Lennox International Inc SL280UH090V36B Other Unit Adjustments, Heating Sequence of Operation

Page 54

Other Unit Adjustments

Primary and Secondary Limits

The primary limit is located on the heating compartment vestibule panel. The secondary limits (if equipped) are lo- cated in the blower compartment, attached to the back side of the blower. These auto reset limits are factory set and re- quire no adjustment.

Flame Rollout Switches (Two)

These manually reset switches are located on (or inside of) the burner box. If tripped, check for adequate combustion air before resetting.

Pressure Switches

The pressure switch assembly (includes two switches) is located in the heating compartment adjacent to the com- bustion air inducer. These switches check for proper com- bustion air inducer operation before allowing ignition trial. The switches are factory−set and require no adjustment.

Temperature Rise

Place the unit into operation with a second−stage heating demand. After supply and return air temperatures have stabilized, check the temperature rise. If necessary, adjust the heating blower speed to maintain the temperature rise within the range shown on the unit nameplate. Increase the blower speed to decrease the temperature rise. Decrease the blower speed to increase the temperature rise. Failure to properly adjust the temperature rise may cause erratic limit operation.

Thermostat Heat Anticipation

Set the heat anticipator setting (if adjustable) according to the amp draw listed on the wiring diagram that is attached to the unit.

NOTE − Do not secure the electrical conduit directly to the air ducts or structure.

Heating Sequence of Operation

Electronic Ignition

The two−stage, variable speed integrated control used in SL280UHV units has an added feature of an internal Watch- guard control. The feature serves as an automatic reset de- vice for ignition control lockout caused by ignition failure. Af- ter one hour of continuous thermostat demand for heat, the Watchguard will break and remake thermostat demand to the furnace and automatically reset the control to begin the ignition sequence.

NOTE − The ignition control thermostat selection DIP switch is factory−set in the AGE" position.

Applications Using a Two−Stage Thermostat See figure 37 for ignition control sequence

A − Heating Sequence −− Integrated Control Thermostat Selection DIP Switch 1 OFF in wo−Stage" Position (Factory Setting)

1 − On a call for heat, thermostat first−stage contacts close sending a signal to the integrated control. The inte- grated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts. The combustion air inducer is ener- gized at low speed.

2 − Once the control receives a signal that the low pres- sure switch has closed, the combustion air inducer be- gins a 15−second pre−purge in low speed.

NOTE − If the low fire pressure switch does not close the combustion air inducer will switch to high fire. After a 15 second pre−purge the high fire pressure switch will close and the unit will begin operation on high fire. After 10 to 20 seconds of high fire operation the unit will switch to low fire..

3 − After the pre−purge is complete, a 20−second initial ig- nitor warm−up period begins. The combustion air in- ducer continues to operate at low speed.

4 − After the 20−second warm−up period has ended, the gas valve is energized on low fire (first stage) and ignition oc- curs. At the same time, the control module sends a sig- nal to begin an indoor blower 30−second ON−delay. When the delay ends, the indoor blower motor is ener- gized on the low fire heating speed, the HUM contacts close energizing the humidifier and 120V ACC termi- nal is energized. The furnace will continue this opera- tion as long as the thermostat has a first−stage heating demand.

5 − If second−stage heat is required, the thermostat sec- ond−stage heat contacts close and send a signal to the integrated control. The integrated control initiates a 30−second second−stage recognition delay.

6 − At the end of the recognition delay, the integrated con- trol energizes the combustion air inducer at high speed. The control also checks the high fire (second stage) pressure switch to make sure it is closed. The high fire (second stage) gas valve is energized and the indoor blower motor is energized for operation at the high fire heating speed.

7 − When the demand for high fire (second stage) heat is satisfied, the combustion air inducer is switched to the low−fire heating speed and the high−fire (second stage) gas valve is de−energized. The low−fire (first stage) gas valve continues operation. The indoor blower motor is switched to the low−fire heating speed.

8 − When the thermostat demand for low−fire (first stage) heat is satisfied, the gas valve is de−energized and the field−selected indoor blower off delay begins. The combustion air inducer begins a 5−second post−purge period.

9 − When the combustion air post−purge period is com- plete, the inducer, the HUM contacts as well as the 120V ACC terminals are de−energized. The indoor blower is de−energized at the end of the off delay.

Page 54

Image 54
Contents Installation Instructions SL280UHV Table of ContentsSide Return Air Opening Unit Dimensions − inches mmReturn air from both sides Either SideAccess Panel Blower Assembly Parts ArrangementSight Glass Safety Information SL280UHV Gas FurnaceShipping and Packing List Air Handler Unit Use of Furnace as Construction HeaterGeneral EvaporatorCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from InsideEquipment in Confined Space ALL AIR from Outside Equipment in Confined SpaceEquipment Confined Space ALL AIR from Outside Setting Equipment BottomBlower Motor Rigid LEG Indoor AIR 20 X 25 XFurnace Front Return AIR BaseEnd Bottom Horizontal Application Installation Clearances Top LeftRight Typical Horizontal ApplicationFilters Duct SystemTop Vent Discharge VentingUpflow Position Left Side Vent DischargeHorizontal Left Position Horizontal Right PositionSide Vent Discharge Sticker Common Venting Using Metal−Lined Masonry ChimneyDisconnected Vent Vent PipeVent Connector Through an unused masonry chimney flue is not considered102 127 −1/2 152 178 10−1/2 MIN MAX Feet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard Gas Piping Ers or straps. Install a drip leg in vertical pipe runs to− In some localities, codes may require the installation Every 8 to 10 feet 2.44 to 3.01 m with suitable hangHorizontal Application Left−Side Air DischargeRight−Side Air Discharge Electrostatic Discharge ESD Interior MAKE−UP BOX InstallationElectrical BOXNon−Communicating CommunicatingIcomfortt Integrated Control Outdoor Unit Icomfort Touch 120V Connections NON−COMMUNICATING System WiringCommunicating System Wiring ApplicationsDIP Switch Settings and On−Board Links See figure OFF Single Stage Thermostat w Dual fuel capa Bilities SL280UHV Schematic Wiring Diagram Typical SL280UHV Field Wiring Diagram Integrated Control RS−BUS Link TB82, future use+ = Data High Connection − = Data LOW Connection −10% approx OFF On−Board Links 940 1045985 880SL280UH090V36B Blower Performance less filter 1155 12801220 10951170 12951235 11101165 13601230 11001160 12901225 1380+18% 1605 SL280UH110V60C Blower Performance less filter +18% 1785 SL280UH135V60D Blower Performance less filter Operating Sequence Compressor Thermostat energizes Y2White Rodgers GAS Valve For Your Safety Read Before LightingUnit Start−Up Honeywell GAS ValveProper Combustion Gas Pressure AdjustmentGAS Meter Clocking Chart DialHigh Altitude Other Unit Adjustments Heating Sequence of OperationHeating Operation with TWO−STAGE Thermostat Heating Operation with Single Stage ThermostatSEC Service Electrical SHOCK, Fire Or Explosion Hazard11− Back wash using steam. Begin from the burner opening SL280UHV BURNER, Combustion AIR Inducer Assembly13− To clean the combustion air inducer visually inspect 17− Reinstall burner box, manifold assembly and burner boxSL280UHV NOX Inserts Planned Service Repair Parts ListIntegrated Control Diagnostic Modes Integrated Control Diagnostic CodesPower at the thermostat. Alert stops all services Normal operation 5 seconds after fault recoveredFurnace / air handler. Clears after fault recovered Equipment is unable to communicate. IndicatesControl will still operate on default parameter set Reconfigure the system. Replace control if heatingMissioning and Execute ’Set Factory Default mode’ Ate feature will be set as ’installed’ and that couldFault is cleared Low pressure switch failed openSumes normal operation after fault is cleared Tion after fault is clearedSoft lockout or reset Open or not within specifications −hour soft lockOut. Clears when flame has been proven stable To flame failureError after current is sensed in both RUN Pair/add duct. Cleared after the current service deIs not running. Check power to outdoor unit. Clears Vice is removed, or after power resetSor run cycle, or after power reset Program Unit Capacity/Size Mode FinishedTroubleshooting Heating Sequence of Operation Call for FIRST−STAGE HeatCall for SECOND−STAGE Heat Call for Heat SatisfiedCall for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE Heat 2ND Stage HeatTroubleshooting Cooling Sequence of Operation Call for CoolingTroubleshooting Continuous Fan Sequence of Operation Call for FAN