Lennox International Inc SL280UH070V36A Use of Furnace as Construction Heater, General

Page 5

Temperature Rise

NOTE − Furnace must be adjusted to obtain a temperature rise(high and low fire) within the range(s) specified on the unit nameplate. Failure to do so may cause erratic limit operation and may result in premature heat exchanger failure.

This SL280UHV furnace must be installed so that its elec- trical components are protected from water.

Installed in Combination with a Cooling Coil

When this furnace is used with cooling units, it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compartment. See figure 1. With a parallel flow arrangement, a damper (or other means to control the flow of air) must adequately pre- vent chilled air from entering the furnace. If the damper is manually operated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT or COOL setting. See figure 1.

Heating Unit Installed Parallell to Air Handler Unit

Dampers

(open during heating operation only)

Gas Unit

Air Handler Unit

Dampers

(open during cooling operation only)

Heating Unit Installed Upstream of Cooling Unit

Gas Unit

Evaporator

FIGURE 1

When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Elec- tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following ad- dress:

National Fire Protection Association

1 Battery March Park

Quincy, MA 02269

NOTE − This furnace is designed for a minimum continu- ous return air temperature of 60°F (16°C) or an intermit- tent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air tem- perature must not exceed 85°F (29°C) dry bulb.

The SL280UHV furnace may be installed in alcoves, clos- ets, attics, basements, garages, and utility rooms in the up- flow or horizontal position.

This furnace is not designed for installation in mobile homes, recreational vehicles, or outdoors.

Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection.

Use of Furnace as Construction Heater

Lennox does not recommend the use of SL280UHV units as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors and op- eration of the unit with clogged or misplaced filters will dam- age the unit.

SL280UHV units may be used for heating of buildings or structures under construction, if the following conditions are met:

D The vent system must be permanently installed per these installation instructions.

DA room thermostat must control the furnace. The use of fixed jumpers that will provide continuous heating is not allowed.

DThe return air duct must be provided and sealed to the furnace.

DReturn air temperature range between 60°F (16°C) and 80°F (27°C) must be maintained.

DAir filters must be installed in the system and must be maintained during construction.

DAir filters must be replaced upon construction comple- tion.

DThe input rate and temperature rise must be set per the furnace rating plate.

DOne hundred percent (100%) outdoor air must be pro- vided for combustion air requirements during construc- tion. Temporary ducting may supply outdoor air to the furnace. Do not connect duct directly to the furnace. Size the temporary duct following these instructions in section for Combustion, Dilution and Ventilation Air in a confined space with air from outside.

DThe furnace heat exchanger, components, duct system, air filters and evaporator coils must be thoroughly cleaned following final construction clean−up.

DAll furnace operating conditions (including ignition, in- put rate, temperature rise and venting) must be verified according to these installation instructions.

General

These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.

In addition to the requirements outlined previously, the fol- lowing general recommendations must be considered when installing a SL280UHV furnace:

Page 5

Image 5
Contents Table of Contents Installation Instructions SL280UHVReturn air from both sides Unit Dimensions − inches mmSide Return Air Opening Either SideSight Glass Access Panel Blower AssemblyParts Arrangement Shipping and Packing List Safety InformationSL280UHV Gas Furnace General Use of Furnace as Construction HeaterAir Handler Unit EvaporatorCombustion, Dilution & Ventilation Air Space ALL AIR from Inside Equipment in ConfinedEquipment Confined Space ALL AIR from Outside Equipment in Confined Space ALL AIR from OutsideEquipment in Confined Space Blower Motor Rigid LEG Setting EquipmentBottom Furnace Front 20 X 25 XIndoor AIR Return AIR BaseRight Horizontal Application Installation Clearances Top LeftEnd Bottom Typical Horizontal ApplicationDuct System FiltersUpflow Position VentingTop Vent Discharge Left Side Vent DischargeSide Vent Discharge Horizontal Left PositionHorizontal Right Position Disconnected Vent Common Venting Using Metal−Lined Masonry ChimneySticker Vent PipeThrough an unused masonry chimney flue is not considered Vent Connector102 127 −1/2 152 178 10−1/2 MIN MAX Feet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard − In some localities, codes may require the installation Ers or straps. Install a drip leg in vertical pipe runs toGas Piping Every 8 to 10 feet 2.44 to 3.01 m with suitable hangRight−Side Air Discharge Horizontal ApplicationLeft−Side Air Discharge Electrical Interior MAKE−UP BOX InstallationElectrostatic Discharge ESD BOXCommunicating Non−CommunicatingIcomfortt Integrated Control Outdoor Unit Icomfort Touch Communicating System Wiring NON−COMMUNICATING System Wiring120V Connections ApplicationsDIP Switch Settings and On−Board Links See figure OFF Single Stage Thermostat w Dual fuel capa Bilities SL280UHV Schematic Wiring Diagram Typical SL280UHV Field Wiring Diagram + = Data High Connection − = Data LOW Connection Integrated ControlRS−BUS Link TB82, future use −10% approx OFF On−Board Links 985 1045940 880SL280UH090V36B Blower Performance less filter 1220 12801155 10951235 12951170 11101230 13601165 11001225 12901160 1380+18% 1605 SL280UH110V60C Blower Performance less filter +18% 1785 SL280UH135V60D Blower Performance less filter Operating Sequence Thermostat energizes Y2 CompressorUnit Start−Up For Your Safety Read Before LightingWhite Rodgers GAS Valve Honeywell GAS ValveGAS Meter Clocking Chart Gas Pressure AdjustmentProper Combustion DialHigh Altitude Heating Sequence of Operation Other Unit AdjustmentsSEC Heating Operation with TWO−STAGE ThermostatHeating Operation with Single Stage Thermostat Electrical SHOCK, Fire Or Explosion Hazard Service13− To clean the combustion air inducer visually inspect SL280UHV BURNER, Combustion AIR Inducer Assembly11− Back wash using steam. Begin from the burner opening 17− Reinstall burner box, manifold assembly and burner boxSL280UHV NOX Inserts Repair Parts List Planned ServiceIntegrated Control Diagnostic Codes Integrated Control Diagnostic ModesFurnace / air handler. Clears after fault recovered Normal operation 5 seconds after fault recoveredPower at the thermostat. Alert stops all services Equipment is unable to communicate. IndicatesMissioning and Execute ’Set Factory Default mode’ Reconfigure the system. Replace control if heatingControl will still operate on default parameter set Ate feature will be set as ’installed’ and that couldSumes normal operation after fault is cleared Low pressure switch failed openFault is cleared Tion after fault is clearedOut. Clears when flame has been proven stable Open or not within specifications −hour soft lockSoft lockout or reset To flame failureIs not running. Check power to outdoor unit. Clears Pair/add duct. Cleared after the current service deError after current is sensed in both RUN Vice is removed, or after power resetSor run cycle, or after power reset Finished Program Unit Capacity/Size ModeCall for FIRST−STAGE Heat Troubleshooting Heating Sequence of OperationCall for Heat Satisfied Call for SECOND−STAGE Heat2ND Stage Heat Call for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE HeatCall for Cooling Troubleshooting Cooling Sequence of OperationCall for FAN Troubleshooting Continuous Fan Sequence of Operation