6 − The entire length of single wall metal vent connector shall be readily accessible for inspection, cleaning, and replacement.
7 − Single appliance venting configurations with zero lat- eral lengths (tables 3 and 4) are assumed to have no elbows in the vent system. For all other vent configura- tions, the vent system is assumed to have two 90° el- bows. For each additional 90° elbow or equivalent (for example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10% (0.90 x maximum listed ca- pacity).
8 − The common venting tables (5, 6, 7, and 8) were gen- erated using a maximum horizontal vent connector length of 1−1/2 feet (.46 m) for each inch (25 mm) of connector diameter as follows:
TABLE 2
Connector Diameter | Maximum Horizontal |
inches (mm) | Connector Length feet (m) |
|
|
|
|
3 (76) | 4−1/2 (1.37) |
|
|
4 (102) | 6 (1.83) |
|
|
5 (127) | 7−1/2 (2.29) |
|
|
6 (152) | 9 (2.74) |
|
|
7 (178) | 10−1/2 (3.20) |
9 − If the common vertical vent is offset, the maximum common vent capacity listed in the common venting tables should be reduced by 20%, the equivalent of two 90° elbows (0.80 x maximum common vent capacity). The horizontal length of the offset shall not exceed
10− The vent pipe should be as short as possible with the least number of elbows and angles required to com- plete the job. Route the vent connector to the vent us- ing the shortest possible route.
11− A vent connector shall be supported without any dips or sags and shall slope a minimum of 1/4 inch (6.4 mm) per linear foot (305 mm) of connector, back toward the appliance.
12− Vent connectors shall be firmly attached to the furnace
flue collar by self−drilling screws or other approved means, except vent connectors of listed type B vent material which shall be assembled according to the manufacturer’s instructions. Joints between sections of single wall connector piping shall be fastened by screws or other approved means.
13 − When the vent connector used for Category I ap- pliances must be located in or pass through a crawl- space, attic or other areas which may be cold, that por- tion of the vent connector shall be constructed of listed
14 − All venting pipe passing through floors, walls, and ceil- ings must be installed with the listed clearance to com- bustible materials and be fire stopped according to lo- cal codes. In absence of local codes, refer to NFGC (Z223.1).
15 − No portion of the venting system can extend into, or pass through any circulation air duct or plenum.
16 − Vent connectors serving Category I appliances shall not be connected to any portion of mechanical draft systems operating under positive pressure such as Category III or IV venting systems.
17 − If vent connectors are combined prior to entering the common vent, the maximum common vent capacity listed in the common venting tables must be reduced by 10%, the equivalent of one 90° elbow (0.90 x maximum common vent capacity).
18 − The common vent diameter must always be at least as large as the largest vent connector diameter.
19 − In no case, shall the vent connector be sized more than two consecutive table size diameters over the size of the draft hood outlet or flue collar outlet.
20 − Do not install a manual damper, barometric draft regu- lator or flue restrictor between the furnace and the chimney.
21 − When connecting this appliance to an existing dedi- cated or common venting system, you must inspect the venting system’s general condition and look for signs of corrosion. The existing vent pipe size must conform to these instructions and the provided venting tables. If the existing venting system does not meet these re- quirements, it must be resized.
Page 17