Page 19

TABLE 4

Capacity of Type B Double−Wall Vents with Single−Wall Metal Connectors

Serving a Single Category I Appliance

 

 

 

 

 

Vent and Connector Diameter − D (inches)

 

 

 

Height

Lateral

 

 

 

 

 

 

 

 

 

 

 

 

 

3 Inch

 

4 Inch

 

5 Inch

 

6 Inch

H

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Appliance Input Rating in Thousands of Btu Per Hour

 

 

 

(feet)

(feet)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MIN

 

MAX

MIN

 

MAX

MIN

 

MAX

MIN

 

MAX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

38

 

77

59

 

151

85

 

249

126

 

373

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

39

 

51

60

 

96

85

 

156

123

 

231

6

 

 

 

 

 

 

 

 

 

 

 

 

 

4

NR

 

NR

74

 

92

102

 

152

146

 

225

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

NR

 

NR

83

 

89

114

 

147

163

 

220

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

37

 

83

58

 

164

83

 

273

123

 

412

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

39

 

56

59

 

108

83

 

176

121

 

261

8

 

 

 

 

 

 

 

 

 

 

 

 

 

5

NR

 

NR

77

 

102

107

 

168

151

 

252

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

NR

 

NR

90

 

95

122

 

161

175

 

243

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

37

 

87

57

 

174

82

 

293

120

 

444

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

39

 

61

59

 

117

82

 

193

119

 

287

10

 

 

 

 

 

 

 

 

 

 

 

 

 

5

52

 

56

76

 

111

105

 

185

148

 

277

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

NR

 

NR

97

 

100

132

 

171

188

 

261

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

36

 

93

56

 

190

80

 

325

116

 

499

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

38

 

69

57

 

136

80

 

225

115

 

337

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

5

51

 

63

75

 

128

102

 

216

144

 

326

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

NR

 

NR

95

 

116

128

 

201

182

 

308

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

NR

 

NR

NR

 

NR

158

 

186

220

 

290

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

35

 

96

54

 

200

78

 

346

114

 

537

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

37

 

74

56

 

148

78

 

248

113

 

375

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

50

 

68

73

 

140

100

 

239

141

 

363

20

 

 

 

 

 

 

 

 

 

 

 

 

 

10

NR

 

NR

93

 

129

125

 

223

177

 

344

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

NR

 

NR

NR

 

NR

155

 

208

216

 

325

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

NR

 

NR

NR

 

NR

186

 

192

254

 

306

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

34

 

99

53

 

211

76

 

372

110

 

584

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

37

 

80

55

 

164

76

 

281

109

 

429

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

49

 

74

72

 

157

98

 

271

136

 

417

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

10

NR

 

NR

91

 

144

122

 

255

171

 

397

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

NR

 

NR

115

 

131

151

 

239

208

 

377

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

NR

 

NR

NR

 

NR

181

 

223

246

 

357

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

NR

 

NR

NR

 

NR

NR

 

NR

NR

 

NR

NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maxi- mum listed capacity).

Page 19

Image 19
Contents Table of Contents Installation Instructions SL280UHVEither Side Unit Dimensions − inches mmReturn air from both sides Side Return Air OpeningParts Arrangement Access Panel Blower AssemblySight Glass SL280UHV Gas Furnace Safety InformationShipping and Packing List Evaporator Use of Furnace as Construction HeaterGeneral Air Handler UnitCombustion, Dilution & Ventilation Air Space ALL AIR from Inside Equipment in ConfinedEquipment in Confined Space Equipment in Confined Space ALL AIR from OutsideEquipment Confined Space ALL AIR from Outside Bottom Setting EquipmentBlower Motor Rigid LEG Return AIR Base 20 X 25 XFurnace Front Indoor AIRTypical Horizontal Application Horizontal Application Installation Clearances Top LeftRight End BottomDuct System FiltersLeft Side Vent Discharge VentingUpflow Position Top Vent DischargeHorizontal Right Position Horizontal Left PositionSide Vent Discharge Vent Pipe Common Venting Using Metal−Lined Masonry ChimneyDisconnected Vent StickerThrough an unused masonry chimney flue is not considered Vent Connector102 127 −1/2 152 178 10−1/2 MIN MAX Feet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard Every 8 to 10 feet 2.44 to 3.01 m with suitable hang Ers or straps. Install a drip leg in vertical pipe runs to− In some localities, codes may require the installation Gas PipingLeft−Side Air Discharge Horizontal ApplicationRight−Side Air Discharge BOX Interior MAKE−UP BOX InstallationElectrical Electrostatic Discharge ESDCommunicating Non−CommunicatingIcomfortt Integrated Control Outdoor Unit Icomfort Touch Applications NON−COMMUNICATING System WiringCommunicating System Wiring 120V ConnectionsDIP Switch Settings and On−Board Links See figure OFF Single Stage Thermostat w Dual fuel capa Bilities SL280UHV Schematic Wiring Diagram Typical SL280UHV Field Wiring Diagram RS−BUS Link TB82, future use Integrated Control+ = Data High Connection − = Data LOW Connection −10% approx OFF On−Board Links 880 1045985 940SL280UH090V36B Blower Performance less filter 1095 12801220 11551110 12951235 11701100 13601230 11651380 12901225 1160+18% 1605 SL280UH110V60C Blower Performance less filter +18% 1785 SL280UH135V60D Blower Performance less filter Operating Sequence Thermostat energizes Y2 CompressorHoneywell GAS Valve For Your Safety Read Before LightingUnit Start−Up White Rodgers GAS ValveDial Gas Pressure AdjustmentGAS Meter Clocking Chart Proper CombustionHigh Altitude Heating Sequence of Operation Other Unit AdjustmentsHeating Operation with Single Stage Thermostat Heating Operation with TWO−STAGE ThermostatSEC Electrical SHOCK, Fire Or Explosion Hazard Service17− Reinstall burner box, manifold assembly and burner box SL280UHV BURNER, Combustion AIR Inducer Assembly13− To clean the combustion air inducer visually inspect 11− Back wash using steam. Begin from the burner openingSL280UHV NOX Inserts Repair Parts List Planned ServiceIntegrated Control Diagnostic Codes Integrated Control Diagnostic ModesEquipment is unable to communicate. Indicates Normal operation 5 seconds after fault recoveredFurnace / air handler. Clears after fault recovered Power at the thermostat. Alert stops all servicesAte feature will be set as ’installed’ and that could Reconfigure the system. Replace control if heatingMissioning and Execute ’Set Factory Default mode’ Control will still operate on default parameter setTion after fault is cleared Low pressure switch failed openSumes normal operation after fault is cleared Fault is clearedTo flame failure Open or not within specifications −hour soft lockOut. Clears when flame has been proven stable Soft lockout or resetVice is removed, or after power reset Pair/add duct. Cleared after the current service deIs not running. Check power to outdoor unit. Clears Error after current is sensed in both RUNSor run cycle, or after power reset Finished Program Unit Capacity/Size ModeCall for FIRST−STAGE Heat Troubleshooting Heating Sequence of OperationCall for Heat Satisfied Call for SECOND−STAGE Heat2ND Stage Heat Call for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE HeatCall for Cooling Troubleshooting Cooling Sequence of OperationCall for FAN Troubleshooting Continuous Fan Sequence of Operation