Lennox International Inc Furnace Performance and Specifications for Lennox Models SL280UH090V48B and SL280UH090V60C

Page 43

BLOWER DATA

SL280UH090V60C BLOWER PERFORMANCE (less filter)

BOTTOM RETURN AIR, RETURN AIR FROM BOTH SIDES OR RETURN AIR FROM BOTTOM AND ONE SIDE 0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

HEATING

1 Heating Speed

 

 

 

 

 

 

 

 

 

 

 

DIP Switch

 

First Stage Heating Speed - cfm

 

 

Second Stage Heating Speed - cfm

 

Settings

 

 

 

 

 

 

 

 

 

 

 

+24%

 

1420

 

 

 

1565

 

 

+18%

 

1355

 

 

 

1490

 

 

+12%

 

1285

 

 

 

1415

 

 

+6%

 

1215

 

 

 

1335

 

 

Factory Default

 

1145

 

 

 

1260

 

 

–6%

 

1080

 

 

 

1185

 

 

–12%

 

1010

 

 

 

1110

 

 

–18%

 

940

 

 

 

1035

 

 

 

 

 

COOLING

 

 

 

 

 

 

1 Cooling Speed

 

First Stage Cooling Speed - cfm

 

 

Second Stage Cooling Speed - cfm

 

DIP Switch

Low

Medium-Low

Medium-High

 

2 High

Low

 

Medium-Low

Medium-High

 

2 High

Settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

1110

1205

1420

 

1680

1575

 

1740

2000

 

2305

Factory Default

1005

1100

1280

 

1545

1440

 

1595

1820

 

2125

890

1015

1125

 

1380

1295

 

1450

1610

 

1930

SINGLE SIDE RETURN AIR

0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

HEATING

1 Heating Speed

 

 

 

 

 

 

 

 

 

 

 

DIP Switch

 

First Stage Heating Speed - cfm

 

 

Second Stage Heating Speed - cfm

 

Settings

 

 

 

 

 

 

 

 

 

 

 

+24%

 

1360

 

 

 

1500

 

 

+18%

 

1295

 

 

 

1425

 

 

+12%

 

1230

 

 

 

1355

 

 

+6%

 

1165

 

 

 

1280

 

 

Factory Default

 

1100

 

 

 

1210

 

 

–6%

 

1030

 

 

 

1135

 

 

–12%

 

965

 

 

 

1065

 

 

–18%

 

900

 

 

 

990

 

 

 

 

 

COOLING

 

 

 

 

 

 

1 Cooling Speed

 

First Stage Cooling Speed - cfm

 

 

Second Stage Cooling Speed - cfm

 

DIP Switch

 

 

 

 

 

 

 

 

 

 

 

Low

Medium-Low

Medium-High

 

2 High

Low

 

Medium-Low

Medium-High

 

2 High

Settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

1050

1165

1335

 

1620

1515

 

1680

1915

 

2225

Factory Default

955

1060

1215

 

1480

1390

 

1545

1735

 

2060

840

945

1090

 

1290

1220

 

1385

1580

 

1825

1Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch Settings.

2Factory default setting.

NOTES - The effect of static pressure is included in air volumes shown.

First stage HEAT is approximately 91% of the same second stage HEAT.

First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 500 cfm. Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 480 cfm.

Page 43

Image 43
Contents Table of Contents Installation Instructions SL280UHVEither Side Unit Dimensions − inches mmReturn air from both sides Side Return Air OpeningParts Arrangement Access Panel Blower AssemblySight Glass SL280UHV Gas Furnace Safety InformationShipping and Packing List Evaporator Use of Furnace as Construction HeaterGeneral Air Handler UnitCombustion, Dilution & Ventilation Air Space ALL AIR from Inside Equipment in ConfinedEquipment in Confined Space Equipment in Confined Space ALL AIR from OutsideEquipment Confined Space ALL AIR from Outside Bottom Setting EquipmentBlower Motor Rigid LEG Return AIR Base 20 X 25 XFurnace Front Indoor AIRTypical Horizontal Application Horizontal Application Installation Clearances Top LeftRight End BottomDuct System FiltersLeft Side Vent Discharge VentingUpflow Position Top Vent DischargeHorizontal Right Position Horizontal Left PositionSide Vent Discharge Vent Pipe Common Venting Using Metal−Lined Masonry ChimneyDisconnected Vent StickerThrough an unused masonry chimney flue is not considered Vent Connector102 127 −1/2 152 178 10−1/2 MIN MAX Feet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard Every 8 to 10 feet 2.44 to 3.01 m with suitable hang Ers or straps. Install a drip leg in vertical pipe runs to− In some localities, codes may require the installation Gas PipingLeft−Side Air Discharge Horizontal ApplicationRight−Side Air Discharge BOX Interior MAKE−UP BOX InstallationElectrical Electrostatic Discharge ESDCommunicating Non−CommunicatingIcomfortt Integrated Control Outdoor Unit Icomfort Touch Applications NON−COMMUNICATING System WiringCommunicating System Wiring 120V ConnectionsDIP Switch Settings and On−Board Links See figure OFF Single Stage Thermostat w Dual fuel capa Bilities SL280UHV Schematic Wiring Diagram Typical SL280UHV Field Wiring Diagram RS−BUS Link TB82, future use Integrated Control+ = Data High Connection − = Data LOW Connection −10% approx OFF On−Board Links 880 1045985 940SL280UH090V36B Blower Performance less filter 1095 12801220 11551110 12951235 11701100 13601230 11651380 12901225 1160+18% 1605 SL280UH110V60C Blower Performance less filter +18% 1785 SL280UH135V60D Blower Performance less filter Operating Sequence Thermostat energizes Y2 CompressorHoneywell GAS Valve For Your Safety Read Before LightingUnit Start−Up White Rodgers GAS ValveDial Gas Pressure AdjustmentGAS Meter Clocking Chart Proper CombustionHigh Altitude Heating Sequence of Operation Other Unit AdjustmentsHeating Operation with Single Stage Thermostat Heating Operation with TWO−STAGE ThermostatSEC Electrical SHOCK, Fire Or Explosion Hazard Service17− Reinstall burner box, manifold assembly and burner box SL280UHV BURNER, Combustion AIR Inducer Assembly13− To clean the combustion air inducer visually inspect 11− Back wash using steam. Begin from the burner openingSL280UHV NOX Inserts Repair Parts List Planned ServiceIntegrated Control Diagnostic Codes Integrated Control Diagnostic ModesEquipment is unable to communicate. Indicates Normal operation 5 seconds after fault recoveredFurnace / air handler. Clears after fault recovered Power at the thermostat. Alert stops all servicesAte feature will be set as ’installed’ and that could Reconfigure the system. Replace control if heatingMissioning and Execute ’Set Factory Default mode’ Control will still operate on default parameter setTion after fault is cleared Low pressure switch failed openSumes normal operation after fault is cleared Fault is clearedTo flame failure Open or not within specifications −hour soft lockOut. Clears when flame has been proven stable Soft lockout or resetVice is removed, or after power reset Pair/add duct. Cleared after the current service deIs not running. Check power to outdoor unit. Clears Error after current is sensed in both RUNSor run cycle, or after power reset Finished Program Unit Capacity/Size ModeCall for FIRST−STAGE Heat Troubleshooting Heating Sequence of OperationCall for Heat Satisfied Call for SECOND−STAGE Heat2ND Stage Heat Call for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE HeatCall for Cooling Troubleshooting Cooling Sequence of OperationCall for FAN Troubleshooting Continuous Fan Sequence of Operation