Integrated Control Diagnostic Codes (continued)

Code

Diagnostic Codes/Status of Equipment

Action Required to Clear and Recover

 

 

 

E 105

Device communication problem − No other devices on RS BUS (Commu-

Equipment is unable to communicate. Indicates

 

nication

numerous message errors. In most cases errors are

 

system).

related to electrical noise. Make sure high voltage

 

 

power is separated from RSBus. Check for mis−

 

 

wired and/or loose connections between the stat,

 

 

indoor unit and outdoor unit. Check for a high volt-

 

 

age source of noise close to the system. Fault

 

 

clears after communication is restored.

 

 

 

E 110

Low line voltage.

Line Voltage Low (Voltage lower than nameplate

 

 

rating). Check power line voltage and correct. Alarm

 

 

clears 5 seconds after fault recovered.

 

 

 

E 111

Line voltage polarity reversed.

Reverse line power voltage wiring. System resumes

 

 

normal operation 5 seconds after fault recovered.

 

 

 

E 112

Ground not detected

System shuts down. Provide proper earth ground.

 

 

System resumes normal operation 5 seconds after

 

 

fault recovered.

 

 

 

E 113

High line voltage.

Line Voltage High (Voltage higher than nameplate

 

 

rating). Provide power voltage within proper range.

 

 

System resumes normal operation 5 seconds after

 

 

fault recovered.

 

 

 

E 114

Line voltage frequency out−of−range.

No 60 Hertz Power. Check voltage and line power

 

 

frequency. Correct voltage and frequency problems.

 

 

System resumes normal operation 5 seconds after

 

 

fault recovered.

 

 

 

E 115

Low 24V − Control will restart if the error recovers.

24−Volt Power Low (Range is 18 to 30 volts). Check

 

 

and correct voltage. Check for additional power−rob-

 

 

bing equipment connected to system. May require

 

 

installation of larger VA transformer to be installed in

 

 

furnace / air handler. Clears after fault recovered.

 

 

 

E 116

High 24V.

24 Volt Power High (Range is 18 to 30 volts). Check

 

 

and correct voltage. Check for proper line voltage

 

 

(120V, 240V, etc.) to equipment. Clears when con-

 

 

trol senses proper voltage.

 

 

 

E 117

Poor ground detected (Warning only)

Provide proper grounding for unit. Check for proper

 

 

earth ground to the system. Warning only will clear

 

 

30 seconds after fault recovered.

 

 

 

E 120

Unresponsive device. Communication only.

Usually caused by delay in outdoor unit responding

 

 

to indoor unit poling. Recycle power. Check all wir-

 

 

ing connections. Cleared after unresponsive device

 

 

responds to any inquiry.

 

 

 

E 124

Active communicating thermostat signal missing for more than 3 min-

Equipment lost communication with the thermostat.

 

utes.

Check four wiring connections, ohm wires and cycle

 

 

power at the thermostat. Alert stops all services and

 

 

waits for heartbeat message from thermostat (sub-

 

 

net controller). Cleared after valid thermostat (sub-

 

 

net controller) message is received.

 

 

 

E 125

Control failed self−check, internal error, failed hardware. Will restart if

Hardware problem on the control. Cycle power on

 

error

control. Replace if problem prevents service and is

 

recovers. Integrated control not communicating. Covers hardware errors

persistent. Critical alert. Cleared 300 seconds after

 

(flame sense circuit faults, pin shorts, etc.).

fault recovered.

 

 

 

E 126

Control internal communication problem.

Hardware problem on the control. Cycle power on

 

 

control. Replace if problem prevents service and is

 

 

persistent. Cleared 300 seconds after fault recov-

 

 

ered.

 

 

 

Page 61

Image 61
Contents Table of Contents Installation Instructions SL280UHVReturn air from both sides Unit Dimensions − inches mmSide Return Air Opening Either SideParts Arrangement Access Panel Blower AssemblySight Glass SL280UHV Gas Furnace Safety InformationShipping and Packing List General Use of Furnace as Construction HeaterAir Handler Unit EvaporatorCombustion, Dilution & Ventilation Air Space ALL AIR from Inside Equipment in ConfinedEquipment in Confined Space Equipment in Confined Space ALL AIR from OutsideEquipment Confined Space ALL AIR from Outside Bottom Setting EquipmentBlower Motor Rigid LEG Furnace Front 20 X 25 XIndoor AIR Return AIR BaseRight Horizontal Application Installation Clearances Top LeftEnd Bottom Typical Horizontal ApplicationDuct System FiltersUpflow Position VentingTop Vent Discharge Left Side Vent DischargeHorizontal Right Position Horizontal Left PositionSide Vent Discharge Disconnected Vent Common Venting Using Metal−Lined Masonry ChimneySticker Vent PipeThrough an unused masonry chimney flue is not considered Vent Connector102 127 −1/2 152 178 10−1/2 MIN MAX Feet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard − In some localities, codes may require the installation Ers or straps. Install a drip leg in vertical pipe runs toGas Piping Every 8 to 10 feet 2.44 to 3.01 m with suitable hangLeft−Side Air Discharge Horizontal ApplicationRight−Side Air Discharge Electrical Interior MAKE−UP BOX InstallationElectrostatic Discharge ESD BOXCommunicating Non−CommunicatingIcomfortt Integrated Control Outdoor Unit Icomfort Touch Communicating System Wiring NON−COMMUNICATING System Wiring120V Connections ApplicationsDIP Switch Settings and On−Board Links See figure OFF Single Stage Thermostat w Dual fuel capa Bilities SL280UHV Schematic Wiring Diagram Typical SL280UHV Field Wiring Diagram RS−BUS Link TB82, future use Integrated Control+ = Data High Connection − = Data LOW Connection −10% approx OFF On−Board Links 985 1045940 880SL280UH090V36B Blower Performance less filter 1220 12801155 10951235 12951170 11101230 13601165 11001225 12901160 1380+18% 1605 SL280UH110V60C Blower Performance less filter +18% 1785 SL280UH135V60D Blower Performance less filter Operating Sequence Thermostat energizes Y2 CompressorUnit Start−Up For Your Safety Read Before LightingWhite Rodgers GAS Valve Honeywell GAS ValveGAS Meter Clocking Chart Gas Pressure AdjustmentProper Combustion DialHigh Altitude Heating Sequence of Operation Other Unit AdjustmentsHeating Operation with Single Stage Thermostat Heating Operation with TWO−STAGE ThermostatSEC Electrical SHOCK, Fire Or Explosion Hazard Service13− To clean the combustion air inducer visually inspect SL280UHV BURNER, Combustion AIR Inducer Assembly11− Back wash using steam. Begin from the burner opening 17− Reinstall burner box, manifold assembly and burner boxSL280UHV NOX Inserts Repair Parts List Planned ServiceIntegrated Control Diagnostic Codes Integrated Control Diagnostic ModesFurnace / air handler. Clears after fault recovered Normal operation 5 seconds after fault recoveredPower at the thermostat. Alert stops all services Equipment is unable to communicate. IndicatesMissioning and Execute ’Set Factory Default mode’ Reconfigure the system. Replace control if heatingControl will still operate on default parameter set Ate feature will be set as ’installed’ and that couldSumes normal operation after fault is cleared Low pressure switch failed openFault is cleared Tion after fault is clearedOut. Clears when flame has been proven stable Open or not within specifications −hour soft lockSoft lockout or reset To flame failureIs not running. Check power to outdoor unit. Clears Pair/add duct. Cleared after the current service deError after current is sensed in both RUN Vice is removed, or after power resetSor run cycle, or after power reset Finished Program Unit Capacity/Size ModeCall for FIRST−STAGE Heat Troubleshooting Heating Sequence of OperationCall for Heat Satisfied Call for SECOND−STAGE Heat2ND Stage Heat Call for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE HeatCall for Cooling Troubleshooting Cooling Sequence of OperationCall for FAN Troubleshooting Continuous Fan Sequence of Operation