TABLE 11
SL280 Field Wiring Applications With Conventional Thermostat
| DIP Switch Settings and On−Board Links (See figure 34) |
|
|
| |
| DIP Switch 1 | On Board Links Must Be Cut To Select |
|
|
|
Thermostat | Thermostat |
| Wiring Connections | ||
System Options |
| ||||
| Heating |
|
|
| |
|
|
|
|
| |
| Stages |
|
|
|
|
1 Heat / 1 Cool | ON |
| S1 | FURNACE | OUTDOOR |
NOTE − Use DIP |
|
| T’STAT | TERM. STRIP | UNIT |
|
|
|
|
| |
switch 2 to set |
|
|
|
|
|
second−stage |
|
|
|
|
|
heat ON delay. |
| DO NOT CUT ANY |
|
|
|
OFF−7 minutes. |
| ON−BOARD LINKS |
|
| * |
|
|
|
| ||
ON−12 minutes. |
|
|
|
|
|
1 Heat / 2 Cool | ON | S1 | FURNACE | OUTDOOR |
NOTE − Use DIP |
| T’STAT | TERM. STRIP | UNIT |
|
|
|
| |
switch 2 to set |
|
|
|
|
second−stage |
|
|
|
|
heat ON delay. |
| CUT ON−BOARD LINK |
| * |
OFF−7 minutes. |
| W915 |
| |
| 2 STAGE |
| ||
ON−12 minutes. |
|
|
| |
| COMPR |
|
|
1 Heat / 2 Cool | ON | CUT ON−BOARD LINK | S1 | FURNACE | OUTDOOR |
with t’stat with |
| T’STAT | TERM. STRIP | UNIT | |
| W915 | ||||
humidity control |
| 2 STAGE |
|
|
|
| COMPR |
|
|
| |
|
|
|
|
| |
NOTE − Use DIP |
|
|
|
|
|
switch 2 to set |
|
|
|
| * |
second−stage |
|
|
|
| |
heat ON delay. |
|
|
|
|
|
OFF−7 minutes. |
| CUT ON−BOARD LINK |
|
|
|
| W914 |
|
|
| |
ON−12 minutes. |
|
|
|
| |
| DEHUM |
|
|
| |
|
| OR |
|
|
|
|
| HARMONY |
|
|
|
|
|
|
| o |
|
* Not required on all units.
Page 29