tacts are energized. The integrated control also initi- ates a second−stage on delay (factory−set at 7 minutes; adjustable to 12 minutes).

5 − If the heating demand continues beyond the second− stage on delay, the integrated control energizes the combustion air inducer at high speed. The control also checks the high fire (second stage) pressure switch to make sure it is closed. The high fire (second stage) gas valve is energized and the indoor blower motor is energized for operation at the high fire heating speed.

6 − When the thermostat heating demand is satisfied, the combustion air inducer begins a 5−second low speed post−purge. The field−selected indoor blower off delay begins. The indoor blower operates at the low−fire heating speed.

7 − When the combustion air post−purge period is com- plete, the inducer, the HUM contacts as well as the 120V ACC terminals are de−energized. The indoor blower is de−energized at the end of the off delay.

HEATING OPERATION WITH TWO−STAGE THERMOSTAT

1

15

35

39

30* second 80

5 SEC

blower

ON

Pre−Purge

Ignitor Warm−up

Trial For

blower

Post

delay

OFF

 

Ignition

 

Purge

 

 

 

1 stg heat demand

 

 

 

 

 

 

low speed CAI

 

 

 

 

 

 

ignitor

 

 

 

 

 

 

low fire gas valve

 

 

 

 

 

 

indoor blower low heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 stg heat demand

 

30 seconds RECOGNITION PERIOD

 

 

 

 

 

high speed CAI

 

 

 

 

 

 

 

high fire gas valve

 

 

 

 

 

 

 

indoor blower high heat

 

 

 

 

 

 

* Conventional thermostat 30 seconds, icomfort Touch® thermostat set for 30 adjustable 15 to 45 seconds.

FIGURE 37

HEATING OPERATION WITH SINGLE STAGE THERMOSTAT

 

 

 

1

 

15

35

39

30* second80

 

 

 

 

ON

 

Pre−Purge

 

 

Ignitor Warm−up

 

Trial For

 

 

 

 

 

 

 

 

 

 

blower

 

 

 

 

 

 

 

 

 

 

Ignition

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

heat demand

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

low speed CAI

 

 

 

 

 

 

 

 

 

 

 

ignitor

 

 

 

 

 

 

 

 

 

 

 

low fire gas valve

 

 

 

 

 

 

 

 

 

 

 

indoor blower low heat

 

 

 

 

 

 

 

 

 

 

 

5 SEC

Post Purge

blower

delay

7 or 12 minutes after heating demand begins, furnace switches to high fire (depends on setting)

high speed CAI

high fire gas valve indoor blower high heat

* Conventional thermostat 30 seconds, icomfort Touch® thermostat set for 30 adjustable 15 to 45 seconds.

FIGURE 38

Page 55

Image 55
Contents Table of Contents Installation Instructions SL280UHVEither Side Unit Dimensions − inches mmReturn air from both sides Side Return Air OpeningParts Arrangement Access Panel Blower AssemblySight Glass SL280UHV Gas Furnace Safety InformationShipping and Packing List Evaporator Use of Furnace as Construction HeaterGeneral Air Handler UnitCombustion, Dilution & Ventilation Air Space ALL AIR from Inside Equipment in ConfinedEquipment in Confined Space Equipment in Confined Space ALL AIR from OutsideEquipment Confined Space ALL AIR from Outside Bottom Setting EquipmentBlower Motor Rigid LEG Return AIR Base 20 X 25 XFurnace Front Indoor AIRTypical Horizontal Application Horizontal Application Installation Clearances Top LeftRight End BottomDuct System FiltersLeft Side Vent Discharge VentingUpflow Position Top Vent DischargeHorizontal Right Position Horizontal Left PositionSide Vent Discharge Vent Pipe Common Venting Using Metal−Lined Masonry ChimneyDisconnected Vent StickerThrough an unused masonry chimney flue is not considered Vent Connector102 127 −1/2 152 178 10−1/2 MIN MAX Feet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard Every 8 to 10 feet 2.44 to 3.01 m with suitable hang Ers or straps. Install a drip leg in vertical pipe runs to− In some localities, codes may require the installation Gas PipingLeft−Side Air Discharge Horizontal ApplicationRight−Side Air Discharge BOX Interior MAKE−UP BOX InstallationElectrical Electrostatic Discharge ESDCommunicating Non−CommunicatingIcomfortt Integrated Control Outdoor Unit Icomfort Touch Applications NON−COMMUNICATING System WiringCommunicating System Wiring 120V ConnectionsDIP Switch Settings and On−Board Links See figure OFF Single Stage Thermostat w Dual fuel capa Bilities SL280UHV Schematic Wiring Diagram Typical SL280UHV Field Wiring Diagram RS−BUS Link TB82, future use Integrated Control+ = Data High Connection − = Data LOW Connection −10% approx OFF On−Board Links 880 1045985 940SL280UH090V36B Blower Performance less filter 1095 12801220 11551110 12951235 11701100 13601230 11651380 12901225 1160+18% 1605 SL280UH110V60C Blower Performance less filter +18% 1785 SL280UH135V60D Blower Performance less filter Operating Sequence Thermostat energizes Y2 CompressorHoneywell GAS Valve For Your Safety Read Before LightingUnit Start−Up White Rodgers GAS ValveDial Gas Pressure AdjustmentGAS Meter Clocking Chart Proper CombustionHigh Altitude Heating Sequence of Operation Other Unit AdjustmentsHeating Operation with Single Stage Thermostat Heating Operation with TWO−STAGE ThermostatSEC Electrical SHOCK, Fire Or Explosion Hazard Service17− Reinstall burner box, manifold assembly and burner box SL280UHV BURNER, Combustion AIR Inducer Assembly13− To clean the combustion air inducer visually inspect 11− Back wash using steam. Begin from the burner openingSL280UHV NOX Inserts Repair Parts List Planned ServiceIntegrated Control Diagnostic Codes Integrated Control Diagnostic ModesEquipment is unable to communicate. Indicates Normal operation 5 seconds after fault recoveredFurnace / air handler. Clears after fault recovered Power at the thermostat. Alert stops all servicesAte feature will be set as ’installed’ and that could Reconfigure the system. Replace control if heatingMissioning and Execute ’Set Factory Default mode’ Control will still operate on default parameter setTion after fault is cleared Low pressure switch failed openSumes normal operation after fault is cleared Fault is clearedTo flame failure Open or not within specifications −hour soft lockOut. Clears when flame has been proven stable Soft lockout or resetVice is removed, or after power reset Pair/add duct. Cleared after the current service deIs not running. Check power to outdoor unit. Clears Error after current is sensed in both RUNSor run cycle, or after power reset Finished Program Unit Capacity/Size ModeCall for FIRST−STAGE Heat Troubleshooting Heating Sequence of OperationCall for Heat Satisfied Call for SECOND−STAGE Heat2ND Stage Heat Call for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE HeatCall for Cooling Troubleshooting Cooling Sequence of OperationCall for FAN Troubleshooting Continuous Fan Sequence of Operation