Troubleshooting: Heating Sequence of Operation (Continued)
CALL FOR SECOND−STAGE HEAT
2
| CALL FOR 2ND STAGE HEAT | 1 |
|
| ||
|
| (HIGH FIRE) |
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 2 STAGE THERMOSTAT | |||
|
|
|
| |
|
|
|
| |
| RECOGNITION DELAY | |||
|
| (30 SECONDS) | ||
ONLY FOR 1ST EXPIRED? | ||||
REQUEST FOR |
|
|
| |
2ND STAGE HEAT |
| YES |
| |
|
| |||
|
|
|
|
SINGLE STAGE THERMOSTAT 2
2ND STAGE ON DELAY EXPIRED?
YES
INDUCER SWITCHED
TO HIGH SPEED
HIGH |
|
|
|
|
|
|
|
PRESSURE SWITCH |
|
|
|
| INDUCER SWITCHED |
|
|
| NO |
|
| ||||
CLOSED WITHIN 10 |
|
|
| TO LOW SPEED |
| ||
|
|
|
|
| |||
SECONDS? |
|
|
|
|
|
|
|
YES
2ND STAGE GAS VALVE
ENERGIZED
INDOOR BLOWER ENERGIZED
ON HIGH HEAT SPEED
3
CALL FOR HEAT SATISFIED
5 MINUTE DELAY | 3 |
(ERROR CODE FLASHES) |
1SYSTEM WILL ALWAYS LIGHT ON LOW FIIRE, EVEN IF 2ND STAGE HEAT IS IN PLACE.
2WHEN USED WITH A SINGLE STAGE THERMOSTAT, SET SW1 TO THE ON POSITION IN DIP SWITCH S4.
3IF THE HIGH FIRE PRESSURE SWITCH DOES NOT CLOSE WITHIN 5 ATTEMPTS, THE SYSTEM WILL OPERATE AT LOW FIRE FOR THE REMAINDER OF THE CALL FOR HEAT REQUEST.
Page 69