Lennox International Inc Gas Piping, Every 8 to 10 feet 2.44 to 3.01 m with suitable hang

Page 23

Gas Piping

 

 

 

 

 

 

 

4 −

The piping should be sloped 1/4 inch (6.4 mm) per 15

 

 

 

 

 

 

 

 

feet (4.57 m) upward toward the meter from the fur-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nace. The piping must be supported at proper intervals

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION

 

 

 

 

 

 

[every 8 to 10 feet (2.44 to 3.01 m)] with suitable hang-

 

 

 

 

 

 

 

 

ers or straps. Install a drip leg in vertical pipe runs to the

 

 

 

 

 

 

 

 

 

 

 

If a flexible gas connector is required or allowed by

 

 

 

 

unit.

 

 

 

 

 

 

the authority that has jurisdiction, black iron pipe

 

 

 

5 −

A 1/8" N.P.T. plugged tap or pressure post

is located

shall be installed at the gas valve and extend outside

 

 

 

 

 

 

 

on the gas valve to facilitate test gauge connection.

the furnace cabinet. The flexible connector can then

 

 

 

 

 

 

 

 

See figures 35 and 36.

 

 

 

be added between the black iron pipe and the gas

 

 

 

 

 

 

 

 

 

 

6 − In some localities, codes may require the installation of

supply line.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a manual main shut-off valve and union (furnished by

Gas Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the installer) external to the unit. The union must be of

1 − This unit is shipped standard for left or right side instal-

 

 

 

the ground joint type.

 

 

 

 

lation of gas piping (or top entry in horizontal applica-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IMPORTANT

 

 

tions). Connect the gas supply to the piping assembly.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 −

When connecting the gas supply piping, consider fac-

 

 

 

 

 

 

 

 

 

 

 

 

 

Compounds used on threaded joints of gas piping

 

 

 

tors such as length of run, number of fittings, and fur-

 

 

 

 

 

must be resistant to the actions of liquified petro-

 

nace rating to avoid excessive pressure drop. Table 9

 

 

 

 

 

leum gases.

 

 

 

 

 

 

lists recommended pipe sizes for typical applications.

 

 

 

 

 

 

 

 

 

NOTE − If emergency shutoff is necessary, shut off the main

3 −

The gas piping must not run in or through air ducts,

 

 

clothes chutes, gas vents or chimneys, dumb waiters,

 

manual gas valve and disconnect main power to the fur-

 

or elevator shafts.

 

 

 

 

 

 

nace. The installer should properly label these devices.

 

 

 

 

 

 

TABLE 9

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Pipe Capacity − ft3/hr (m3/hr)

 

 

 

 

 

Nominal

Internal

 

 

 

 

 

Length of Pipe − feet (m)

 

 

 

Iron Pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Diameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inches

10

20

30

40

 

 

50

 

 

60

 

70

80

90

100

inches

 

 

 

 

 

(mm)

(3.048)

(6.096)

(9.144)

(12.192)

 

(15.240)

 

(18.288)

 

(21.336)

(24.384)

(27.432)

(30.480)

 

(mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2

.622

175

120

97

82

 

 

73

 

 

66

 

61

57

53

50

 

(12.7)

(17.799)

(4.96)

(3.40)

(2.75)

(2.32)

 

(2.07)

 

(1.87)

 

(1.73)

(1.61)

(1.50)

(1.42)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

.824

360

250

200

170

 

 

151

 

138

 

125

118

110

103

(19.05)

(20.930)

(10.19)

(7.08)

(5.66)

(4.81)

 

(4.28)

 

(3.91)

 

(3.54)

(3.34)

(3.11)

(2.92)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1.049

680

465

375

320

 

 

285

 

260

 

240

220

205

195

 

(25.4)

(26.645)

(919.25)

(13.17)

(10.62)

(9.06)

 

(8.07)

 

(7.36)

 

(6.80)

(6.23)

(5.80)

(5.52)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1−1/4

1.380

1400

950

770

660

 

 

580

 

530

 

490

460

430

400

(31.75)

(35.052)

(39.64)

(26.90)

(21.80)

(18.69)

 

(16.42)

 

(15.01)

 

(13.87)

(13.03)

(12.18)

(11.33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1−1/2

1.610

2100

460

1180

990

 

 

900

 

810

 

750

690

650

620

 

(38.1)

(40.894)

(59.46)

(41.34)

(33.41)

(28.03)

 

(25.48)

 

(22.94)

 

(21.24)

(19.54)

(18.41)

(17.56)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

2.067

3950

2750

2200

1900

 

1680

 

1520

 

1400

1300

1220

1150

 

(50.8)

(52.502)

(111.85)

(77.87)

(62.30)

(53.80)

 

(47.57)

 

(43.04)

 

(39.64)

(36.81)

(34.55)

(32.56)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2−1/2

2.469

6300

4350

3520

3000

 

2650

 

2400

 

2250

2050

1950

1850

 

(63.5)

(67.713)

(178.39)

(123.17)

(99.67)

(84.95

 

(75.04)

 

(67.96)

 

(63.71)

(58.05)

(55.22)

(52.38)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

3.068

11000

7700

6250

5300

 

4750

 

4300

 

3900

3700

3450

3250

 

(76.2)

(77.927)

(311.48)

(218.03)

(176.98)

(150.07)

 

(134.50)

 

(121.76)

 

(110.43)

(104.77)

(97.69)

(92.03)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE − Capacity given in cubic feet (m3 ) of gas per hour and based on 0.60 specific gravity gas.

Page 23

Image 23
Contents Table of Contents Installation Instructions SL280UHVEither Side Unit Dimensions − inches mmReturn air from both sides Side Return Air OpeningSight Glass Access Panel Blower AssemblyParts Arrangement Shipping and Packing List Safety InformationSL280UHV Gas Furnace Evaporator Use of Furnace as Construction HeaterGeneral Air Handler UnitCombustion, Dilution & Ventilation Air Space ALL AIR from Inside Equipment in ConfinedEquipment Confined Space ALL AIR from Outside Equipment in Confined Space ALL AIR from OutsideEquipment in Confined Space Blower Motor Rigid LEG Setting EquipmentBottom Return AIR Base 20 X 25 XFurnace Front Indoor AIRTypical Horizontal Application Horizontal Application Installation Clearances Top LeftRight End BottomDuct System FiltersLeft Side Vent Discharge VentingUpflow Position Top Vent DischargeSide Vent Discharge Horizontal Left PositionHorizontal Right Position Vent Pipe Common Venting Using Metal−Lined Masonry ChimneyDisconnected Vent StickerThrough an unused masonry chimney flue is not considered Vent Connector102 127 −1/2 152 178 10−1/2 MIN MAX Feet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard Every 8 to 10 feet 2.44 to 3.01 m with suitable hang Ers or straps. Install a drip leg in vertical pipe runs to− In some localities, codes may require the installation Gas PipingRight−Side Air Discharge Horizontal ApplicationLeft−Side Air Discharge BOX Interior MAKE−UP BOX InstallationElectrical Electrostatic Discharge ESDCommunicating Non−CommunicatingIcomfortt Integrated Control Outdoor Unit Icomfort Touch Applications NON−COMMUNICATING System WiringCommunicating System Wiring 120V ConnectionsDIP Switch Settings and On−Board Links See figure OFF Single Stage Thermostat w Dual fuel capa Bilities SL280UHV Schematic Wiring Diagram Typical SL280UHV Field Wiring Diagram + = Data High Connection − = Data LOW Connection Integrated ControlRS−BUS Link TB82, future use −10% approx OFF On−Board Links 880 1045985 940SL280UH090V36B Blower Performance less filter 1095 12801220 11551110 12951235 11701100 13601230 11651380 12901225 1160+18% 1605 SL280UH110V60C Blower Performance less filter +18% 1785 SL280UH135V60D Blower Performance less filter Operating Sequence Thermostat energizes Y2 CompressorHoneywell GAS Valve For Your Safety Read Before LightingUnit Start−Up White Rodgers GAS ValveDial Gas Pressure AdjustmentGAS Meter Clocking Chart Proper CombustionHigh Altitude Heating Sequence of Operation Other Unit AdjustmentsSEC Heating Operation with TWO−STAGE ThermostatHeating Operation with Single Stage Thermostat Electrical SHOCK, Fire Or Explosion Hazard Service17− Reinstall burner box, manifold assembly and burner box SL280UHV BURNER, Combustion AIR Inducer Assembly13− To clean the combustion air inducer visually inspect 11− Back wash using steam. Begin from the burner openingSL280UHV NOX Inserts Repair Parts List Planned ServiceIntegrated Control Diagnostic Codes Integrated Control Diagnostic ModesEquipment is unable to communicate. Indicates Normal operation 5 seconds after fault recoveredFurnace / air handler. Clears after fault recovered Power at the thermostat. Alert stops all servicesAte feature will be set as ’installed’ and that could Reconfigure the system. Replace control if heatingMissioning and Execute ’Set Factory Default mode’ Control will still operate on default parameter setTion after fault is cleared Low pressure switch failed openSumes normal operation after fault is cleared Fault is clearedTo flame failure Open or not within specifications −hour soft lockOut. Clears when flame has been proven stable Soft lockout or resetVice is removed, or after power reset Pair/add duct. Cleared after the current service deIs not running. Check power to outdoor unit. Clears Error after current is sensed in both RUNSor run cycle, or after power reset Finished Program Unit Capacity/Size ModeCall for FIRST−STAGE Heat Troubleshooting Heating Sequence of OperationCall for Heat Satisfied Call for SECOND−STAGE Heat2ND Stage Heat Call for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE HeatCall for Cooling Troubleshooting Cooling Sequence of OperationCall for FAN Troubleshooting Continuous Fan Sequence of Operation