TABLE 5

Vent Connector Capacity

Type B Double−Wall Vents with Type B Double−Wall Connectors

Serving Two or More Category I Appliances

Vent

Connector

 

 

 

Vent and Connector Diameter − D (inches)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

Rise

 

3 Inch

 

4 Inch

 

5 Inch

 

6 Inch

 

 

 

 

 

 

 

 

 

 

 

 

H

R

 

 

 

Appliance Input Rating in Thousands of Btu Per Hour

 

 

 

(feet)

(feet)

 

 

 

 

 

 

 

 

 

 

 

 

MIN

 

MAX

MIN

 

MAX

MIN

 

MAX

MIN

 

MAX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

22

 

37

35

 

66

46

 

106

58

 

164

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

2

23

 

41

37

 

75

48

 

121

60

 

183

 

3

24

 

44

38

 

81

49

 

132

62

 

199

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

22

 

40

35

 

72

49

 

114

64

 

176

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

2

23

 

44

36

 

80

51

 

128

66

 

195

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

24

 

47

37

 

87

53

 

139

67

 

210

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

22

 

43

34

 

78

49

 

123

65

 

189

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

2

23

 

47

36

 

86

51

 

136

67

 

206

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

24

 

50

37

 

92

52

 

146

69

 

220

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

21

 

50

33

 

89

47

 

142

64

 

220

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

2

22

 

53

35

 

96

49

 

153

66

 

235

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

24

 

55

36

 

102

51

 

163

68

 

248

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

21

 

54

33

 

99

46

 

157

62

 

246

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

2

22

 

57

34

 

105

48

 

167

64

 

259

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

23

 

60

35

 

110

50

 

176

66

 

271

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

20

 

62

31

 

113

45

 

181

60

 

288

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

2

21

 

64

33

 

118

47

 

190

62

 

299

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

22

 

66

34

 

123

48

 

198

64

 

309

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 6

Common Vent Capacity

Type B Double−Wall Vents with Type B Double−Wall Connectors

Serving Two or More Category I Appliances

Vent

 

 

 

Common Vent Diameter − D (inches)

 

 

 

 

 

 

 

 

 

 

 

Height

4 Inch

5 Inch

6 Inch

7 Inch

 

 

 

 

 

 

 

 

 

H

 

 

Appliance Input Rating in Thousands of Btu Per Hour

 

 

(feet)

 

 

 

 

 

 

 

 

 

FAN + FAN

FAN + NAT

FAN + FAN

 

FAN + NAT

FAN + FAN

FAN + NAT

FAN + FAN

FAN + NAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

92

81

140

 

116

204

161

309

248

 

 

 

 

 

 

 

 

 

 

8

101

90

155

 

129

224

178

339

275

 

 

 

 

 

 

 

 

 

 

10

110

97

169

 

141

243

194

367

299

 

 

 

 

 

 

 

 

 

 

15

125

112

195

 

164

283

228

427

352

 

 

 

 

 

 

 

 

 

 

20

136

123

215

 

183

314

255

475

394

 

 

 

 

 

 

 

 

 

 

30

152

138

244

 

210

361

297

547

459

 

 

 

 

 

 

 

 

 

 

Page 20

Image 20
Contents Installation Instructions SL280UHV Table of ContentsUnit Dimensions − inches mm Return air from both sidesSide Return Air Opening Either SideSight Glass Access Panel Blower AssemblyParts Arrangement Shipping and Packing List Safety InformationSL280UHV Gas Furnace Use of Furnace as Construction Heater GeneralAir Handler Unit EvaporatorCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from InsideEquipment Confined Space ALL AIR from Outside Equipment in Confined Space ALL AIR from OutsideEquipment in Confined Space Blower Motor Rigid LEG Setting EquipmentBottom 20 X 25 X Furnace FrontIndoor AIR Return AIR BaseHorizontal Application Installation Clearances Top Left RightEnd Bottom Typical Horizontal ApplicationFilters Duct SystemVenting Upflow PositionTop Vent Discharge Left Side Vent DischargeSide Vent Discharge Horizontal Left PositionHorizontal Right Position Common Venting Using Metal−Lined Masonry Chimney Disconnected VentSticker Vent PipeVent Connector Through an unused masonry chimney flue is not considered102 127 −1/2 152 178 10−1/2 MIN MAX Feet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard Ers or straps. Install a drip leg in vertical pipe runs to − In some localities, codes may require the installationGas Piping Every 8 to 10 feet 2.44 to 3.01 m with suitable hangRight−Side Air Discharge Horizontal ApplicationLeft−Side Air Discharge Interior MAKE−UP BOX Installation ElectricalElectrostatic Discharge ESD BOXNon−Communicating CommunicatingIcomfortt Integrated Control Outdoor Unit Icomfort Touch NON−COMMUNICATING System Wiring Communicating System Wiring120V Connections ApplicationsDIP Switch Settings and On−Board Links See figure OFF Single Stage Thermostat w Dual fuel capa Bilities SL280UHV Schematic Wiring Diagram Typical SL280UHV Field Wiring Diagram + = Data High Connection − = Data LOW Connection Integrated ControlRS−BUS Link TB82, future use −10% approx OFF On−Board Links 1045 985940 880SL280UH090V36B Blower Performance less filter 1280 12201155 10951295 12351170 11101360 12301165 11001290 12251160 1380+18% 1605 SL280UH110V60C Blower Performance less filter +18% 1785 SL280UH135V60D Blower Performance less filter Operating Sequence Compressor Thermostat energizes Y2For Your Safety Read Before Lighting Unit Start−UpWhite Rodgers GAS Valve Honeywell GAS ValveGas Pressure Adjustment GAS Meter Clocking ChartProper Combustion DialHigh Altitude Other Unit Adjustments Heating Sequence of OperationSEC Heating Operation with TWO−STAGE ThermostatHeating Operation with Single Stage Thermostat Service Electrical SHOCK, Fire Or Explosion HazardSL280UHV BURNER, Combustion AIR Inducer Assembly 13− To clean the combustion air inducer visually inspect11− Back wash using steam. Begin from the burner opening 17− Reinstall burner box, manifold assembly and burner boxSL280UHV NOX Inserts Planned Service Repair Parts ListIntegrated Control Diagnostic Modes Integrated Control Diagnostic CodesNormal operation 5 seconds after fault recovered Furnace / air handler. Clears after fault recoveredPower at the thermostat. Alert stops all services Equipment is unable to communicate. IndicatesReconfigure the system. Replace control if heating Missioning and Execute ’Set Factory Default mode’Control will still operate on default parameter set Ate feature will be set as ’installed’ and that couldLow pressure switch failed open Sumes normal operation after fault is clearedFault is cleared Tion after fault is clearedOpen or not within specifications −hour soft lock Out. Clears when flame has been proven stableSoft lockout or reset To flame failurePair/add duct. Cleared after the current service de Is not running. Check power to outdoor unit. ClearsError after current is sensed in both RUN Vice is removed, or after power resetSor run cycle, or after power reset Program Unit Capacity/Size Mode FinishedTroubleshooting Heating Sequence of Operation Call for FIRST−STAGE HeatCall for SECOND−STAGE Heat Call for Heat SatisfiedCall for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE Heat 2ND Stage HeatTroubleshooting Cooling Sequence of Operation Call for CoolingTroubleshooting Continuous Fan Sequence of Operation Call for FAN